Laserfiche WebLink
Spill Bucket Testing Report <br /> 1. FACILITY INFORMATION <br /> Facility Name: MAIN STREET ARCO AM PM Date of Testing: 03/12/2020 <br /> Facility Address: 1100 S Main St Manteca,CA 95337 <br /> Facility Contact: Jesse I Phone: (209)609-0117 <br /> 2. TESTING CONTRACTOR INFORMATION <br /> Company Name: Diamond Petroleum Services, Inc. <br /> Technician Conducting Test: Guadalupe Sanchez <br /> Contractor License# 1005444 ICC Certification #5250451 <br /> 3. SPILL BUCKET TESTING INFORMATION <br /> Test Method Used: Hydrostatic <br /> Test Equipment Used: Standard Tape Measure Equipment Resolution: 1'16" <br /> Identify Spill Bucket (la), Tank TI: 87 M West Fill TI: 87 M Gast Fill T2: 87 91 Fill T3: 89 Fill <br /> Number, Stored Product, etc. <br /> Bucket Installation Type: Direct Bury Direct Bury Direct Bury Direct Bury <br /> x Contained in Sump x Contained in Sump x Contained in Sump x Contained in Sum <br /> Bucket Inside Diameter: III, l l" 1 I" III, <br /> Bucket Depth: 13 ''4" 14'/4" 14 V 14'/4" <br /> Wait time between applying 5 minutes 5 minutes 5 minutes 5 minutes <br /> vacuum/water and start of test: <br /> Test Start Time(Ti): 3:30 p.m. 9:45 a.m. 9:45 a.m. 9:45 a.m. <br /> Initial Reading(Ri): 11 '/4" 11 '/4" 11 '/4" 113/8" <br /> Test End Time(TF): 4:30 p.m. 10:45 a.m. 10:45 a.m. 10:45 a.m. <br /> Final Reading(RF): 11 %11 11 '/4" 11 %" 113/8" <br /> Test Duration(TF—Ti): 1 hr 1 hr 1 hr 1 hr <br /> Change in Reading(RF-R,): 0 0 0 0 <br /> Pass/Fail Threshold or 1/8" 1/8" 1/81, 1/8" <br /> Criteria: <br /> Test Result: x Pass ❑ Fail x Pass 0 Fail x Pass ❑ Fail x Pass ❑ Fail <br /> Comments: The 87 M West spill bucket was replaced "like for like". Inspector on site <br /> Technician's Signature--� Date: 03/12/2020 <br />