GENERAL NOTES KEYED NOTES
<br /> 1. FURNISH ALL MATERIALS, EQUIPMENT AND SUPPLIES AND PERFORM I EXISTING 10" FIR PROTECTION WATER SUPPLY TO BUILDING TO REVISIONS
<br /> ALL WORK AND OPERATIONS TO REMODEL, EXPAND AND MAKE REMAIN. WATER SYSTEM SUPPLIES THE FOLLOWING WATER
<br /> FUNCTIONAL FIRE SPRINKLER SYSTEMS TO PROVIDE FIRE PROTECTION
<br /> OF ALL AREAS OF THE EXISTING WINCO#10 STOCKTON, CA. THE PRESSURES/FLOWS (FROM AS-BUILT FIRE SPRINKLER DRAWINGS):
<br /> SYSTEM DESIGN SHALL MEET THE REQUIREMENTS OF NFPA 13 2016 STATIC PRESSURE: 55 PSI
<br /> (E) EDITION AND BE IN ACCORDANCE WITH THE DRAWINGS AND RESIDUAL PRESSURE: 50 PSI
<br /> ASSISTANT (E) STORE
<br /> (E) SPECIFICATIONS. FLOW: 1,500 GPM
<br /> MANAGER'S MANAGER'S LAUNDRY 2. THE FIRE SPRINKLER SYSTEM SHALL BE DESIGNED, INSTALLED,
<br /> OFFICE OFFICE ROOM REMODELED AND TESTED IN ACCORDANCE WITH THE APPLICABLE 2 EXISTING ELECTRIC MOTOR DRIVEN FIRE PUMP TO REMAIN. PUMP
<br /> PROVISIONS OF THE FOLLOWING CODES AND STANDARDS: IS RATED TO SUPPLY 80 PSI AT 1,000 GPM WITH A MAXIMUM FLOW
<br /> 203 I 204 208 I A. CALIFORNIA BUILDING CODE (CBC) -2018 EDITION OF 1,500 GPM AT 55 PSI BOOST.
<br /> B. CALIFORNIA FIRE CODE CFC -2018 EDITION
<br /> C. NFPA 13 INSTALLATION OFFR SPRINKLER SYSTEMS -2016 EDITION 3 EXISTING WET-PIPE FIR SPRINKLER RISERS 2 TO REMAIN. RISER
<br /> 1 DROP -- I I I I ... ...... I , I I C D. STOCKTON FIR DEPARTMENT REQUIREMENTS FOR SYSTEM 1 (EAST) SUPPLIES ALL FIR SPRINKLERS EAST OF
<br /> _ I 1 I I 3. THE DESIGN OF THE FIRE SPRINKLER SYSTEMS CONTAINED ON THESE COLUMN LINE 6. RISER FOR SYSTEM 2 WEST SUPPLIES ALL FIRE
<br /> 1" x 1" x 1/2" TEE WITH 1/2" ' ♦ -- I I DRAWINGS IS CONCEPTUAL IN NATURE. THE LOCATIONS SHOWN ON
<br /> TEE WITH 1/2" PLUG ,. SPRINKLERS ST COLUMN LINE 6. )
<br /> --
<br /> ;���- - �� I�� THESE DRAWINGS FOR SPRINKLERS, PIPING AND OTHER FIR WE OF
<br /> p I i 1 I PROTECTION EQUIPMENT AR APPROXIMATE AND MUST BE ADJUSTED
<br /> W h p I I I E 4 EXISTING 6-WAY WALL MOUNTED FIRE DEPARTMENT
<br /> DRY PENDANT BARREL I::: :: 1 I j u I , , , REQUIRED TO MATCH ACTUAL BUILDING CONDITIONS. TH
<br /> -c� _ E , FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE TO FIELD CONNECTION (FDC) TO REMAIN. FDC IS CONNECTED TO FIRE
<br /> FILL SPACE WITH �. J , LYI :.:., : W I Z. [ ) I VERIFY EXISTING PIPING/SPRINKLERS, DEVELOP THE FINAL DESIGN PROTECTION SYSTEMS ON DISCHARGE SIDE OF FIRE PUMP AS
<br /> POLYURETHANE FOAM _ _ , - MEC IC FOR EACH FIR SPRINKLER SYSTEM,PREPARE SHOP DRAWINGS, REQUIRE
<br /> ROM I HYDRAULIC CALCULATIONS AND OBTAIN APPROVAL FROM D BY NFPA 13 8.17.2.4.8.
