GENERAL NOTES ABBREVIATIONS AND TAGS 4 ELECTRICAL LEGEND 1 <br /> ABB. DESCRIPTION ABB. DESCRIPTION SYMBOL DESCRIPTION <br /> 1. GENERAL CONTRACTOR SHALL VERIFY FIELD CONDITIONS BEFORE SUBMITTING BID. 39. FOR ALL LIGHTING FIXTURES MOUNTED IN SUSPENDED CEILING THE GENERAL CONTRACTOR SHALL ROBISON <br /> 2. ALL WORK SHALL BE DONE IN ACCORDANCE WITH NEC AS AMENDED BY CEC, AND ANY ADDITIONAL PROVIDE AND INSTALL INDIVIDUAL SUPPORT AT EACH CORNER OF RECESSED LIGHTING TROFFER AE APPROVED EQUIVALENT WP WEATHERPROOF <br /> STATE OR LOCAL CODES WHICH MAY APPLY. CONNECTED TO BUILDING STRUCTURE ABOVE ALL CONDUIT AND MC CABLE MOUNTED ABOVE AFF ABOVE FINISHED FLOOR (E) EXISTING TO REMAIN $x SINGLE POLE SINGLE THROW SWITCH, +44" AFF U.O.N. X MEANS: ENGINEERING, INC <br /> SUSPENDED CEILING SHALL BE INDIVIDUALLY SUPPORTED IN THE SAME FASHION AS PER NEC <br /> 3. GENERAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, CERTIFICATES, ETC. REQUIRED. REQUIREMENTS. EF EXHAUST FAN (N) NEW a - CONTROLLING FIXTURE OR OUTLET "a" 1940140TH AVE W..SUITE 302 <br /> WA <br /> 40. NO "DOUBLING UP" ON CIRCUIT BREAKERS OR CONDUCTOR SPLICES WITH IN PANEL BOARDS SHALL BE EC ELECTRICAL CONTRACTOR 2 - DOUBLE POLE LY206-364-334398036 <br /> 06-3364-3 439TEL <br /> 4. GENERAL CONTRACTOR SHALL OBTAIN AND PAY FOR BOTH ROUGH AND FINAL UNDER-WRITERS OR OTHER PERMITTED. THE CONTRACTOR SHALL PROVIDE JUNCTION BOXES ADJACENT TO PANELBOARDS AS NTS NOT TO SCALE <br /> APPROVED INSPECTION AGENCY CERTIFICATES "ELECTRICAL INSPECTION". THESE CERTIFICATES SHALL BE REQUIRED TO SPLICE COMMON CIRCUITS CONNECTORS. PROVIDE FURNISH, INSTALL AND CONNECT. MC MECHANICAL CONTRACTOR 3 - THREE WAY CONTACT:TYLER BEAM <br /> PRESENTED WITH REQUEST FOR FINAL PAYMENT. GC GENERAL CONTRACTOR D - RATING AS REQUIRED <br /> 41. DO NOT SCALE FROM THESE DRAWINGS. GFCI GROUND FAULT CKT. INTERRUPTER DIMMER ( ) <br /> 5. IT IS THE INTENT OF THESE PLANS TO PROVIDE A COMPLETE OPERATING ELECTRICAL SYSTEM. THE AC MECHANICAL UNIT TAG. SEE <br /> CONTRACTOR SHALL FURNISH AND INSTALL ALL WIRING, EQUIPMENT, MATERIAL. ETC. REQUIRED, EXCEPT SMD SEE MECHANICAL DRAWINGS 1 MECHANICAL DRAWINGS FOR ® LOW VOLTAGE SWITCH FOR LIGHTING CONTROL PANEL <br /> 42. PLANS ARE PREPARED WITH REQUIRED BRANCH CIRCUITS INDICATED BY CIRCUITS NUMBERS. PROVIDE R�FESS/p <br /> WHERE SPECIFICALLY NOTED AS BEING FURNISHED BY OTHERS. SHOULD THERE BE ANY QUESTIONS