Laserfiche WebLink
Emergency Shut-Off (ESO) Testing 19204310.5 <br /> Facility#: Arno 7049 Contractor:Gettler-Ryan Inc. <br /> Address: 800 E Keltteman Lan Address:6805 Slerra Ct Suite G <br /> City, State: Lodl,CA City, State:Dublin,CA 94568 <br /> Test Date: 11/27/2019 Technician: Bodo Sanchez <br /> The objective of this test is to provide assurance that when the ESO switch is activated,all the fueling system circuits <br /> (turbines,and dispensers)are de-energized,and remain de-energized until they are re-set manually. <br /> SWITCH# 9 2 3 4 5 <br /> Location of ESO Tank Building Building Inside <br /> (be spedfic) <br /> Type of Switch: Momentary Momentary Momentary Momentary <br /> Push Pull Momentary <br /> Plain light/Toggle Other <br /> Type of Turbine Control Relay System: FE EPTRO MAG VFC <br /> Power Integrity Custom Fab. Square D <br /> Power Solution Carolina Box Brown Box <br /> PERFORMANCE TEST <br /> Does the ESO shutdown power to the Y <br /> DISPENSERS?(Y/N) Y Y Y <br /> Does the ESO shutdown power to the Y <br /> TURBINES?(YM) Y Y Y <br /> OVERALL RESULT(Pass or Fail) PASS PASS PASS PASS <br /> If the test fails and cannot be fixed while onsite,call the Help Desk&document the ticket number <br /> If the test faits,contractor MUST: place an"Out of Service"tag on the ESO(s); &notify the site manager and teach them <br /> alternative emergency shut down procedures(i.e., locate circuit panel,clearly identify turbine and dispenser breakers for shut- <br /> off in the event of an emergency) <br />