Laserfiche WebLink
SAN J O A Q U I N Environmental Health Department <br /> COUNTY- <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ESCALON MINI MART 1097 YOSEMITE AVE, ESCALON December 18, 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS ll,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> On the 10/26/18 designated operator(DO)inspection report under <br /> No alarm history was printed during the report <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII through XI. <br /> -Section V <br /> The owner/operator failed to provide explanation of follow-up actions that will be taken for the statement provided by <br /> the DO in section III. <br /> -Section VI <br /> The OWNER/OPERATOR failed to provide a name,signature, and date within 48 hours of receiving the DO report <br /> under the ACKNOWLEDGMENT OF COMPLIANCE ISSUES section. <br /> -Section VII <br /> The DO fail to mark yes or No for the question" Has each follow-up action of section III from the previous inspection <br /> been completed appropriately?' <br /> On the 11/13/18 designated operator(DO)inspection report under <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII through XI. <br /> -Section VI <br /> The OWNER/OPERATOR failed to provide a name,signature, and date within 48 hours of receiving the DO report <br /> under the ACKNOWLEDGMENT OF COMPLIANCE ISSUES section. <br /> -Section VII <br /> The DO fail to mark yes or No for the question"Has each follow-up action of section III from the previous inspection <br /> been completed appropriately?" <br /> The alarm history reports for the1/2/18, 9/24/18, and 10/26/18 inspection reports were not found on site. <br /> The designated operator failed to verify that the alarms from regular sump on 2/2/18, 7/26/18, 12/14/18 and <br /> 12/15/18 Premium sump on 6/7/18 were responded to appropriately. <br /> In the DO report for 7/20/18 the DO marked YES under the question"sensor located in tank top containment sumps <br /> have not alarmed in the past month?"however on 7/15/18 there was a regular sump alarm and it should state NO. <br /> During the monthly inspection,the designated operator shall review the alarm history for the previous month, check <br /> that each alarm was documented and responded to appropriately, and attach a copy of the alarm history with <br /> documentation taken in response to any alarms to the monthly report. Ensure that designated operators performing <br /> inspections at least once every 30 days at this facility and are including all of the required information on the reports. <br /> This is a repeat violation, Class II. <br /> FA0000279 PR0231497 SC001 12/1812018 <br /> EHD 23-01 Rev.09/28/2018 Page 5 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 952051 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />