ROOFTOP PACKAGED UNIT SCHEDULE MECHANICAL LEGEND REVISIONS
<br /> NO. DESCRIPTION DATE
<br /> EQUIPMENT EQUIPMENT
<br /> EQUIPMENT
<br /> (CFM) FAN MOTOR ELECTRICAL(UNIT) COOLING COIL HEATING WEIGHT FLEXIBLE DUCTWORK
<br /> MFR MODEL NOTES � ROUND DUCTWORK BREAK
<br /> NO. SERVICE SEER
<br /> SUPPLY AIR OUTSIDE AIR AIR MIN OUTSIDE TYPE ESP. RPM BHP HP ELEC. MCA MOCP TOTAL SENSIBLE COOLING EAT LAT MEH MBH STAGES DB/WB DB/WB REFRIG' MBH INPUT OUTPUT STAGES EDB LAT(°DB) (LBS) -----
<br /> LINED DUCTWORK
<br /> RTU-1 MEZZANINE BREAK ROOM 14.1 2,000 480 480 BELT 0.6 1369 1.6 2.9 460V-3 PH 14.5 20 59 55 1 80.0/62.0 54.5/51.5 R410A 112 90 1 60 101.7 690 JOHNSON ZQG06E4C1AA1B223A3 1,3,4, 6,7,OWNER SUPPLIED,CONTRACTOR INSTALLED DUCTWORK BREAK
<br /> CONTROLS
<br /> JOHNSON TO THERMOSTAT 12x8 DUCT SIZE (FIRST FIGURE
<br /> RTU-2 MEZZANINE OFFICES 14.0 1,200 300 300 BELT 0.6 1119 0.66 2.4 460V-3 PH 10.7 15 33.9 31.8 1 80.0/62.0 55.5/52.0 R410A 70 56 1 60 103.2 573 CONTROLS ZQG04D4B1AA1B223A3 1,3,4, 6,7,OWNER SUPPLIED,CONTRACTOR INSTALLED INDICATED FACING SIDE)
<br /> RTU-3 PROCESSOR ROOM 14.0 900 80 80 BELT 0.8 1119 0.58 2.4 460V-3 PH 10.7 15 31.3 26.5 1 80.0/62.0 52.7/49.5 R410A 70 56 1 60 117.6 573 JOHNSON ZQG04D4B1AA1B223A3 1,3,4, 6,7, 10,OWNER SUPPLIED,CONTRACTOR INSTALLED 0 SPACE TEMPERATURE SENSOR 12" DUCT SIZE (DIAMETER)
<br /> CONTROLS
<br /> RTU-4 BAKERY 14.1 2,000 230 230 BELT 0.8 1432 1.73 2.9 460V-3 PH 14.5 20 59 55 1 80.0/62.0 54.5/51.5 R410A 70 56 1 60 85.9 690 JOHNSON ZQG06D4C1AA1B223A3 1,3,4, 6, 7,OWNER SUPPLIED,CONTRACTOR INSTALLED SMOKE DETECTOR FLEXIBLE DUCT CONNECTION
<br /> CONTROLS
<br /> RTU-5 DELUBULK STORAGE 14.0 1,600 205 205 BELT 0.6 1331 1.07 2.4 460V-3 PH 11.2 15 47.5 42.6 1 80.0/62.0 55.3/51.3 R410A 70 56 1 60 92.4 613 JOHNSON ZQG05D4C1AA1B223A3 1,3,4, 6, 7,OWNER SUPPLIED,CONTRACTOR INSTALLED CO2 SENSOR °R R"° SQUARE TO RND TRANSITION
<br /> CONTROLS
<br /> RTU-6 BOOKKEEPING 14.0 1,200 245 245 BELT 0.6 1119 0.66 2.4 460V-3 PH 10.7 15 33.9 31.8 1 80.0/62.0 55.5/52.0 R410A 70 56 1 60 103.2 573 JOHNSON
<br /> ZQG04D4B1AA1B223A3 1,3,4, 6, 7,OWNER SUPPLIED,CONTRACTOR INSTALLED MOTORIZED DAMPER EXT. INSULATED DUCT
<br /> CONT
<br /> FLOW METER
<br /> ICE ALCOVE/GROCERY JOHNSON �
<br /> RTU-7 14.0 1,600 465 465 BELT 0.8 1400 1.16 2.4 460V-3 PH 11.2 15 47.4 42.6 1 80.0/62.0 55.3/51.5 R410A 70 56 1 60 92.4 613 ZQG05D4C1AA1B223A3 1,3,4, 6, 7,OWNER SUPPLIED,CONTRACTOR INSTALLED INSULATION
<br /> TRANSFER CONTROLS
<br /> BARAMETRIC DAMPER
<br /> RTU-8 PIZZA 14.0 900 95 95 BELT 0.6 1033 0.46 2.4 460V-3 PH 10.7 15 31.3 26.5 1 80.0/62.0 52.7/49.4 R410A 70 56 1 60 117.6 573 JOHNSON Z G04D4B1AA1B223A3 1,3,4, 6,7,OWNER SUPPLIED,CONTRACTOR INSTALLED *::n ELBOW W/TURNING VANES
<br /> CONTROLS Q DUCTWORK RISE ARCH.PROJECT NO.