<br /> (E I
<br /> TOP PANEL OF COOLER { I E K I 10 I AUTHORITY HAVING 5 EXISTING FEED OR CROSS MAIN FOR WET-PIPE FIRE SPRINKLER
<br /> -- - -
<br /> F ---- •� G
<br /> OR FREEZER BOX(N.I.C.) I I R I I I I .. `I F I I 4. THE FIRE SPRINKLER CONTRACTOR SHALL THOROUGHLY REVIEW ALL SYSTEM TO REMAIN. LOCATION IS APPROXIMATE. CONTRACTOR
<br /> 12" MIN. I I F TO FIELD VERIFY LOCATION, EVATION AND SIZE.
<br /> :. .. ;.
<br /> • I ' CONTRACT DRAWINGS AND SPECIFICATIONS THAT IMPACT THE FIRE ON, EL
<br /> 2 I SPRINKLER SYSTEM PRIOR TO BID. ANY QUESTIONS THAT AFFECT THE
<br /> c 6
<br /> �� ������ � :..... : . :� � :��: ;���;:�� � � ` � :"� � DESIGN AND INSTALLATION OF THE FIR SPRINKLER SYSTEM SHALL
<br /> • - �' BUILDING REMODEL TO OCCUR IN AREA SHOWN. DEMO, MODIFY,
<br /> BE RESOLVED BEFORE THE CONTRACT IS AWARDED.NO ALLOWANCE ARCH.PROJECT NO.
<br /> A WILL BE PERMITTED IN THE CONTRACT FOR CHANGES MADE AFTER ADJUST AND/OR ADD FIRE SPRINKLERS AND PIPING AS REQUIRED
<br /> AWARD OF CONTRACT. TO ACCOMMODATE REMODEL AND ENSURE FIRE SPRINKLER 2006
<br /> PROTECTION THROUGHOUT BUILDING IN ACCORDANCE WITH NFPA DRAWN
<br /> I (E) I I 5 CONTRACTOR SHALL
<br /> ONS AND EQUIPMENTSHOP DATA DRAWINGS,
<br /> HYDRAULIC SPRINKLER 13. REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND
<br /> SECURITY (E) EXTENT OF REMODEL. COORDINATE WITH MECHANICAL AND NSS
<br /> ROOM HALLWAY SYSTEM AND SUBMIT TO LOCAL AUTHORITY HAVING JURISDICTION ELECTRICAL SYSTEMS. LOCATIONS OF FIRE SPRINKLERS AND
<br /> "- DRY PENDENT HEAD & 206 FOR REVIEW/APPROVAL. CONTRACTOR MAY REQUEST COPIES OF CHECKED
<br /> ESCUTCHEON. FOR USE 201 HYDRAULIC CALCULATIONS FROM THE PROJECT ARCHITECT FOR PIPING ON DRAWINGS IS APPROXIMATE AND SHOULD BE FIELD
<br /> IN ALL FREEZERS AND SUBMITTAL TO LOCAL JURISDICTION IF REQUIRED. VERIFIED BY CONTRACTOR. GTJ
<br /> COOLER BOXES 6.2 6.4 7 7.3 8 9 10 6. REFERENCE THE ARCHITECTURAL PLANS FOR CHANGES TO THE SUBMITTAL DATES
<br /> 7 EXISTING DRY-PIPE FIR SPRINKLER SYSTEM PROTECTING INSIDE
<br /> BUILDING FEATURES THAT AFFECT THE EXISTING FIRE SPRINKLER AND BELOW FRONT AND SIDE CANOPIES TO BE COMPLETELY 06/11/2020
<br /> SYSTEM INSTALLATION. THE FIRE SPRINKLER CONTRACTOR IS DEMOLISHED. EXISTING PIPING IS BEGINNING TO DEVELOP LEAKS
<br /> RESPONSIBLE FOR MAKING HIS OWN JOB CHECK AND ANY NECESSARY
<br /> ADJUSTMENTS TO THE EXISTING FIRE SPRINKLER SYSTEM PRIOR TO RELATED TO EXCESSIVE INTERIOR CORROSION. REMOVE ALL
<br /> FABRICATION. MAKE FINAL COORDINATION WITH OTHER TRADES AND PIPING, FITTINGS, SPRINKLERS AND ESCUTCHEONS. REMOVE
<br /> OFF-SET PIPING AND HEADS AS NECESSARY. MAJOR CONFLICTS SHALL PIPING BACK TO AND INCLUDING EXISTING RISER. OTB DATE
<br /> FIRE SPRINKLER PLAN BE BROUGHT TO THE ATTENTION OF THE GENERAL CONTRACTOR FOR PIPING/SPRINKLERS TO BE REPLACED WITH NEW
<br /> FREEZER/COOLER PENETRATION NOT USED Np RESOLUTION BY THE ARCHITECT. PIPING/SPRINKLERS CONNECTED TO EXISTING WET-PIPE FIRE
<br /> 1 2 OFFICE MEZZANINE RTg 7. ADJUST,ADD AND/OR REMOVE SPRINKLERS, MAINS, BRANCH LINES SPRINKLER SYSTEMS.