UAC UNDER ANOTHER CONTRACT ADDITIONAL REQUIREMENTS. Q Nq <br /> AND INSTALL ALL CONDUITS. CONDUCTORS BOXES MISCELLANEOUS FITTINGS ETC. FOR A COMPLETE $T DOUBLE OR THREE POLE HP RATED TOGGLE SWITCH �O . LER 9 l <br /> CONCERNING RESPONSIBILITY, THEY SHALL BE ADDRESSED TO ARCHITECT PRIOR TO BID. NO EXTRA UON UNLESS OTHERWISE NOTED E-4 DETAIL TAG. REFER TO DETAIL 4 � � <br /> CHARGES WILL BE ALLOWED. AND OPERABLE SYSTEM (HOME RUN SHOWN). BRANCH CIRCUIT INSTALLATION SHALL COMPLY WITH 4 ON SHEET NUMBER E-4. $OS SWITCH OCCUPANCY SENSOR WITH MANUAL ON/OFF OVERRIDE �<v �• �, <br /> SPECIFICATIONS AND N.E.C. (R) (E) TO BE REMOVED BUTTON c z <br /> 6. ELECTRICAL SERVICE SHALL BE COORDINATED WITH THE EXISTING FIELD CONDITIONS. 43. IN COMPLIANCE WITH STATE TITLE 24 ACCESSIBILITY REQUIREMENTS, 406.3(G), THE BOTTOM OF (RL) (E) TO BE RELOCATED o0o EQUIPMENT UNIT TAG, PC PHOTOCELL FOR DAYLIGHT ZONING w No. E-21545 m <br /> 7. CONSULT WITH CONTRACTORS FURNISHING HVAC EQUIPMENT AND REFRIGERATION TO VERIFY LOADS AND RECEPTACLE OUTLETS SHALL NOT BE LESS THAN 15"AFF. THE TOP OF SWITCHES AND OTHER DEVICES (RR) (E) TO BE REMOVED AND SEE EQUIPMENT SCHEDULE. O x� <br /> SECURE EXACT LOCATIONS REFER TO HVAC DRAWINGS). WIRE AND CONNECT TO ALL HVAC EQUIPMENT. SMOKE DETECTOR <br /> ( ) SHALL BE NOT MORE THAN 48"AFF OR 44"AFF IF REACHING OVER OBJECT EXCEEDING 20" DEEP. REINSTALLED ELECTRICAL LIGHTING EQUIPMENT S F< GPS' �Q <br /> £CTR\ � <br /> INCLUDING CONTROLS AND THERMOSTATS. LCP LIGHTING CONTROL PANEL qT � <br /> 44. NATIONALLY RECOGNIZED TESTING LABORATORY SHALL LIST ALL EQUIPMENT IN COMPLIANCE WITH NEC a UNIT TAG/TYPE 1UH DIMMEST ACCESSIBLE TYPE CONTROL COMPATIBLE WITH FIXTURE F OF CAS\F� <br /> 8. CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO ALL CONTROLS, OWNER-SUPPLIED EQUIPMENT, ART. 110.3. SEE LIGHT FIXTURE SCHEDULE. Seal <br /> MECHANICAL AND PLUMBING EQUIPMENT AS REQUIRED. DUPLEX RECEPTACLE 20A, 125V, NEMA 5-20R WALL MOUNTED. <br /> 9. REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATION DETAILS. ALL FIXTURE AND DEVICE LOCATIONS 45. ALL EQUIPMENT LISTED IN SCHEDULES SHALL BE PROVIDED WITH REQUIRED POWER CONNECTION, U.O.N. (WP= WEATHERPROOF, D= DEDICATED, GFI=GROUND FAULT <br /> SHOWN ON ARCHITECTURAL DRAWINGS SUPERSEDE THOSE SHOWN ON ELECTRICAL PLANS. INTERRUPTER) bp <br /> 46. ELECTRICAL CONTRACTOR SHALL FOLLOW LOCK OUT/TAG OUT PROCEDURE PER CAL-OSHA