<br /> RTU-9 SALES FLOOR 16 000 5 475 0-30% DIRECT 2.4 2109 15.72 - 460V-3 PH 97 110 396.3 347.3 4 83.6/65.0 51.4/51.4 R410A 400 324 VARIABLE 60 79 7,867 DAIKIN DPSA035 1 2 4 5 6 7 8 9 OWNER SUPPLIED CONTRACTOR INSTALLED FLOW DIRECTION � DUCT FITTING, SQR TAKE-OFF 2004
<br /> 16.3 (IEER) 10-100% '
<br /> DUCT FITTING, RND TAKE-OFF DRAWN
<br /> RTU-10 SALES FLOOR 16.3 (IEER) 16,000 5,475 0-30% DIRECT 2.4 2109 15.72 - 460V-3 PH 97 110 396.3 347.3 4 83.6/65.0 51.4/51.4 R410A 400 324 VARIABLE 60 79 7,867 DAIKIN DPSA035 1 2 4 5 6 7 8 9 OWNER SUPPLIED CONTRACTOR INSTALLED 4 PIPE TEMPERATURE GAUGE SS
<br /> 10-100%
<br /> DUCT FITTING' CONICAL SPIN-IN VARIABLE � PRESSURE GAUGE
<br /> RTU-11 SALES FLOOR 16.3 (IEER) 16,000 5,475 0-30% DIRECT 2.4 2109 15.72 - 460V-3 PH 97 110 396.3 347.3 4 83.6/65.0 51.4/51.4 R410A 400 324 1 VARIABLE 60 79 7,867 DAIKIN DPSA035 1,2,4,5, 6, 7, 8,9,OWNER SUPPLIED,CONTRACTOR INSTALLED CHECKED
<br /> DUCT FITTING, CONICAL SPIN-IN CRD
<br /> H
<br /> JOHNSON FFQ I TEMPERATURE SENSOR W/AIR SCOOP SUBMITTAL DATES
<br /> NOTES:
<br /> RTU-12 BULK STORAGE 14.0 900 65 65 BELT 0.6 1033 0.46 2.4 460V-3 PH 10.7 15 31.3 26.5 1 80.0/62.0 52.7/49.5 R410A 70 56 1 60 117.6 573 CONTROLS ZQG04D4B1AA1B223A3 1,3,4, 6,7, 10,OWNER SUPPLIED,CONTRACTOR INSTALLED
<br /> FLOW SWITCH DUCT FITTING, CONICAL TAP 06/11/20
<br /> 1. INDICATED PERFORMANCE IS AT DESIGN ELEVATION.
