Laserfiche WebLink
AR Rrgr� <br /> SAN J O A Q U I N Environmental Health Department <br /> C0UIq I Y <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name : TFacility Address: Date: <br /> ARCO 05450 1617 W FREMONT ST , STOCKTON July 15 , 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I, CLASS II , or MINOR = Notice to Comply) <br /> Item # Remarks <br /> 204 CCR 2712 ( 1 ) Current monitoring plan approved by the EHD not found on site . <br /> An approved copy of the monitoring plans were not available for inspection . A copy of these plans shall be accessible <br /> on site at all times . Immediately locate and retain a copy on site. <br /> This is a minor violation. <br /> 320 CCR 2635 , 2637 . 2 , 2665 , 2712 Failure to comply with the installation , inspection , or record keeping of the overfill <br /> prevention . <br /> Overfill prevention testing was conducted on 01 /03/ 19 . This testing was required to be conducted by October 13 , <br /> 2018 . Ensure all future testing is conducted within required time frames . <br /> This is a Class II violation . <br /> Overall Inspection Comments : <br /> An inspection report was provided to the facility operator on the day of inspection . The report was amended by <br /> the EHD . The amended report replaces the initial report . <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation , and any supporting <br /> paperwork , by August 14 , 2019 . <br /> Starting September 1 , 2018 , all in- office CERS help will be provided at EHD hourly rate ( $ 152 ) . To schedule an <br /> appointment, please call (209 ) 468 -3420 . <br /> AFTER THE COMPLIANCE DATE , EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING THIS <br /> FACILITY BACK INTO COMPLIANCE . <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD' S CURRENT HOURLY RATE . <br /> Received by : Date: Inspector: Inspector Phone: <br /> Printed Name and Title: PAUL NSO , EHS Trainee (209 ) 468 -3432 <br /> FA0003606 PR0231923 SCO01 07/15/2019 <br /> EHD 23-01 Rev, 09/28/2018 Page 4 of 4 Underground Storage Tank Program OIR <br /> 1868 E . Hazelton Avenue Stockton , California 95205 1 T 209 468-3420 1 F 209 464 -0138 1 www, sjcehd . com <br />