GETTUR - RYAN INC. GR ,lob # 19202056 . 1 <br /> FORM 1 <br /> SUMMARY OF SOURCE TEST DATA <br /> SOURCE INFORMATION FACILITY PARAMETERS <br /> GDF Name and Address GDF Representative and Title PHASE II SYSTEM TYPE <br /> Arco 7147 Womp Daryl Lee (Check One ) <br /> 1206 E March Lane <br /> Stockton , CA 95210 GDF Phone No. Balanceowma <br /> 415 . 902 . 5089 p Hirt <br /> Permit Conditions Source; GDF Vapor Recovery System Red Jacket <br /> Canister Hasstech <br /> Healy <br /> GDF # Other <br /> ONNOWN <br /> A/C N <br /> Manifolded ? Yes NO <br /> Operating Parameters <br /> Number of Nozzles served by Tank 91 10 Number of Nozzles Served by Tank #3 <br /> Number of Nozzles Served by Tank 42 10 Number of Nozzles Served by Tank #4 <br /> Applicable Regulations : VR -203A and VR-204x1 VN Recommended <br /> Source Test Results and Comments <br /> Tank # : 1 2 3 4 <br /> 1 . Product Grade 87 91 <br /> 2 . Actual Tank Capacity, gallons 9728 9728 <br /> 3 . Gasoline Volume Total 4032 6983 <br /> 4 . Ullage, gallons (#243 ) 8441 5696 2745 <br /> 5 . Initial Pressure, inches H2O 2 . 00 <br /> 6 . Pressure After 1 Minute, inches H2O 2 . 00 <br /> 7 . Pressure After 2 Minutes, inches H2O 1 ' 98 <br /> 8 , Pressure After 3 Minutes, inches H2O 1 . 98 <br /> 9 . Pressure After 4 Minutes, inches H2O 1 ' 99 <br /> 10 . Final Pressure After 5 Minutes, inches H2O 1 . 98 <br /> 11 . Allowable Final Pressure 1 . 83 <br /> Test Conducted by: Test Company: Date of Test : <br /> Elodio Sanchez Gettler- Ryan Inc. 10 / 30 / 2019 <br /> California Air Resource Board March 17, 1999 <br /> TP-201 . 3 , Page 14 <br /> I <br /> i <br /> s <br /> 1 <br />