<br /> 2. UNIT PROVIDED WITH MANUFACTURER'S ROOF CURB ADAPTER. e POINT OF NEW CONNECTION DUCT FITTING, RND 90^ TAP
<br /> 3. UNIT EQUIPPED WITH ECONOMIZER. POINT OF DISCONNECT OTB DATE
<br /> 4. PROVIDE WITH NON-POWERED CONVENIENCE OUTLET AND INTEGRAL DISCONNECT. e DUCT FITTING, RND 45^ TAP
<br /> 5. UNIT EQUIPPED WITH HOT GAS REHEAT COIL FOR DEHUMIDIFICATION. �- LINE BREAK
<br /> 6. PROVIDE WITH BAROMETRIC RELIEF. ROUND DUCT, TURN DOWN
<br /> 7. CONTRACTOR RESPONSIBLE TO MODIFY EXISTING DUCT THROUGH ROOF TO MATCH NEW SARA DUCT OPENINGS. GENERAL BREAK LINE
<br /> 8. UNIT TO BE PROVIDED WITH REFRIGERATION ONLY CONTROLS(ROC)FOR INTERGRATION INTO BMS. v w
<br /> 9. PER 2019 TITLE 24 ENERGY COMPLAINCE SECTION 140.4(E)1 EXEMPTION 2,ECONOMIZERS ARE NOT REQUIRED WHERE SUPERMARKET REFRIGERATION SYSTEMS WOULD BE IMPACTED. DDBACKDRAFT DAMPER ® MANUAL PULL STATION ° z o
<br /> oa
<br /> 10. UNIT TO BE PROVIDED WITH MANUFACTURER'S ROOF CURB. x w � �'
<br /> OPPOSED BLADE DAMPER
<br /> SUPPLY DUCT -DUCT ROUTED w o r H�Ouo:
<br /> o z
<br /> 'u P. a o
<br /> TOWARD z °aawmcn Z o Lu
<br /> DUCT TRANSITION SINGLE LINE RETURN TRANSFER DUCT - o a 44 A
<br /> DUCT ROUTED TOWARD z z w E
<br /> (9 HUMIDISTAT OR HUMIDITY SENSOR EXHAUST DUCT -DUCT ROUTED v° A z a I z_ o
<br /> a w a A O O C N
<br /> MANUAL VOLUME DAMPER TOWARD Q A A o z© 2- y 3
<br /> FAN SCHEDULE HOOD SCHEDULE ROUND DUCT -DUCT ROUTED z w o W _ N
<br /> FSDD --E COMBINATION SMOKE/FIRE TOWARD o¢ v Uo
<br /> STATIC MOTOR DIMENSIONS EXHAUST Q v z a o�,
<br /> DAMPER FLAT OVAL DUCT -DUCT z ' Q o 0111
<br /> w � �OcGhv
<br /> EXHAUST ROUTED TOWARD
<br /> EQUIPMENT WEIGHT HOOD EXHAUST EXHAUST FD FIRE DAMPER w o y� a, a o
<br /> SERVICE PROJECT SCOPE CFM AN RPM PRESS DRIVE TYPE SONES CONTROL MANUFACTURER MODEL NOTES NO. SERVES DUCT VELOCITY INTERLOCK MANUFACTURER MODEL NOTES K o
<br /> NO. ( BS TYPE WIDTH DEPTH HEIGHT FAN CFM (FPM) � SUPPPL YY DUCT - DUCT ROUTED o i' . �o
<br /> v�o3c�
<br /> IN.W.G.) HP V. -PH. �" ) CONNECTION INTAKE OR EXHAUST
<br /> EF-1 PIZZA HOOD DEMO EXISTING 1,920 961 1.250 3/4 480V-3 PH. BELT 14.8 MONITORED BY BMS 290 COOK 245VCRXP 1,3,4,GREASE BOX,VENTED ROOF CURB. E H-1 PIZZA I - - - E EF-1 600 - - EXISTING - - co N
<br /> REPLACE WITH NEW VCR-XP O O _ � RETURN/TRANSFER DUCT, DUCT �
<br /> �- DIRECTION OF AIRFLOW ROUTED AWAY /� `F)
<br /> DEMO EXISTING INTERLOCK WITH EQUIP. COOK BAKERY PAN W O -