<br /> NTS NTS NTS NTS AND OTHER FIRE SPRINKLER SYSTEM COMPONENTS OR DEVICES AS
<br /> %z" 1'-0" REQUIRED TO MEET THE REMODEL CONDITIONS AND TO PROTECT ALL 8 PENDENT FIRE SPRINKLERS THROUGHOUT BAKERY, SERVICE DELI,
<br /> AREAS OF BUILDING ADDITIONS. EXISTING BRANCH LINES AND SEAFOOD AND PIZZA SALES SHALL BE HIGH TEMPERATURE RATED.
<br /> SPRINKLERS IN AREAS NOT UNDERGOING REMODEL REMAIN(UNLESS Q
<br /> OTHERWISE NOTED). COMPLETE SPRINKLER COVERAGE SHALL BE w o
<br /> PROVIDED THROUGHOUT THE BUILDING AS PART OF THIS WORK. 9 HYDRAULIC DESIGN AREA#1 (WALL OF VALUES). OWNER x w x z° � o
<br /> REQUIREMENT (EXCEEDS NFPA 13)FOR 20'HIGH RACK STORAGE OF H w o°o
<br /> 8. EXISTING FIRE SPRINKLER SYSTEM PROTECTING BUILDING IS CLASS IV COMMODITY. MINIMUM DISCHARGE DENSITY OF 0.80 w Q o o s
<br /> HYDRAULICALLY CALCULATED TO PROVIDE A MINIMUM DISCHARGE GPM/S FT OVER 1 500 S FT WITH 250 GPM HOSE ALLOWANCE. ° `' Q ¢ "6 cn� v ° c
<br /> DENSITY OF 0.60 GPM/SQ FT OVER 2,000 SQ FT. EXISTING DESIGN IS DESIGN Q AREA REQUIRES 84.8 PSI AT 1490.6 GPM AT DISCHARGE ° w a°z N o u w
<br /> ADEQUATE TO PROTECT SALES FLOOR AND SERVICE DEPARTMENTS x w Q �"
<br /> ORDINARY HAZARD GROUP 2). HYDRAULICALLY REDESIGN PORTIONS FLANGE OF EXISTING FIRE PUMP. PUMP SUPPLIES (ASSUMING 55 PSI � z x x w w 'u�© e 2
<br /> F FIRE SPRINKLER SYSTEM PROTECTING HIGH PILED STORAGE TO FROM CITY SUPPLY)APPROXIMATELY 88.8 PSI AT 1490.6 GPM. �°z w x
<br /> COMPLY WITH OWNER REQUIREMENTS (EXCEED NFPA 13). CALCULATE a u¢F H°z a o
<br /> to
<br /> SYSTEM TO PROVIDE A MINIMUM DISCHARGE DENSITY OF 0.80 GPM/SQ 10 HYDRAULIC DESIGN AREA#2 WEST RACKS). OWNER a A Q a W �° 1 r
<br /> FT OVER 1,500 SQ FT WITH 250 EXTERIOR HOSE ALLOWANCE. ( ) z w¢¢w¢ H ° o
<br /> REQUIREMENT (EXCEEDS NFPA 13) FOR 20'HIGH RACK STORAGE OF w w a o H ' t
<br /> 9. OFF-PREMISE SUPERVISION OF FIRE SPRINKLER SYSTEM AND CLASS IV COMMODITY. MINIMUM DISCHARGE DENSITY OF 0.80 4,n w o z 0
<br /> GPM/SQ FT OVER 1,500 SQ FT WITH 250 GPM HOSE ALLOWANCE. z w o u 2 w v v
<br /> PROVISION OF LOCAL WATER FLOW ALARM DEVICE PROVIDED BY FIR w x ¢ z V,' a I k
<br /> DESIGN AREA REQUIRES 92.8 PSI AT 1377.7 GPM AT DISCHARGE Q �F u�° z
