Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> SECONDARY CONTAINMENT TESTING REPORT 'FORM '(Page 2 of s) <br /> V. TANK SECONDARY CONTAINMENT INFORMATION <br /> Manufacturer Identify Tank ID from Section iii for each Manufacturer <br /> Modern Welding AAO BB ❑ C❑ El I D❑ El <br /> El <br /> Test Method Used : ❑ Manufacturer Guidelines (Specify): <br /> Vacuum <br /> p Industry Code or Engineering Standard (Specify) : PEI RP1200 <br /> ❑ Engineered Method (Specify): <br /> # of Attached Pages <br /> Attach the testing procedures and all documentation required to determine the results. <br /> Tank Containment Testing Training and Certifications (List applicable certifications) Expiration Date <br /> VI . COMMENTS <br /> Provide any additional comments here. <br /> UE0420001 Annular - <br /> - 10" HG for two hours , 9 : 00am to 11 : 00am - PASSED <br /> VII . PRODUCT PIPING CONTAINMENT TESTING INFORMATION <br /> Manufacturer Identify Tank ID from Section III for each Manufacturer <br /> Western Fiberglass A Q B ❑ C ❑ I D ❑ <br /> AO Smith A ❑ I B ❑ I C ❑ I D ❑ <br /> Test Method Used : ❑ Manufacturer Guidelines (Specify): <br /> Pressure <br /> 0 Industry Code or Engineering Standard (Specify): PEI RP1200 <br /> ❑ Engineered Method (Specify): <br /> # of Attached Pages <br /> Attach the testing procedures and all documentation required to determine the results. <br /> Product Piping Containment Testing Training and Certifications (List applicable certifications) Expiration Date <br /> Interstitial Communication Verification Method Used : <br /> NIA <br /> V111 . COMMENTS <br /> Provide any additional comments here. <br /> UE0420001 Supply # 1 - <br /> C <br /> I 5 PSI for one hour, 9 : 00am to 10 : 00am - Passed <br /> i <br /> r <br /> UE0420001 Supply # 2 - <br /> 5 PSI for one hour, 9 : 00am to 10: 00am - Passed <br /> UE0420001 Emergency Return - <br /> 5 PSI for one hour, 9: 00am to 10 : 00am - Passed <br /> I <br /> i <br /> i <br /> ID = Identification <br />"t <br />