<br /> EF-2 PAN WASHER HOOD REPLACE WITH NEW 1,500 1,143 0.750 1/2 120V- 1 PH. BELT 11.6 MONTORED BY BMS 98 ACRUB 150ACRUB 1,2,3 (E)H-2 WASHER II - - - (E)EF-2 800 - - EXISTING - - _ ® SUPPLY DIFFUSER EXHAUST DUCT, DUCT ROUTED =
<br /> DEMO EXISTING INTERLOCK WITH EQUIP. COOK AWAY 2 o
<br /> EF-3 OVEN RACK REPLACE WITH NEW 750 1,484 1.250 1/2 120V- 1 PH. BELT 10.2 MONTORED BY BMS 106 VCR 150VCR-HP 1,2,3 H-3 DELI 1 135 54 24 EF-10 2,531 16"0 1813 EF-10,RTU-5 CAPTIVEAIRE 5424 ND-2 1,2,4 RETURN GRILL RND DUCT, DUCT ROUTED AWAY O y
<br /> PENN z
<br /> (E)EF-4 MEZZ ELEC ROOM EXISTING TO REMAIN 1,450 - - - 120V- 1 PH. - - EXISTING - VENTILATION Z-14 5 (E)H-4 CHARGING HOOD 11 - - - (R)EF-14 1,725 - - EXISTING - - ® EXHAUST GRILL FLAT OVAL DUCT, DUCT ROUTED o
<br /> PENN
<br /> AWAY 0 N
<br /> (E)EF-5 MEZZ. TRAINING ROOM EXISTING TO REMAIN 325 - - - 120V- 1 PH. - - EXISTING - VENTILATION ZEPHYR 5 H-5 CHICKEN FRYERS 1 135 54 24 EF-15 2,531 16110 1,813 EF-15,RTU-5 CAPTIVEAIRE 5424 ND-2 1,2,4 � Q � x o
<br /> SHEET METAL DUCT S , DUCT UNIT V Q
<br /> ENN NOTES ® � y W
<br /> (E)EF-6 BAKERY EXISTING TO REMAIN 1,860 - - - 120V- 1 PH. - - EXISTING 70 VENTILATION DX14B 5 1. EXHAUST FAN SHALL BE ELECTRICALLY INTERLOCKED WITH THE EQUIPMENT LISTED. THE EQUIPMENT UNDER THIS HOOD SHALL ONLY TURN ON IF THE EXHAUST FAN IS ON. IF THE FABRIC DUCT ■ � Z
<br /> FAN IS NOT ON,THE INTERLOCK SHALL TURN THE ASSOCIATED EQUIPMENT OFF. FAN SHALL ONLY RUN IF HOOD ON SWITCH IS ENGAGED. ® RETURN/TRANSFER DUCT, DUCT a w W ~
<br /> (E)EF-7 MEN/WOMEN RESTROOM EXISTING TO REMAIN 600 - - - 120V- 1 PH. - - EXISTING - VENTILATION ZEPHYR 5 2. HOOD TO BE FURNISHED COMPLETE WITH FACTORY-INSTALLED SUPPRESSION NOZZLES AND MOUNTED ANSUL FIRE SUPPRESSION SYSTEM IN STAINLESS STEEL CABINET. UNIT CONNECTION cn
<br /> PENNCOORDINATE LOCATIONS OF CABINETS AND PULL STATIONS WITH ARCHITECT/ENGINEER PRIOR TO ORDERING. ACCESS DOOR = @)
<br /> EXHAUST DUCT, DUCT UNIT w
<br /> EMPLOYEE RESTROOM EXISTING TO REMAIN 100 - - - 120V- 1 PH. - - EXISTING - VENTILATION ZEPHYR 5 Z ~
<br /> (E)EF-8 4• TYPE I CANOPY HOOD CONSTRUCTED OF CONTINUOUSLY WELDED 18 GAUGE 430 STAINLESS STEEL WITH#3 FINISH. UNIT SHALL INCLUDE INTEGRAL EXHAUST COLLAR,FILTER CONNECTION W Q
<br /> HOUSING WITH FULL HOOD LENGTH DRIP TRAY AND GREASE CUP,STAINLESS STEEL GREASE EXTRACTOR.,FLUSH MOUNTED CONTROL SWITCHES,STAINLESS STEEL STAND-OFFS, EQUIPMENT CALLOUT ROUND DUCT DUCT UNIT Q ~
<br /> (E)EF-9 EMPLOYEE BREAKROOM EXISTING TO REMAIN 195 - - - 120V- 1 PH. - - EXISTING - VENTILATION ZEPHYR 5 STAINLESS STEEL CEILING TRIM,STAINLESS STEEL OFF-SET TRIM,AND RATED LIGHTS,UNIT SHALL BE U.L.LISTED AND INCLUDE NATIONAL SANITATION FOUNDATION(NSF)SEAL. W