<br /> ALARM CONTRACTOR(RE: F1 &F1.1). FLANGE OF EXISTING FIR PUMP. PUMP SUPPLIES (ASSUMING 55 PSI � x v P.ti v
<br /> w „xoow H
<br /> 10. ALL DEVICES AND MATERIALS USED FOR THE CONSTRUCTION OF THE FROM CITY SUPPLY)APPROXIMATELY 96.7 PSI AT 1377.7 GPM. F 3 a a� z
<br /> FIRE SPRINKLER SYSTEM SHALL BE UL LISTED FOR USE IN FIRE 11 HYDRAULIC DESIGN AREA#3 (GROCERY TRANSFER). OWNER
<br /> SPRINKLER SYSTEMS. `+
<br /> REQUIREMENT (EXCEEDS NFPA 13)FOR 20'HIGH RACK STORAGE OF
<br /> 11. WATER SUPPLY AVAILABLE AT DISCHARGE OF EXISTING FIRE PUMP CLASS IV COMMODITY. MINIMUM DISCHARGE DENSITY OF 0.80
<br /> (FROM FIRE SPRINKLER SHOP DRAWINGS) GPM/SQ FT OVER 1,500 SQ FT WITH 250 GPM HOSE ALLOWANCE.
<br /> STATIC: 156 PSI DESIGN AREA REQUIRES 56.3 PSI AT 1464.9 GPM AT DISCHARGE Q
<br /> RESIDUAL: 105 PSI FLANGE OF EXISTING FIRE PUMP. PUMP SUPPLIES (ASSUMING 55 PSI 'n
<br /> FLOW: 1,500 GPM FROM CITY SUPPLY)APPROXIMATELY 90.7 PSI AT 1464.9 GPM. UJ Q v�
<br /> 12. NEW FIRE SPRINKLER PIPING SHALL BE STEEL PIPE CONFORMING TO 0C!3 "" Zr
<br /> ANSI/ASTM A53,ASTM A135 OR A795. 2-1/2" AND LARGER(NOM)PIPING 12 HYDRAULIC DESIGN AREA#4 (FRONT CANOPY). ORDINARY a Cil m
<br /> SHALL BE SCHEDULE 10. 2" AND SMALLER(NOMINAL) SHALL BE HAZARD GROUP 1. MINIMUM DISCHARGE DENSITY OF 0.15 GPM/SQ Q -5
<br /> ALLIED DYNATHRAD PIPING OR APPROVED EQUAL. ALL PIPING SHALL - Q N
<br /> HAVE A CRR(U.L. CORROSION RESISTANCE RATIO)EQUAL TO OR FT OVER HYDRAULICALLY MOST REMOTE 7 SPRINKLERS (NFPA 13 Pe
<br /> GREATER THAN 1.0. 11.2.3.4.2) WITH 250 GPM HOSE ALLOWANCE. DESIGN AREA
<br /> REQUIRES 47.1 PSI AT 159.9 GPM AT DISCHARGE FLANGE OF
<br /> 13. NEW FITTINGS: PROVIDE CAST IRON FITTINGS FOR THREADED PIPE. EXISTING FIRE PUMP. PUMP SUPPLIES ASSUMING 55 PSI FROM CITY ■ W
<br /> PROVIDE RUBBER GASKETED FITTINGS FOR ROLL GROOVED SCHD 10 SUPPLY)APPROXIMATELY 151.4 PSI AT 159.9 GPM. W
<br /> MAINS. PROVIDE WELDED OUTLETS FOR BRANCH LINE ATTACHMENTS
<br /> TO MAINS. MECHANICAL TEES MAY BE USED FOR CONNECTION TO co � Ln
<br /> EXISTING BRANCH LINES. PLAIN END FITTINGS ARE NOT ACCEPTABLE. 13 TYPE 1 HOOD OVER GREASE-PRODUCING COOKING EQUIPMENT. W
<br /> SEE MECHANICAL DRAWINGS FOR WET CHEMICAL SYSTEM DESIGN W m �.
