Laserfiche WebLink
19204310 . 5 <br /> by <br /> .y <br /> Line Leak Detector Test Data Sheet <br /> Station# Arco 7049 Date December 5th 2019 <br /> Address 800 E Kettleman Lane <br /> Lodi, CA 95240 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 <br /> DSL <br /> Manufacturer VR VR <br /> VR <br /> Model 848480 848480 <br /> 848480 <br /> Full Operating Pressure(psi) 34 32 32 <br /> Line Bleed Back(nil) NA NA NA <br /> Trip Time(sec) NA NA NA <br /> Metering Pressure(psi) NA NA NA <br /> F/E Holding Pressure(psi) <br /> 20 19 20 <br /> Test Leak Rate(ml/min)(gph) 18 9ML 18 9ML 18 9ML <br /> PASS or FAIL PASS PASS PASS <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Elodio SNchez Lic#220793 <br /> Signature L. • d <br /> E I V E 6 JA <br /> D <br /> DEC 4 7 2019 <br /> ENVIRONMENTAL HEALTH <br /> DFPARTIAFNT <br />