<br /> ® CONNECTION
<br /> DEMO EXISTING SEE H-3 DETAIL CALLOUT Lc
<br /> EF-10 DELI HOOD 2,531 1,146 1.100 1.00 480V-3 PH. DIRECT 14.2 153 CAPTIVEAIRE DU18011FA 1,2, 3,4 @ DPT DIFFERENTIAL PRESSURE NN
<br /> PENNREPLACE WITH NEW MONTORED BY BMS O TRANSDUCER
<br /> EXISTING TO BELLIN
<br /> (E)EF-11 MEZZANINE BREAKROOM RELOCATED 220 - - - 120V- 1 PH. - - EXISTING - VENTILATION ZEPHYR 5 SECTION REFERENCE NUMBER LnQ
<br /> SECTION REFERENCE SHEET _LREPLACE WITH NEW ACE-B
<br /> EF-12 ELECTRICAL ROOM DEMO EXISTING 400 1,032 0.25 1/6 120V- 1 PH. BELT 4.1 MONITORED BY BMS 46 COOK 100ACEB 1,2,3 z a_
<br /> EF-13 FIRE RISER ROOM DEMO EXISTING 850 1,713 0.30 1/6 120V- 1 PH. BELT 10.6 INTERLOCK WITH EQUIP. 46 COOK 100ACEB 1,2,3
<br /> REPLACE WITH NEW MONTORED BY BMS ACE-B
<br /> (R)EF-14 BATTERY HOOD EXISTING TO BE 1,725 - - 0.50 208V-1PH. - - EXISTING - COOK 18005B 5,PROVIDE NEW ROOF CURB QROFESS/
<br /> RELOCATED ACE-B �P��O H.
<br /> EF-15 CHICKEN HOOD NEW 2 531 1,162 1.150 1.00 480V-3 PH. DIRECT 14.5 SEE H-5 153 CAPTIVEAIRE DU180BFA 1 2 3 4 ABBREV. DESCRIPTION 2
<br /> ' MONTORED BY BMS
<br /> NOTES: AD ACCESS DOOR MFR MANUFACTURER
<br /> 5 �
<br /> SITE DESIGN CONDITIONS P: 12/31/21
<br /> l. INDICATED PERFORMANCE IS AT ELEVATION. AFF ABOVE FINISH FLOOR MIN MINIMUM
<br /> 2. PROVIDE WITH BIRD SCREEN,BACKDRAFT DAMPER,AND ROOF CURB ADAPTER FOR ROOF MOUNTED FANS AFR ABOVE FINISH ROOF N NEW q�F�HAN\0
<br /> 3. PROVIDE WITH PRE-WIRED DISCONNECT. APPD APPROVED NIC NOT IN CONTRACT F OF CAUFO
<br /> 4. PROVIDE HINGED BASE KIT. ARCH ARCHITECTURAL OR ARCHITECT OC ON CENTER 06/11/20
<br /> SITE LOCATION: STOCKTON,CA SITE ELEVATION(FT): 26
<br /> 5. LUBRICATE BEARINGS,CHANGE BELTS,AND STEAM CLEAN. BOD BOTTOM OF DUCT R REPLACED
<br /> WINTER OUTDOOR DESIGN TEMP: 30.3 °F SUNNIER OUTDOOR DESIGN TEMP: 101.1 °F DB 70.0 'F WB DL DISCHARGE LINE RA RETURN AIR
<br /> AD REQUIRED
<br /> DPT DIFFERENTIAL PRESSURE TRANSDUCER REE SUPPLY AIR
<br /> WINTER INDOOR DESIGN TEMP: 70.0 °F SUMMER INDOOR DESIGN TEMP: 72.0 'F DB 59.0 °F WB E EXISTING SIM SIMILIAR
<br /> EA EXHAUST AIR SL SUCTION LINE
<br /> GRILLE - REGISTER - DIFFUSER SCHEDULE EC ELECTRICAL CONTRACTOR SM SHEET METAL
<br /> F.O. FLAT OVAL SPEC SPECIFICATION OR SPECIFIED
<br /> GC GENERAL CONTRACTOR SS STAINLESS STEEL
<br /> SYMBOL KEY: LL LIQUID LINE TYP TYPICAL
<br /> A B SD-1 10" MAX MAXIMUM UNO UNLESS NOTED OTHERWISE
