SWRCB, January 2002 Page of 1 <br /> 6. PIPING SUMP TE, STING <br /> Test Method Developed By: ❑ Sump Manufacturer ❑ Industry Standard X Professional Engineer <br /> ❑ Other (Speer) <br /> Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br /> ❑ Other (Specifj) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> 01111111111111 <br /> Sump # 1-87 Sump # 2-Race 100 Sump # 3»91 Sump # 4-Diesel <br /> Sump Diameter: 42" 42" 42" 42" <br /> Sump Depth: 38 38" 39" 41 " <br /> Sump Material : Fiberglass Fiberglass Fiberglass Fiberglass <br /> Height from Tank Top to Top of 15" 16 16" 15" <br /> Highest Piping Penetration : <br /> Height from Tank Top to Lowest 9„ <br /> 1 <br /> Electrical Penetration; <br /> Condition of sump prior to testing. Dry Dry Dry Dry <br /> Portion of Sump Tested ' Water Level 19" Water Level 20" Water Level 20" Water Level 19" <br /> Does turbine shut down when <br /> sump sensor detects liquid (both Yes Yes Yes Yes <br /> product and water)?* <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail-safe yes Yes Yes Yes <br /> shutdown?' <br /> Was fail-safe verified to be No No No No <br /> operational?* <br /> Wait time between applying water 5 Minutes 5 Minutes 5 Minutes 5 Minutes <br /> and starting test: <br /> Test Start Time: 9 :32 8 :47 9 :42 8 :42 <br /> i <br /> Initial Reading (Rr) : . 001 tool .001 . 001 <br /> Test End Time: 10 : 02 9: 17 10 : 12 9 : 12 <br /> Final Reading (Rr) : tool .001 $001 tool <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading (Rr. Rr) : 0 0 0 0 <br /> Pass/Fall Threshold or Criteria: . 005/30 Minutes . 005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Result: Pass Pass Pass Pass <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced and Yes Yes Yes Yes } <br /> verified functional after testing? <br /> Comments — (include information on repairs made prior to testing, and recommended follow-up fait failed tests) <br /> l <br /> ' If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG - 160) <br />