STANDARDS <br /> 10. CIRCUIT NUMBER ON THE DRAWINGS ARE FOR IDENTIFICATION ONLY AND DO NOT INDICATE THE POSITION DURING CONSTRUCTION. DUPLEX RECEPTACLES 20A, 125V, NEMA 5-20R HALF SWITCHED. <br /> ON THE PANEL BOARD. CONNECT THE CIRCUITS WITH THE LIGHTEST LOADS AND THE RECEPTACLE <br /> CIRCUITS NEAR THE TOP OF THE PANEL, AND THE MORE HEAVILY LOADED CIRCUITS NEAR THE BOTTOM. 47. DUCT DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM TO INITIATE SUPERVISION. THE DOUBLE DUPLEX RECEPTACLES, NEMA 5-20R. <br /> BALANCE ALL CIRCUITS EVENLY BETWEEN PHASE SO THAT FEEDER WIRES CARRY APPROXIMATELY EQUAL DUCT DETECTORS SHALL REQUIRE AN ACCEPTANCE FUNCTION TEST AND TEST SHALL BE WITNESSED CEILING DUPLEX RECEPTACLE 20A, 125V, NEMA 5-20R <br /> CURRENT. ALL PHASES MUST BE BALANCED WITHIN 10% OR LESS. G.C. SHALL REBALANCE IF NECESSARY. BY THE FIRE INSPECTOR FOR AUTOMATIC SHUTDOWN. TESTING SHALL BE IN ACCORDANCE WITH NFPA <br /> 72 2016 EDITION AND MANUFACTURER'S INSTRUCTIONS. ALL SUBCONTRACTORS SHALL BE PRESENT (WP= WEATHERPROOF, D= DEDICATED, GFI=GROUND FAULT <br /> 11. BRANCH CIRCUIT CONDUCTORS SHALL NOT BE LESS THAN #12AWG. THE INSULATION SHALL BE COLOR HVAC, FIRE ALARM AND ELECTRICAL. INTERRUPTER) <br /> CODED. AND SHALL BE 600 VOLT. TYPE THHN/THWN COPPER. <br /> CABLES IN HIGH TEMPERATURE AREAS SHALL HAVE INSULATION TYPE SUITABLE FOR THE TEMPERATURE. <br /> ❑ DOUBLE DUPLEX RECEPTACLES, NEMA 5-20R. (FLOOR MOUNTED) <br /> 12. CABLES USED IN SPACES FOR ENVIRONMENTAL AIR SHALL CONFORM WITH APPLICABLE N.E.0 <br /> REQUIREMENTS. <br /> SPECIAL RECEPTACLE, RATING AS SHOWN. <br /> 13. ALL WIRING USED IN RETURN OR DISCHARGE AIR PLENUMS SHALL BE PLENUM RATED OR INSTALLED PER Q) JUNCTION OR OUTLET BOX <br /> METHODS APPROVED BY THE LATEST EDITION OF THE N.E.C. FOR SUCH APPLICATION. WALL MOUNTED JUNCTION BOX <br /> 14 ALL WIRE AND CABLE CONDUCTORS SHALL BE COPPER WITH INSULATION RATED 60OV. CONDUCTORS (3) CAT-5 DATA OUTLETS. PROVIDE OUTLET BOX AND <br /> SIZED #10 AWG AND SMALLER SHALL BE SOLID, AND CONDUCTORS SIZED LARGER THAN #10 AWG SHALL COVERPLATE WITH CABLING TO TERMINATION POINT. <br /> BE STANDARD WIRE. <br /> 15. BRANCH CIRCUITS FOR POWER AND LIGHTING SHALL NOT BE LESS THAN #12 AWG. OR AS NOTED. WIRES EY FUSED DISCONNECT SWITCH, RATING AS SHOWN <br /> ARE TO BE SIZED FOR THE APPROPRIATE VOLTAGE DROPS. Zi <br /> NON FUSED DISCONNECT SWITCH, RATING AS SHOWN <br /> 