<br /> 14. WHERE PIPE ELEVATION CHANGES ARE SHOWN THEY ARE AND SUBMITTAL REQUIREMENTS. CONTRACTOR SHALL PROVIDE _ 00
<br /> APPROXIMATE DIMENSIONS ONLY. CONTRACTOR SHALL SET CUTTING SHOP DRAWINGS AND OBTAIN PERMIT AS REQUIRED BY LOCAL Q W v cq
<br /> LENGTHS TO MAINTAIN ELEVATIONS OF MAINS &LINES AS INDICATED AUTHORITY. �� W
<br /> &OFFSET AS NECESSARY TO AVOID BUILDING ELEMENTS. T a
<br /> 15. HANGERS: PROVIDE PIPE SUPPORT IN ACCORDANCE WITH NFPA 13. BIDDING INFO NOTES i JL
<br /> p x
<br /> 1-1/4 AND SMALLER PIPE: MINIMUM ONE HANGER PER LENGTH OF PIPE �n 0-�
<br /> AND MAXIMUM 12'-0" BETWEEN HANGERS. 1. ALL INFORMATION CONTAINED IN "SCHEDULE OF GENERAL NOTES"
<br /> 1 ,
<br /> 1-1/2" AND LARGER: MAXIMUM 15'-0" BETWEEN HANGERS. ON SHEET F2.1 IS TO BE INCLUDED ON SHOP DRAWINGS, WITH
<br /> EDITING WHERE APPROPRIATE, BY THE CONTRACTOR.
<br /> 1 16. SEISMIC BRACING: BRACING SHALL BE PROVIDED FOR ALL NEW
<br /> i I PIPING 2-1/2" OR GREATER IN NOMINAL DIAMTER(INCLUDING 2-1/2" 2. THE SPRINKLER SYSTEM DESIGN HAS BEEN COORDINATED WITH
<br /> -----------------------------i___________________________________________________________________________----_i____________--------------------------------------- -----------------------------------L------------- BRANCH LINES)AS REQUIRED BY NFPA#13 USING SCHEDULE 40 PIPE. OTHER BUILDING ELEMENTS AND REFLECTS THE INSURANCE,
<br /> RIGID COUPLINGS USED ON FEED MAINS AND CROSS MAINS. OPERATIONAL AND AESTHETIC CONCERNS OF THE OWNER.
<br /> DEVIATION FROM THE DESIGN OTHER THAN DEVIATIONS PERMITTED
<br /> 17. PROVIDE EXTRA SPRINKLERS PER NFPA 13 FOR PROTECTION BELOW IN THE BID DOCUMENTS AND APPROVED IN WRITING BY THE
<br /> 1 I 1 DUCTS, CONDUIT, REFRIGERATION LINES OR SIMILAR EXPOSED F � Usl�
<br /> ENGINEER SHALL NOT BE PERMITTED.
<br /> - ------------- - - - - - - - - - - - - - - - - - - - - j - - - ---- ------------------------------------ - - � OBSTRUCTIONS OVER 48" WIDE. PROVIDE EXTRA SPRINKLERS AS ��
<br /> REQUIRED BY NFPA 13 WHERE SPRINKLER DISCHARGE IS OBSTRUCTED. GFiE0Of3YT.
