My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2019
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
V
>
VICTOR
>
880
>
2300 - Underground Storage Tank Program
>
PR0231746
>
COMPLIANCE INFO_2019
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
9/15/2020 12:33:05 PM
Creation date
9/15/2020 10:39:01 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2019
RECORD_ID
PR0231746
PE
2361
FACILITY_ID
FA0003862
FACILITY_NAME
Marks Fuel & Food, Inc.
STREET_NUMBER
880
Direction
E
STREET_NAME
VICTOR
STREET_TYPE
RD
City
LODI
Zip
95240
APN
049-050-32
CURRENT_STATUS
01
SITE_LOCATION
880 E VICTOR RD
P_LOCATION
02
P_DISTRICT
004
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
79
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SAN" J D�l+ �� I 11411" Environmental Health Department <br /> COUNTY— <br /> Underground <br /> �l O U N T Y— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Marks Fuel& Food Inc. T880 E VICTOR RD LODI October 09 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> 1)A designated operator inspection was performed on October 24, 2018 and the next inspection was performed on <br /> November 28, 2018, 36 days later. The designated operator visual inspections shall be conducted within 30 days or <br /> less of the previous inspection. Ensure that all designated operator inspections are performed within the required time <br /> frames. <br /> 2)The designated operator failed to check and note all required items on the visual inspection reports. <br /> -The"NA"in sections VII through XI were not explained. <br /> -Section V of the inspection reports were missing follow up actions about scheduling Overfill Prevention Equipment <br /> Testing. <br /> -Section VI of the report was missing the date, name, and signature of the UST owner/operator. <br /> -Section VII was left blank on the 10/24/2019 monthly inspection report. <br /> -The designated operator answered the question regarding UDC sensor locations but did not list which UDC were <br /> visually inspected. <br /> -Secondary containment test date was incorrectly stated as 2/22/2017. <br /> -Tank and line tightness testing information was left blank. <br /> -Tank and line tightness test information was left blank. <br /> During the visual inspection,the designated operator shall check that all required testing and maintenance for the UST <br /> system have been completed and shall check all required items on the report. Ensure that designated operators <br /> performing visual inspections at this facility are including all of the required information on the reports. <br /> This is a Class II violation. <br /> 310 CCR 2636(f)(4) Piping is not fail-safe outside UDCs or fails to stop flow of product at dispenser inside UDCs. <br /> According to the service technician,the 91 tank relay was not shutting down the pump and does not meet the <br /> requirements for annual line tightness testing exemption. All pressurized piping with secondary containment shall be <br /> pressure tested at least once every 12 months at a minimum release detection of 0.1 gallons per hour at 150 percent <br /> of the normal operating pressure. Continuous monitoring systems that are fail safe and shut down the pump when a <br /> leak is detected, or optionally stop the flow of product at the dispenser if the leak is in the under dispenser <br /> containment(UDC), shall satisfy the requirement for annual line tightness testing. Immediately schedule an annual <br /> line tightness test and provide 48 hours notification to the EHD. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 11/9/2019. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209)468-3420. <br /> Documents provided during inspection: <br /> FA0003862 PR0231746 SCO01 10/09/2019 <br /> EHD 23-01 Rev.08/27/2019 Page 8 of 9 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />
The URL can be used to link to this page
Your browser does not support the video tag.