A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> KISHIDA, GEORGE INC 1 1725 ACKERMAN DR, LODI November 15, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 201 CCR 2712(b)(1-2) Failure to maintain monitoring, maintenance, and follow up action records. <br /> OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. The <br /> Secondary Containment testing conducted on 11/30/18 and the Overfill prevention testing conducted on 11/15/18 <br /> were not found on site. <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1) date and time of all monitoring or sampling; (2) monitoring equipment calibration and maintenance <br /> records; (3) results of any visual observations; (4) results of sample analysis performed a lab or in the field; (5) logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6) results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br /> last three years on site and submit copies to the EHD. <br /> This is a minor violation. <br /> 301 HSC 25292.1(a) UST system is not operated to prevent unauthorized release, including spills and overfills. <br /> OBSERVATION: The fuel filter under the dispenser# 1 is not located to allow drips and leaks to drain back into the <br /> UDC. <br /> REGULATION GUIDANCE: The underground storage tank system shall be operated to prevent unauthorized <br /> releases. <br /> CORRECTIVE ACTION: Immediately provide approved secondary containment for the filters under permit and <br /> inspection by the EHD. <br /> This is a Class II violation. <br /> 320 CCR 2635, 2637.2, 2665, 2712 Failure to comply with the installation, inspection, or record keeping of the overfill <br /> prevention. <br /> OBSERVATION: Overfill prevention testing was conducted on 11/15/18 <br /> REGULATION GUIDANCE: Overfill prevention equipment inspections were required to be conducted by October <br /> 13, 2018, and every 36 months thereafter, and within 30 days of completion of a repair. <br /> CORRECTIVE ACTION: Ensure all future testing is conducted within required time frames. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by December 15, 2019. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> FA0003756 PR0231309 SCO01 11/15/2019 <br /> EHD 23-01 Rev.9/20/2019 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />