Laserfiche WebLink
DYNAMIC BACK PRESSURE TEST DATA (BLOCKAGE) TECHNICIAN: FELIX RAMIREZ <br /> Cert#0099 <br /> Site: ARCO STOCKTON Date: 11/12/2019 Time: 1030 <br /> Nozz/Fuel 20 CFH 60 CFH 80 CFH PASS/FAIL Nozz/Fuel 20 CFH 60 CFH 80 CFH PASS/FAIL <br /> Grade (.15"Water) (.35"Water) (.62"Water) Grade (.15"Water) (.35"Water) (.62"Water) <br /> 1 ALL .30 .44 PASS 2 All .23 .35 PASS <br /> 3 ALL .23 .44 PASS 4 ALL .25 .39 PASS <br /> 5 ALL .25 .44 PASS 6 ALL .23 .39 PASS <br /> 7 ALL .25 .40 PASS 8 ALL .25 .44 PASS <br /> 9 ALL .25 .42 PASS 10 ALL .26 .54 PASS <br /> 11 ALL .24 .40 PASS 12 ALL .23 .35 PASS <br /> L----L -------- L L----L----L------- <br /> LIQUID REMOVAL CHECK **See Long Form Test Report for wet Failure Testing I Blockage Tester Integrity: <br /> D=Dry 1 "w.c. 5 minutes PASS <br /> [-]DRY ❑DRY ❑DRY ❑DRY [-]DRY ❑DRY ❑DRY [-]DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> ❑DRY ❑DRY ❑DRY []DRY ❑DRY ❑DRY ❑DRY ❑DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> ❑DRY ❑DRY ❑DRY ❑DRY [-]DRY ❑DRY ❑DRY [-]DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> [-]DRY ❑DRY ❑DRY ❑DRY [-]DRY ❑DRY ❑DRY [-]DRY ❑DRY <br /> M1 ml ml ml ml ml ml ml ml <br /> ❑ Job Complete Repairs Done to Pass Test: <br /> ❑ I Not Complete Repairs Still Needed: <br /> Parts: None Drop Tube rings Fill Adaptor Gaskets Hoses Whip Hose <br /> Nozzles Breakaways PV Valves Others: <br />