16. ALL EQUIPMENT AND LIGHT FIXTURES WIRING SHALL NOT BE LESS THAN #12 AWG TYPE SFF-2. AND <br /> FLEXIBLE CORDS SHALL NOT BE LESS THAN #12 AWG TYPE S. MOTOR OUTLET AND FLEX CONNECTION TO MOTOR. Q <br /> 17. CONTROL WIRING SHALL NOT BE LESS THAN #14 AWG UNLESS OTHERWISE NOTED. T❑ LV INGROUND TRANSFORMER m <br /> 18. HOMERUNS SHOWN ARE SCHEMATIC. CONTRACTOR MAY ORIGINATE HOMERUNS FROM DIFFERENT FLEXIBLE CONDUIT WITH CONNECTION TO EQUIPMENT cr) <br /> LOCATIONS. ALL WIRE INCLUDING HOMERUNS SHALL BE DELINEATED ON AS-BUILT DRAWINGS. <br /> WIRE SIZING SCHEDULE 2 PANELBOARD/LOAD CENTER, SURFACE, FLUSH. O <br /> 19. ALL WIRING INSTALLED UNDER THIS CONTRACT SHALL BE TESTED FOR PROPER CONNECTIONS AND SHORT > o <br /> CIRCUITS PRIOR TO THE TURNING OVER OF WORK AS A COMPLETE UNIT. w <br /> BRANCH CIRCUIT WIRING IN CONDUIT CONCEALED IN CEILING <br /> 20. PROVIDE ALL ELECTRICAL SYSTEM GROUNDING IN ACCORDANCE WITH N.E.C. REQUIREMENTS EVEN IF IT IS OR WALL. z <br /> NOT SHOWN ON THE DRAWINGS. INCLUDE ADDITIONAL GROUNDING CONDUCTORS IN NONMETALLIC BRANCH CIRCUIT WIRING IN CONDUIT CONCEALED UNDER FLOOR OR <br /> RACEWAYS EVEN THOUGH THE DRAWINGS SHOW ONLY CIRCUIT AND/OR NEUTRALS CONDUCTORS. THE UNDERGROUND. m <br /> PLUMBING AND PIPING SYSTEM SHALL NOT BE USED AS A GROUND. ALL TRANSFORMER NEUTRALS SHALL <br /> BE GROUNDED TO BUILDING STEEL IN ACCORDANCE WITH NEC 250-70. 20 AMPS, 120V LTG & RECEPTACLE CIRCUITS BRANCH CIRCUIT HOMERUN TO PANEL. Q <br /> 21. ALL CONDUITS PASSING THROUGH PARTITIONS ARE TO BE APPROPRIATELY SLEEVED AND SEALED. CONDUIT UP. z <br /> � DISTANCE WIRE SIZE <br /> 22. FURNISH AND INSTALL ALL CONDUIT WITH PULL WIRES AS REQUIRED. ALL OUTLET BOXES SHALL BE CONDUIT DOWN. w <br /> STEEL, EXTRA DEEP WITH GROUNDING PIGTAILS. GROUNDING PUSH-CLIPS ARE NOT ACCEPTABLE. 1' TO 100' #12 AWG �f�f FLEXIBLE CONDUIT o <br /> 0 23. ALL SLAB PENETRATIONS SHALL BE INSTALLED AND FIRE RATED PER NATIONAL STATE AND LOCAL <br /> CODES 101'- 150' #10 AWG CONDUIT STUBBED OUT IN ACCESSIBLE LOCATION, CAP AND o <br /> a. 24. DO NOT MAKE ANY CHANGES OR SUBSTITUTIONS WITHOUT SPECIFIC WRITTEN APPROVAL FROM THE MARK LOCATION. Q <br /> M ARCHITECT OR ENGINEER. <br /> 151'-200' #10 AWG <br /> aaaaaaa <br /> 25. GUARANTEE ALL WORK, MATERIAL AND EQUIPMENT FOR A PERIOD OF ONE YEAR FROM THE DATED OF 201'-250' #8 AWG <br /> c APPROVAL AND FINAL ACCEPTANCE. <br /> � 26. THIS DESIGN IS BASED ON INITIAL DESIGN DATA. GENERAL CONTRACTOR TO SUPPLY AND INSTALL 251'- 300' #8 AWG <br /> M FEEDERS, FUSES AND CIRCUIT BREAKERS TO MATCH THE NAMEPLATE RATING OF ALL EQUIPMENT. THIS <br /> 3 SHALL BE INCLUDED IN THE INITIAL BID PROPOSAL AND NO EXTRAS SHALL BE ENTERTAINED. 