• <br /> Daljit Sabharwal, Vice President <br /> September 4, 2002 <br /> Page 5 <br /> 35. Repair the outer layers etch piping that is damaged and leaking ammonia <br /> hydroxide. This piping shall be welded at the seams and connections. CFC <br /> 8001.4 <br /> 36. Repair the damaged electrical wiring and components that are damaged by the <br /> ammonia leaks. CFC 8504 <br /> 37. Clean up the ammonium hydroxide caked on the motors, electrical lines, and the <br /> floor. There is a major build up of ammonium hydroxide in this unit. CFC 8504, <br /> 8003.1.3 <br /> 38. Provide cover plates for exposed electrical lines in the back of the ammonia line. <br /> CFC 8504 <br /> 39. Clean and repair the flow trench. CFC 8003.1.3.2 <br /> 40. Provide cover plates and repair the exposed and damaged electrical wiring to the <br /> Resis Stripper unit. CFC 8504 <br /> 41. Replace the damaged piping to the Resis Stripper unit. CFC 8001.4 <br /> 42. Replace the damaged and rusted sprinkler heads located in the Wet Process <br /> area. CFC 1001.5.1 <br /> 43. Smoking shall not be allowed in the chemical plating or processing areas. All <br /> smoking shall be outside away from chemical processing or storage. CFC <br /> 1109.4.1 <br /> Manual Plating Room <br /> 1. Provide secondary containment for the caustic barrels in this area. CFC <br /> 8003.1.3.3 <br /> Plating #2 <br /> 1. Repair and clean up the corrosive chemical residue built-up on the rectifiers <br /> structural beams. Some beam and footplate replacement may be necessary. <br /> CFC 8001.4.7 <br /> 2. Repair or replace the piping on the back of the chemical line that is leaking. <br /> Clean up the built-up of corrosive materials. CFC 8001.4.7 <br /> 3. Replace or repair the tank bracing that is severely deteriorated from corrosive <br /> chemicals. CFC 8001.4.7, 8001.4.7 <br /> 4. Replace the damaged piping and strapping. CFC 8001.4.7 <br /> 5. Provide ventilation for the open chemical tanks at all times. Standby power is <br /> required with a secondary power source. CFC 8003.1.8 <br /> 6. Repair the ceiling that is open and covered with a tarp. Remove all wrappings <br /> from sprinkler pipes. Maintain the H-2 occupancy rating of this area. There is an <br /> approximately 8 X 20 foot opening in the ceiling. CFC 1001.5.1, CBC 307.3, <br /> CFC, 1112 <br />