<br /> A: FIRST LETTER: S-SUPPLY,R-RETURN,&EXHAUST,T-TRANSFER SECOND LETTER:D-DIFFUSER R-REGISTER G-GRILLE (C) 250 CFM MC MECHANICAL CONTRACTOR VTR VENT THROUGH ROOF
<br /> B.LEAD-IN DUCT SIZE(OR NECK SIZE),UNLESS NOTED OTHERWISE. C.CFM VENTILATION CALCULATIONS O
<br /> EQUIPMENT SIZE
<br /> E
<br /> Q TYPE MATERIAL FINISH MANUFACTURER MODEL NOTES
<br /> NO. FRAME FACE UNIT OSA(CFM) UNIT EXHAUST(CFM)
<br /> O
<br /> SDI LOUVERED SUPPLY DIFFUSER 24x24 SEE PLANS STEEL WHITE TITUS TDC - RTU-1 480 EF-1 15920
<br /> SRI SUPPLY REGISTER SEE SEE STEEL WHITE TITUS 30ORL - M
<br /> PLANS PLANS RTU-2 300 EF-2 1500 I-�-I rQhl
<br /> RTU-3 80 EF-3 750
<br /> V
<br /> O
<br /> RGI LAY-IN RETURN GRILLE 24x2,4 PLANS ALUMINUM WHITE TITUS 50F - RTU-4 230 (E)EF-4 1,450 O
<br /> SEE
<br /> O
<br /> RG2 SIDEWALL RETURN GRILLE 26x12 PLANS ALUMINUM WHITE TITUS 3LF - RTU-5 205 (E)EF-5 325 O
<br /> O
<br /> RTU-6 245 (E)EF-6 1860
<br /> NOTES: Q O
<br /> RTU-7 465 (E)EF-7 600
<br /> RTU-8 95 (E)EF-8 100
<br /> RTU-9 5475 (E)EF-9 195
<br /> RTU-10 5475 EF-10 2531
<br /> RTU-11 5475 (E)EF-11 220
<br /> RTU-12 65 EF-12 400
<br /> AIR CURTAIN SCHEDULE
<br /> (R)EF-14 1725
<br /> MAX AIRFLOW @ HIGH MOTOR INFORMATION EF-15 2531
<br /> EQUIPMENT NO. LOCATION SPEED WEIGHT MANUFACTURER MODEL NOTES
<br /> CFM FPM QUANTITY NO. OF VOLTAGE AND TOTAL (LBS)
<br /> AND SIZE SPEEDS PHASE AMPS
<br /> AC-2 TRUCKDOCK 15441 7567 (3) 1 HP 1 480V-3 PH. 9.6 263 BERNER IDC14-3096AZ-F 1,2,3 TOTAL(OSA) 18,590 TOTAL(EA) 16,107
<br /> AC-3 CEIVING ROO 3933 5166 (1) 1/2HP 1 480V-3 PH. 1.4 80 BERNER IDC12-1036AZ-F 1,2,3 NET POSITIVE PRESSURIZATION: 2,483
<br /> AC-4 TRUCKDOCK 15441 7567 (3) 1 HP 1 480V-3 PH. 9.6 263 BERNER IDC14-3096AZ-F 1,2,3
<br /> AC-5 TRUCKDOCK 15441 7567 (3) 1 HP 1 480V-3 PH. 9.6 263 BERNER IDC14-3096AZ-F 1,2,3
<br /> AC-6 TRUCKDOCK 15441 7567 (3) 1 HP 1 480V-3 PH. 9.6 263 BERNER IDC14-3096AZ-F 1,2,3
<br /> NOTES:
<br /> 1. PROVIDE WITH MOUNTING HARDWARE FOR USE AT DOOR AS INDICATED AND A HEAVY DUTY 24V MAGNETIC REED DOOR LIMIT SWITCH WITH BRACKET PART NUMBER 9503MRS1F2-SS-HD.
<br /> 2. FURNISH FACTORY MOUNTED/WIRED CONTROL PANEL(LEFT HAND)WITH 24V CONTROL VOLTAGE PART NUMBER 9012CS40A3P480-24.
<br /> 3. FURNISH FACTORY MOUNTED/WIRED 30 AMP NON-FUSED TOGGLE DISCONNECT SWITCH(TOP RIGHT HAND)WITH LOCKOUT CAPABILITY PART NUMBER 95081389C-BI.
<br /> SHEET TITLE
<br /> MECHANICAL
<br /> SCHEDULES &
<br /> LEGEND
<br /> N
<br /> SHEET
<br /> M30
<br /> 0
<br /> N
<br /> O
<br /> N
<br /> O