/� 0 <br /> MAIN SWITCHBOARD "MSB" 1000 AMP 208Y/120V 3 0 4W 65,000 AIC MINIMUM RATING <br /> GE CUSTOM SWITCHBOARD, CONTACT MATT THATCHER (916)-339-4524 <br /> USE G.E AV LINE Architecture / Development <br /> 14901 Quorum Drive <br /> I I I 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 Suite 300 <br /> Dallas Texas 75254 <br /> M 84 <br /> Fax(972)(972)23988054 <br /> O 80A 80A 80A 80A 80A 80A 80A 80A 20A 20A 20A 20A 20A 200A 200A 200A 200A 20A 30A 100A ISSUE RECORD <br /> 3 POLE 3 POLE 3 POLE 3 POLE 3 POLE 3 POLE 3 POLE 3 POLE 1 POLE 1 POLE 1 POLE 1 POLE 1 POLE 3 POLE 3 POLE 3 POLE 3 POLE 3 POLE 3 POLE 2 POLE DATE DESCRIPTION <br /> O O O O O O O O O O O O O I URBAN PROTOTYPE DESIGN <br /> 4 4 4 4 4 4 4 4 4 4 4 4 4 <br /> 10-22-2018 ISSUED FOR PERMIT <br /> 1000A MCB <br /> 3 POLE <br /> C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 30.4 0 30.3 1 15' <br /> LJ LJ LJ LJ LJ LJ LJ LJ LJ LJ LJ LJ LJ o.7% vD 100A-2P+S/N, <br /> 250V <br /> 200.4 200.4 200.4 200.4 NON-FUSIBLE <br /> 80.3 80.3 80.3 80.3 80.3 80.3 80.3 80.3 20.1 20.1 20.1 20.1 20.1 TVSS UPS DISC. SWITCH <br /> 66' 65' 64' 63' 62' 52' 42' 44' 66' 65' 64' 63' 62' 53' 55' 65' <br /> O O REVISION RECORD <br /> __(ED (ED __(ED __(ED -(ED -(ED -(ED __(E3 -(ED __Q]) -(ED __Q:3 __Q:3 VD 0.6% VD _-CED 0.3% VD 65' <br /> 0.7% VD 00.3 I <br /> PNL A <br /> 1000A FUTURE FUTURE FUTURE FUTURE FUTURE 4 6 4 4 6 <br /> IT CLOSET 30' <br /> FRYER FRYER FRYER FRYER FRYER GRIDDLE GRIDDLE GRIDDLE PNL B PNL C PNL HVAC 0.4% VD <br /> II GAS FRYER GAS FRYER GAS FRYER GAS FRYER GAS FRYER <br /> E-41A E-41A E-41A E-41A E-41A E-09 E-09 E-09 <br /> E-41 E-41 E-41 E-41 E-41 <br /> (1) (2) (3) (4) (5) (1) (2) (3) <br /> (1) (2) (3) (4) (5) 100.4 PNL D <br /> 200' SERVICE 20.980 KVA 20.980 KVA 20.980 KVA 20.980 KVA 20.980 KVA 16.248 KVAI 16.248 KVA 16.248 KVA 1 0.720 KVA 0.720 KVA 0.720 KVA 0.720 KVA 0.720 KVA 180' <br /> GROUNDING <br /> 1.8% VD O 10 10 0.2% VD <br /> EXHAUST FAN CONTROL PANEL 1 2 <br /> GRIDDLE GRIDDLE GRIDDLE PROVIDE PANEL'S LABEL: <br /> O E-08 E-08 E-08 PANEL "F" PNL F <br /> 1000A 6 ARC FLASH NOTE (1) (2) (3) <br /> FED FROM PANEL A <br /> UTILITY PAD <br /> SWITCHBOARDS, PANELBOARDS, MOTOR CONTROL PANELS AND METER SOCKET #4 GROUND PER NEC <br /> MOUNT XFMR ENCLOSURES WHICH ARE LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING, OR - 250.32(A) SERVICE GROUND. EF-3 EF-4 EF-5 PR E L <br /> MAINTENANCE WHILE ENERGIZED, SHALL BE FIELD MARKED TO WARN QUALIFIED PERSONS PROVIDE ISOLATED NEUTRAL (1 HP) (1 HP) (1 HP) testi rN <br /> OF POTENTIAL ELECTRIC ARC FLASH HAZARDS PER CEC 110.16. A WARNING LABEL ELECTRICAL SINGLE LINE DIAGRAM (NO JUMPER GROUND-NEUTRAL) <br /> SHALL BE