Laserfiche WebLink
STEP 6: APPLY GREASE TO DROP TUBE <br />Apply black moly grease to the inside diameter of the <br />upper drop tube. Make sure coverage is completely <br />around the tube as shown in Figure 6. <br />Figure 6 <br />STEP 7: APPLY GREASE TO POLYPAK SEAL <br />Ensure that the polypak seal is installed on the inlet <br />tube with the lip up as shown in Figure 7. Apply black <br />moly grease to the polypak as shown. Make sure cover- <br />age is completely around the polypak seal. <br />Inlet <br />Figure 7 <br />STEP 8: INSTALL INLETTUBE <br />Ensure polypak <br />lip is up <br />Polypak�, <br />"—Apply grease <br />around polypak <br />Insert the inlet tube into the upper tube until the upper <br />tube seats against the flange on the inlet tube. Ensure <br />polypak is inserted evenly and stays in inlet tube <br />groove. <br />3 <br />Figure 8 <br />NOTE: Testable inlet tube must have cable port in <br />line with float. Testable inlet tube bottoms out on <br />stop, it does not bottom out on inlet flange. See Fig- <br />ure SA <br />Cable port must be in <br />line with float <br />igure 8A <br />'estable Models Only <br />SEE PAGE 8 FOR INSTRUCTIONS USING THE 71 SO - <br />TOOL. <br />SEE PAGE 9 FOR INSTRUCTIONS USING THE 71 SO- <br />TOOLC. <br />SEE PAGE 10 FOR INSTRUCTIONS USING THE 71SO- <br />TOOLCT. <br />Note: testable 71 SO models ending with a "T' require the <br />71 SO-TOOLCT or modified 71 SO -TOOL or 71 SO- TOOLC <br />7 <br />