Laserfiche WebLink
(ry PEI/RP1200-17 <br /> 6.2.2 Description of Test. The spill bucket is <br /> 65° SPILL BUCKET AND filled with water.The water level is measured at the <br /> CONTAINMENT SUMP beginning and end of the test. <br /> TESTING 6.2.3 Test Equipment. Test equipment shall <br /> include: <br /> 6.1 General. Spill buckets and containment sumps for ° water; <br /> tank systems are neither intended nor designed for the <br /> storage of petroleum products,but rather to contain small measuring stick that f accurate to within 1/16 <br /> leaks and spills for short periods of time. This section (0.063) inch and of sufficient length; <br /> describes the procedures used to test the integrity of spill ° plumber's plug (appropriate size, if used); <br /> buckets and containment sumps to ensure that they do not <br /> leak. ° stopwatch or other time-measurement device <br /> capable of measuring a 1-second increment. <br /> 6.2 Shill Bucket Integrity Testing — Hydrostatic <br /> Test Method. 6.2.4 Preparation. <br /> - 1. Care should be taken when conducting the test <br /> C^ff:�L';tVt911V`SCio Do not use fuels such as gaso- in the rain or during freezing weather condi- <br /> line, E85 or diesel as a test fluid because tions. <br /> they present a serious fire and safety 2.Remove and properly dispose of any liquid and <br /> hazard. Gasoline vapors are flammable debris (leaves, sediment and trash) in the spill <br /> and can explode If exposed to an Ignition bucket. Clean the spill bucket and examine it for <br /> source such as a spark or open flame. If damage, defects or improperly installed compo- <br /> a tank or containment area Is not tight, nents. If there are loose components (e.g., loose <br /> using fuel as the test fluid will cause a band clamps or bolts),tighten these items before <br /> release Into the soil or groundwater. conducting the integrity test. If there are items <br /> - "-" that must be repaired or replaced (e.g., deterio- <br /> 6.2.1 Purpose. This method is used to test the rated gaskets/seals or drain valves), notify the <br /> integrity of single-walled spill buckets or the pri- owner/operator. <br /> mary containment of secondarily contained spill 3.Examine the fill cap and adapter fitting for <br /> buckets. loose, missing or damaged parts, and make <br /> necessary repairs. Complete any repairs before <br /> putting water in the spill bucket. Make sure that <br /> the seal on the fill cap is present and in good <br /> condition.The cap must fit securely and be leak- <br /> water Level tight on the riser.The water level during the test <br /> typically will be above the cap, so a leaking cap <br /> will result in a failed test. As an alternative to <br /> _ a tight-fill cap, use a plumber's plug in the fill <br /> riser if approved by the authority having juris- <br /> diction (AHJ) and tank owner. <br /> 4.The spill bucket drain valve, if present, must <br /> be leak-tight to pass the test. If it is not leak- <br /> tight, it may be possible to simply remove and <br /> permanently plug the drain valve, However, if <br /> you choose to permanently plug,ensure that the <br /> local regulations allow this modification. <br /> FIGURE 64. The hydrostatic method of determining 5.If the spill bucket is found to have cracks, loose <br /> spill bucket integrity uses water to detect leaks. The <br /> measuring stick must be placed in the same location parts or separation of the bucket from the fill <br /> at the beginning and end of the test period to ensure pipe, it is not considered to be liquid-tight. This <br /> accurate water level readings. visually indicates a test failure. <br /> pei.org <br />