301' & UP #6 AWG D RAW I N G INDEX 3 <br /> c 27. THE G.C. SHALL PROVIDE ALL EQUIPMENT. MATERIALS AND LABOR TO COMPLETE ALL ELECTRICAL WORK <br /> IN A NEAT AND WORKMANLIKE MANNER AND IN ACCORDANCE WITH GOOD COMMERCIAL PRACTICE SHEET NUMBER DESCRIPTION <br /> INCLUDING THE INSTALLATION OF ALL THE EQUIPMENT MATERIALS AND SYSTEMS AND THE FINAL D <br /> W CONNECTIONS TO THE OWNER'S EQUIPMENT AND FIXTURES AS REQUIRED BY THE OWNER. THE G.C. Q W <br /> = SHALL ALSO FURNISH TEMPORARY WIRING AND LIGHTING TO PROVIDE A MINIMUM OF 25 FC IN WORK NOTE: <br /> (n AREAS FOR USE OF ALL THE TRADES DURING CONSTRUCTION AND THE INSTALLATION OF THE OWNERS EO.1 LEGEND, NOTES & SCHEDULES O <br /> Jv LINE CONDUCTOR SIZE IS INCREASED TO COMPENSATE FOR VOLTAGE DROP. GROUND CONDUCTOR U M Z � <br /> r„ FIXTURES. THE G.C. IS RESPONSIBLE TO REMOVE ALL TEMPORARY WIRING UPON COMPLETION OF SIZE SHALL BE INCREASED PROPORTIONATELY WITH THE LINE CONDUCTOR PER NEC 250.122(8) EO.2 SPECIFICATIONS W C'7 <br /> CONSTRUCTION OF ALL TRADES. <br /> z 28. G.C. SHALL LABEL ALL JUNCTION BOX, OUTLETS, LIGHT SWITCH, ETC. WITH CIRCUIT NUMBER ON EO.3.1 SINGLE LINE DIAGRAM u O Q Lo <br /> o INTERIOR OF COVER PLATE. 0) <br /> w 29. GENERAL CONTRACTOR SHALL PROVIDE SEISMIC RESTRAINTS AND SUPPORTS FOR ALL FLOOR AND EO.3.2 ELECTRICAL PANEL SCHEDULES _ Q <br /> CEILING MOUNTED ELECTRICAL EQUIPMENT TO RESIST EARTHQUAKE EFFECTS DETERMINED IN � Q O <br /> ACCORDANCE WITH THE BUILDING CODE. EO.4 TITLE 24 FORMS - INDOOR LIGHTING PART 1 <br /> o LLQ J <br /> ``' 30. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE AND INSTALL ALL SUPPLEMENTARY SUPPORT, EO.5 TITLE 24 FORMS - INDOOR LIGHTING PART 2 <br /> a INCLUDING SUPPORT STEEL AS REQUIRED TO HANG ALL EQUIPMENT AND LIGHTING FROM THE1Ld <br /> U <br /> M STRUCTURE IN ACCORDANCE WITH THE ARCHITECTURAL/STRUCTURAL SUPPORT AND APPLICABLE CODE E0.6 TITLE 24 FORMS - OUTDOOR LIGHTING PART 1 ��-�� 1- W W � <br /> CRITERIA. _ ` <br /> a 31. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO PROVIDE FULLY DIMENSIONED COORDINATION EO.7 TITLE 24 FORMS - OUTDOOR LIGHTING PART 2 f <br /> DRAWINGS FOR ALL OF HIS RESPECTIVE WORK. THESE DRAWINGS MUST BE FULL COORDINATED WITH ALL EO.8 TITLE 24 FORMS - SOLAR FORMS PART 1 U_ U Q <br /> CONDITIONS. ALL HVAC, PLUMBING, FIRE PROTECTION, ELECTRICAL, LIGHTING, STRUCTURAL AND <br /> z ARCHITECTURAL SYSTEMS PRIOR TO PREPARING COMPOSITE MULTI DISCIPLINE COORDINATION DRAWINGS. O <br /> E0.9 TITLE 24 FORMS - SOLAR FORMS PART 2 <br /> a 32. ALL DISCONNECTING MEANS AND EQUIPMENT INDICATED ON THE DRAWING SHALL BE IDENTIFIED BY Q <br /> o NAMEPLATE IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE 110-22. EO.9.1 TITLE 24 - SOLAR READY ZONE W <br /> U <br /> a 33. ALL WIRING FOR THE EMERGENCY LIGHTING AND EMERGENCY SYSTEMS SHALL BE INSTALLED IN EO.10 TITLE 24 FORMS - POWER FORMS <br /> m ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE ARTICLE 700. <br /> E1.0 LIGHTING PLAN <br /> 34. THE WIRING METHODS AND MATERIALS INDICATED IN THE SPECIFICATIONS AND ON THE DRAWINGS SHALL <br /> BE INSTALLED AND CONNECTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL E1.2 QSR SHELL LIGHTING PLAN <br /> "' CODE ARTICLE 300. <br /> E2.0 POWER PLAN & EQUIPMENT SCHEDULE <br /> z 35. THE ELECTRICAL SERVICE AND DISTRIBUTION SYSTEM AS INDICATED ON THE RISER DIAGRAM AND <br /> F MATERIALS INDICATED IN THE SPECIFICATIONS SHALL BE IN COMPLIANCE WITH THE REQUIREMENTS OF E2.1 ELECTRICAL ROUGH-IN PLAN <br /> Project Number <br /> THE NATIONAL ELECTRIC CODE ARTICLE 230. E2.2 QSR SHELL POWER PLAN SPA16002.0 <br /> 36. ALL GROUNDING REQUIREMENTS OF THE COMPLETE ELECTRICAL DISTRIBUTION SYSTEM AND AS INDICATED <br /> Al IN THE SPECIFICATIONS SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 250. E3.0 ELECTRICAL ROOF PLAN <br /> W 37. ALL OVER CURRENT PROTECTION SHALL BE IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE E4.0 COMMUNICATION PLAN Sheet Name <br /> o SECTION 240. <br /> 38 PRIOR TO ANY REQUIRED CUTTING AND PATCHING OF CONCRETE FLOOR AND/OR CUTTING OF ROOF E5.0 DIAGRAM & DETAILS - PART 1 LEGEND NOTES <br /> CONTRACTOR SHALL COORDINATE WITH BUILDING ENGINEER. SEAL ALL EXTERIOR AND FIREWALL 9 <br /> 0 PENETRATIONS. <br /> E5.1 DIAGRAM & DETAILS - PART 2ir & SCHEDULES <br /> a E5.2 FAULT CURRENT & ARC FLASH SCHEDULES <br /> a. <br /> E6.0 SITE LIGHTING PLAN <br /> z <br /> W <br /> v E6.1 SITE POWER PLAN <br /> a <br /> v E7.0 CAR WASH LIGHTING PLAN Sheet Number <br /> z E7.1 CAR WASH POWER PLAN <br /> W EOm 1 <br /> L� <br />