SUFFICIENT. ARC FLASH CALCULATIONS ARE NOT NECESSARY UNLESS REQUIRED O♦ <br /> 2)4"C BY THE AUTHORITY HAVING JURISDICTION OR UNLESS THE OWNER SPECIFICALLY REQUIRES I SCALE: NOT TO SCALE (1.25 X 1728 VA) + (2 X 1728 VA) = 5,616 VA �1 <br /> IT. THE MARKING SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED � C 1 <br /> = 15.6 AMPS 208V 30 7 044 <br /> t <br /> PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING OR MAINTENANCE OF THE EXF. � Lp <br /> EQUIPMENT. <br /> t <br /> d fit',CTRkc' ' <br /> .-If <br /> �FCF,L►F��' . <br /> � <br /> TYP. CKT. 65 K AMPERE MAIN DISTRIBUTION PANEL GROUNDING (PANEL 'MSB') /G�"zliG $ <br /> - SINGLE LINE DIAGRAM NOTES POWER FEEDER SCHEDULE <br /> RATING, TYPICAL C - NEUTRAL BUS - - - <br /> A B C I J 1, THE MAIN SWITCHBOARD "MSB" SHALL BE BRACED FOR 65,000 AMPS OF AVAILABLE FAULT CURRENT OR <br /> #2/0 AWG CU MAIN THE ACTUAL AVAILABLE FAULT CURRENT AS DETERMINED BY THE ELECTRIC UTILITY COMPANY, WHICHEVER FEEDER CONDUIT SIZE NOF CONDUCTOR NUMBER AND SIZE OF <br /> TAG CONDUCTORS SIZE GROUNDING CONDUCTOR 1-#6 AWG CU TO PHONE BOARD OR <br /> f< I I 7BONDING JUMPER GROUND BUS 1 - #2/0 AWG CU TO BLDG METAL IS GREATER. <br /> CUSTOMER LOAD ® ® GAS PIPE AT BLDG ENTRY LOCATION, 2. ALL OF THE MAIN SWITCHBOARD CIRCUIT BREAKERS SHALL BE FULLY RATED FOR 65,000 AMPS OF 20.1 3/4" 2 #12 1 #12 <br /> CUSTOMER SIDE OF GAS METER, NOT AVAILABLE FAULT CURRENT AS SHOWN ON THIS SHEET. k try <br /> H-� I MINIMUM OF 20'-0" OF INTENDED TO SERVE AS GROUNDING 3. ALL OF THE PANELBOARDS AND PANELBOARD BRANCH CIRCUIT BREAKERS SHALL BE FULLY RATED FOR 30.3 3/4" 3 #10 1 #10 <br /> 1/2" REBAR IN BUILDING ELECTRODE 22,000 AMPS AND 10,000 AMPS OF AVAILABLE FAULT CURRENT AS SHOWN ON PANEL SCHEDULES ON engineering consultants <br /> WALL FOOTING 7DWG. E2.1. 30.4 3/4 4 #10 1 #10 <br /> 1 - #6 AWG CU TO FIRE WATER 14901 Quorum Dr. #565 Dallas, TX 75254 <br /> TYPICAL I PIPE AT BLDG ENTRY LOCATION 4. ALL EQUIPMENT AND DEVICES SHALL BE RATED TO MATCH OR EXCEED ALL AVAILABLE UTILITY COMPANY1 4 #8 1 #10 O rtmassociates.com 1 972.387.3500 <br /> L CONTACTOR <br /> N <br /> CAPACITY. 40.4 " <br /> _ I GROUNDING ELECTRODE CONDUCTOR 5. ALL FUSES SHALL BE CURRENT LIMITING TYPE EXCEPT WHERE NOTED. 80.3 1-1/4" 3 #3 1 #8 18.GHAA.033 <br /> TB USE #2/0 AWG CU 6. ALL CONDUCTORS SHALL BE COPPER, REFER TO SPECIFICATIONS SHEET E10.0 FOR ADDITIONAL <br /> L I # / 90.3 1 1/4" 3 #2 1 #g PROTOTYPE VERSION <br /> BONDING JUMPER REQUIREMENTS. URBAN DESIGN <br /> N I TO PANELBOARD ENCLOSURE 7. ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE 90.4 1 1/4" 4 #2 1 #8 <br /> WATER METAL WATER PIPE IN DIRECT CONTACT WITH ARTICLE 250, AND ALL INSTALLATIONS SHALL CONFORM TO ALL NATIONAL ELECTRICAL CODE AND ALL PROJECT NAME <br /> SERVICE EARTH FOR MINIMUM 10', CONNECTION MADE LOCAL BUILDING CODES AN ORDINANCES. 