<br /> M O N T U B A N AVENUE I WHERE DROPS TO PIPING BELOW OBSTRUCTIONS ARE REQUIRED, 3. THE FIRE SPRINKLER CONTRACTOR SHALL THOROUGHLY REVIEW ONES
<br /> 1 I DROPS SHALL BE RUN TIGHT TO OBSTRUCTION TO MINIMIZE VISUAL ALL CONTRACT DRAWINGS AND SPECIFICATIONS THAT IMPACT THE �`
<br /> ABOVE GROUND DOUBLE CHECK I INSTALL TAMPER SWITCHES ON OS&Y VALVES I IMPACT. FIRE SPRINKLER SYSTEM PRIOR TO BID. ANY QUESTIONS THAT No. S 4 ;
<br /> i DETECTOR ASSEMBLY I AFFECT THE DESIGN AND INSTALLATION OF THE FIRE SPRINKLER
<br /> I SYSTEM SHALL BE RESOLVED THROUGH ISSUANCE OF REQUEST FOR AIE�iaICAl
<br /> sI'
<br /> 18. SPRINKLERS & ESCUTCHEONS CONTRACTOR MAY SELECT �
<br /> _.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._ ._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.1.110-1
<br /> ._.._.._.._.._.._.._. .._. . Ew....�Fw_. ..__ .._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.._.. INFORMATION(RFI) THROUGH APPROPRIATE CHANNELS. NO
<br /> ' ' MAKE/MODEL OF FIR SPRINKLERS TO BE USED EXCEPT ALL FIR MODIFICATIONS TO SYSTEM DESIGN IS PERMITTED UNLESS '�' oi; l� ,
<br /> \ i SPRINKLERS USED MUST BE APPROVED BY THE OWNER. ACCEPTABLE SPECIFICALLY AUTHORIZED IN WRITING IN RFI RESPONSES.
<br /> MANUFACTURER/SIN FOR ALL ACCEPTABLE FIRE SPRINKLERS ARE 06/11/2020
<br /> 1 I o i LISTED BELOW. ALL ESCUTCHEONS SHALL BE LISTED FOR USE WITH 4. CONTRACTOR SHALL PREPARE AND SUBMIT SHOP DRAWINGS AS
<br /> REQUIRED BY THE SPECIFICATIONS. ALL INFORMATION SHOWN ON
<br /> EACH SPRINKLER. INSTALL ALL SPRINKLERS IN ACCORDANCE WITH THE F2.1 AND F2.2 DRAWINGS SHALL BE INCLUDED ON THE SHOP
<br /> 1 i MANUFACTURER'S RECOMMENDATIONS AND ALL APPLICABLE DRAWINGS IN ADDITION TO INFORMATION THAT MAY BE REQUIRED
<br /> INSTALL BURIED CONDUIT AND i I I PROVISIONS OF NFPA 13. BY THE LOCAL JURISDICTION. PIPING SYMBOLOGY, HEAD SYMBOLS,
<br /> I CONNECT VALVE SWITCHES TO j I 1 I ETC,. SHALL NOT BE CHANGED. CONTRACTOR SHALL BE
<br /> FA SYSTEM IN BUILDING RACK STORAGE AREAS (SALES AND STOCKROOM) -K-16.8, BRASS RESPONSIBLE FOR MAKING HIS OWN "JOB CHECK" &MAKE O
<br /> ' ADJUSTMENTS AS NECESSARY PRIOR TO FABRICATION.
<br /> c PENDENT, ORDINARY TEMPERATURE RATED. TYCO TY7251 OR EQUAL.
<br /> c c 5. TO FACILITATE THE PREPARATION OF DRAWINGS, THE CONTRACTOR
<br /> PIN
<br /> SUPPORT AREAS WITH FINISHED CEILINGS -K-5.6, GLASS BULB, QUICK MAY REQUEST DWG FORMAT DRAWING FILES FROM THE GENERAL O
<br /> • , I RESPONSE, CHROME PLATED, PENDENT OR RECESSED PENDENT. CONTRACTOR. PREPARATION OF SHOP DRAWINGS ON A COMPUTER
<br /> 0 I TEMPERATURE RATING (ORDINARY, INTERMEDIATE OR HIGH) SHALL BASED DESIGN PROGRAM IS ENCOURAGED.
<br /> C c c C r BE AS INDICATED ON DRAWINGS AND IN SPRINKLER LEGEND. 6. WHERE PIPE ELEVATION CHANGES ARE SHOWN THEY ARE
<br /> 1 I ACCEPTABLE SPRINKLERS IN THIS CATEGORY: GLOBE GL5601. APPROXIMATE DIMENSIONS ONLY. CONTRACTOR SHALL SET CUTTING4� >
<br /> i I o 1 RELIABLE R3615, TYCO TY3231, VICTAULIC V2708 OR VIKING VK302. LENGTHS TO MAINTAIN ELEVATIONS OF MAINS &LINES AS INDICATED
<br /> & OFFSET AS NECESSARY TO AVOID TRUSS MEMBERS.
