Laserfiche WebLink
FIBERGLASS PIPING, 2" NOMINAL, BONDED TO SUMP SUMP 2 WIRE <br /> OR UDC INNER WALL USING GASOLINE COMPATIBLE SHIELDED <br /> EPDXY RESIN. BOTTOM OF PIPE TO BE IN CONTACT CABLE <br /> WITH LOWEST PART OF SUMP OR UDC. <br /> SUMP MONITOR LIQUID <br /> CONTRACTOR TO BOND UNISTRUT CHANNEL TO O SENSOR INSIDE <br /> HOLDER TO ALLOW FIBERGLASS PIPE TO CLEAR HOLDER <br /> SUMP COLLAR "LIP". CONTRACTOR TO USE APEX OF <br /> GASOLINE-COMPATIBLE EPDXY TO BOND SPACER TO I TANK <br /> SUMP AND PIPE. CONTRACTOR MAY USE UNISTRUT, ,O <br /> FIBERGLASS PIPE, OR ANY OTHER EQUIVALENT <br /> MATERIAL THAT CAN WITHSTAND ENVIRONMENT OF <br /> SUMP. <br /> TURBINE SIDE SUMP SENSORS TO BE MOUNTED <br /> BELOW APEX OF TANK, AT BOTTOM OF SUMP AT FIBERGLASS <br /> SIDE OF TANK WHERE PRODUCT PENETRATIONS INTO TANK <br /> SUMP ARE MADE AND BELOW LOWEST PENETRATION <br /> FITTING WITHIN SUMP AREA. PRODUCT PIPING TOFIBERGLASS SUMP <br /> DISPENSERS, PRODUCT PIPING CROSS CONNECTION INSIDE TANK COLLAR <br /> BETWEEN SUMPS AND SIPHON PIPING PENETRATIONS LIP <br /> ARE DESIGNED TO ENTER THE SAME SIDE OF THE UNISTRUT 1. SENSOR HOLDER <br /> SUMP AS SHOWN. IF PRODUCT PENETRATION CHANNEL BONDED TO UNISTRUT <br /> ENTERS ON BOTH SIDES OF SUMP DUE TO FIELD CHANNEL <br /> CONDITIONS, THEN DUAL SENSORS AT TURBINE <br /> SUMP WILL BE REQUIRED TO BE INSTALLED. <br /> 2. SENSOR HOLDER <br /> AND UNISTRUT <br /> CHANNEL BONDED TO <br /> SUMP WALL. DO NOT <br /> H: SUMP SENSOR HOLDER DETAILS PENETRATE SUMP! <br /> SCALE: 1" = V-0" <br />