00.3 I 1 1/2" 3 #1 2 #8, #8 IG <br /> - PIPE WITHIN 5' OF BUILDING ENTRY. 8. ALL ELECTRICAL PANELBOARDS SHALL BE PROVIDED WITH APPROVED LOCKING DEVICES. 100.4 1 1/2" 4 #1/0 1 #6 I N-N-O UT <br /> DETAIL FIGURE 1 TYPICAL FOR CKTS. 1-13 g ALL FEEDER LENGTHS SHOWN ON THE SINGLE LINE DIAGRAM ARE FOR CALCULATION PURPOSES ONLY. <br /> THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL FEEDER LENGTHS PRIOR TO BID. 125.3 1 1/2" 3 #1/0 1 #6 BURGER <br /> CONTACTORWIRING DETAIL GROUNDING DETAIL 10• THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE MAIN SWITCHBOARD AND ALL PANELBOARDS AND 200.4 2 1/2' 4 #3/0 1 #6 <br /> CIRCUIT BREAKERS AS MANUFACTURED BY GENERAL ELECTRIC COMPANY. ALL ELECTRICAL EQUIPMENT <br /> O� SCALE: NOT TO SCALE 02 SCALE: NOT TO SCALE 0PROVIDED BY THE ELECTRICAL CONTRACTOR SHALL BEAR THE UNDERWRITERS LABORATORY (UL) LABEL » <br /> FOR THE SPECIFIC USES INSTALLED. ALL MATERIALS AND EQUIPMENT SHALL BE NEW. 250.4 2 1/2 4 #250 1 #4 LATHROP <br /> 1000A 4 ® 3" 4 SETS OF 4 #250 <br /> CALIFORNIA <br /> PANEL MSB LOAD SUMMARY FAULT CURRENT CALCULATION (L-L POINT-TO-POINT) GENERAL NOTE: 16514 GOLDEN VALLEY PKWY <br /> 14 <br /> CONN. LOAD DEMAND DEMAND LOAD MOUNTED: FLOOR NOTES: (Assumed) TRANSFORMER KVA= 300 WITH %Z= 2.25% FAULT Isc(A)= 37010 SWITCHBOARDS, PANELBOARDS, MOTOR CONTROL PANELS, AND METER SOCKET ENCLOSURES WHICH ARE LATHROP, CA 95330 <br /> CATEGORY KVA AMPS FACTOR KVA AMPS VOLTS, 1201208 REFER TO SHEET E2.0 FAULT AT MSB PANEL A PANEL B PANEL C UPS/PANEL D PANEL F LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE WHILE ENERGIZED, SHALL <br /> CONTINUOUS: 25.5 70.8 125% 31.9 88.5 PHASE/WIRE: 3/4 FOR SINGLE LINE DIAGRAM BE FIELD MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS PER <br /> SOURCE TRANSFORMER MSB MSB MSB MSB PANEL A NEC 110.16. A WARNING LABEL SHALL BE SUFFICIENT, ARC FLASH CALCULATIONS ARE NOT <br /> RECEPTACLE: 18.9 52.5 10+.5x 14.5 40.1 BUS SIZE 1000 AMPS NECESSARY UNLESS REQUIRED BY THE AUTHORITY HAVING JURISDICTION OR UNLESS THE OWNER <br /> MOTORS. 12.8 35.5 100% 12.8 35.5 MAIN SIZEITYPE: MCB WIRE SIZE (AWG) 250 310 3/0 310 1 2 SPECIFICALLY REQUIRES IT. THE MARKING SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO <br /> KITCHEN EQUIPMENT: 242.8 673.9 65% 157.8 438.1 BUS TYPE: COPPER COPPER OR ALUMINUM CU CU CU CU CU CU QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE <br /> AIR CONDITIONING 58.8 163.2 100% 58.8 163.2 FULLY RATED: 65 K A METALLIC OR NONMETALLIC RACEWAY N M M M M N EQUIPMENT. <br /> HEAT (ELECTRIC): 5.2 14.5 0% 0.0 0.0 <br /> OTHER 4.6 12.8 100% 4.6 12.8 CONN. PHASE A: 129525 DISTANCE IN FEET (L} 151 53 55 65 30 215 NmNmOUT <br /> LARGEST MOTOR: 24.0 66 10.6 25 6.0 16.7 CONN. PHASE B: 121402 NUMBER OF CONDUCTORS/PHASE (N) 4 1 1 1 1 1 NOTES BY SYMBOL <br /> TOTAL: 1 368.6 1023.2 1 286-41 794.8 CONN. PHASE C: 1 124136 PHASE 3 3 3 3 1 3 \BURGER@ <br /> 1111diw-fl1e111DATA1111118.GHAA.033 - INOB - Lathrop, CA1104 DESIGN DRAWINGS1102 SCHEDULES & CALCSII INOB-LathrFri Oct 19, 2018 8:19 AM-JG VOLTAGE (V) 208 208 208 208 208 208 O REFER TO THE FAN CONTROL PANEL DIAGRAM LOCATED ON SHEET E8.0. <br /> START FAULT CURRENT Isc (A)* 37,010 22766 22766 22766 22766 12773 20 GOD BLESS AMERICA <br /> THE FAN CONTROL PANEL IS TO BE LOCATED IN THE HALLWAY ROOM #111. <br /> CONDUCTOR CONSTANT'C' 18594 12844 12844 12844 7293 6044 <br /> `f FACTOR= 1.732xLxl/(NxCxV) 0.626 0.782 0.812 0.959 0.900 1.650 30 THE TVSS IS RATED AT 30 AMPS, 3 0, 208v, LOCATED INSIDE OF THE ELECTRICAL ROOM. <br /> 'M' MULTIPLIER - 11(1+0 0.615 0.561 0.552 0.510 0.526 0.377 O4 PROVIDE A PERMANENTLY INSTALLED LOCK-OPEN DEVICE ON THE INDICATED CIRCUIT BREAKER THAT <br /> END FAULT(A) 22766 12773 12565 11619 11979 4757 IS CAPABLE OF BEING LOCKED IN THE OPEN POSITION. <br /> PROJECT NUMBER <br /> AIC RATED: 65000 22000 22000 22000 22000 14000 O SELF CONTAINED UPS UNIT - AMERICAN POWER CONVERSION (760) 529-5727. CONTRACTOR IS 180641.001 <br /> TO CONTACT APC FOR COORDINATION AND SPECIFIC INSTALLATION INSTRUCTIONS. INPUT VOLTAGE: <br /> GENERAL FAULT CURRENT NOTES: 208VAC, 1 PH, 2W + GND. OUTPUT VOLTAGE: 120/208VAC, 1 PH, 3W + GND. WEIGHT: 598 LBS. <br /> "W X 27"D X 33"H. MODEL: APC SYMMETRA LX. PROVIDE 3 4" CONDUIT FROM SHEET TITLE <br /> DIMENSIONS: 19 <br /> 1. CONTRACTOR SHALL COORDINATE WITH THE UTILITY COMPANY PRIOR TO COMMENCEMENT OF WORK. / <br /> UPS TO TELEPHONE BOARD. SINGLE LINE <br /> 2. FAULT CURRENT INFORMATION WILL BE PROVIDED WHEN UTILITY INFORMATION IS AVAILABLE. O6 1000A/3P/4W/1000A MAIN CIRCUIT BREAKER, SILVER PLATED COPPER, 65,000 AIC FULLY RATED. <br /> E 3. CONTRACTOR SHALL COORDINATE WITH UTILITY FOR FAULT CURRENT INFORMATION BEFORE INSTALLING REFER TO SHEET E1.0 FOR MORE INFORMATION. CABINET SHALL BE EQUIVALENT TO GE SPECTRA DIAGRAM, NOTES <br /> N ELECTRICAL EQUIPMENT. SERIES. <br /> 00 <br /> 6A VERIFY UTILITY METERING REQUIREMENTS WITH LOCAL UTILITY COMPANY. PROVIDE UTILITY COMPANY <br /> APPROVED CT METER CABINET, METER AND MAIN SERVICE CIRCUIT BREAKER AS REQUIRED. REFER TO <br /> SHEET E1.0 FOR EQUIPMENT LOCATION. <br /> SHEET NUMBER <br /> 0 0 7O BUN GRIDDLE 08 PLUGS DIRECTLY INTO MEAT GRIDDLE 09 VIA INTEGRAL NEMA 15-30R RECEPTACLE. <br /> m ¢ Eo00 <br /> 00 <br /> W <br /> ZZ <br /> � Ckf <br />