<br /> SUPPORT/SALES AREAS WITHOUT CEILINGS -K-5.6, GLASS BULB, QUICK
<br /> ' --------------------------------------------�
<br /> r---------- - --- ---------- 0 ', 1 RESPONSE, CHROME PLATED,UPRIGHT. TEMPERATURE RATING 7. CONTRACTOR MAY REQUEST COPIES OF HYDRAULIC CALCULATIONS
<br /> (ORDINARY, INTERMEDIATE OR HIGH) SHALL BE AS INDICATED ON FROM THE PROJECT ARCHITECT FOR SUBMITTAL TO LOCAL
<br /> C JURISDICTION IF REQUIRED.
<br /> I r4 I , 1 DRAWINGS AND IN SPRINKLER LEGEND. ACCEPTABLE SPRINKLERS IN 1
<br /> W I I I 0 THIS CATEGORY: GLOBE GL5615, RELIABLE R3625, TYCO TY3131, 8, PIPE SIZES INDICATED ON DRAWINGS SHALL BE CONSIDERED TO BE A M
<br /> I I I VICTAULIC V2704 OR VIKING VK300 MINIMUM. SMALLER DIAMETER PIPING MAY NOT BE USED.
<br /> I , SUBSTITUTION OF LARGER DIAMETER PIPING IS ACCEPTABLE IF
<br /> c c c i DRY-PENDENT (WALK-IN COOLERS/FREEZERS) -K-5.6, GLASS BULB, PROVIDED AT NO ADDITIONAL COST TO THE OWNER. CONTRACTOR
<br /> Z I I j I CHROME PLATED, PENDENT, 401 TYPE ESCUTCHEON, INTERMEDIATE PIPE DIAMETERS AND DIT HE INFORMATALL RUN NEW HYDRAULIC ONS BASED ON THEION CONTAINED ON THE ED --
<br /> j I I 0 \. TEMPERATURE RATED. SEE DETAIL 1 ON SHEET F2.1. DRAWINGS TO BE DEPICTED ON THE HYDRAULIC PLACARDS. NEW O
<br /> At �,� �\ HYDRAULIC CALCULATIONS SHALL BE SUBMITTED TO AHJ AND O
<br /> 18. WET CHEMICAL AUTOMATIC EXTINGUISHING SYSTEMS SHALL BE PROJECT ENGINEER. CORROSION RESISTANCE RATIO OF ALL PIPING
<br /> c c c PROVIDED PER MECHANICAL DRAWINGS AND ARE REFERENCED ON SHALL BE EQUAL TO OR GREATER THAN 1.0. �-i O
<br /> J I I THIS DRAWING FOR COORDINATION PURPOSES ONLY. CONTRACTOR �--�
<br /> I I 9. EDIT THE FITTINGS SECTION TO REFLECT THE JOB SPECIFIC USE OF O
<br /> PROVIDING WET CHEMICAL SYSTEMS SHALL SUBMIT SHOP DRAWINGS FITTINGS IF DIFFERENT FROM THAT SHOWN. O ►�/�
<br /> , AS REQUIRED BY LOCAL AUTHORITY. lil
<br /> I I c c c \. \ 10. CONTRACTOR SHALL NOT CONNECT TO UNDERGROUND SUPPLY MAIN
<br /> i I I 19. INSTALL PIPING PITCHED TO DRAIN PER NFPA 13. PROVIDE AUXILIARY WITHOUT VERIFICATION THAT PIPING HAS BEEN FLUSHED AND
<br /> DRAINS PER NFPA 13 TO FACILITATE DRAINAGE OF TRAPPED PORTIONS PRESSURE TESTED IN ACCORDANCE WITH NFPA# 13 &24. O
<br /> OF FIRE SPRINKLER PIPING.
<br /> U . . L--�
<br /> 1 i - ' ' � \� 20. PHASE REMODEL OF EXISTING FIR SPRINKLER SYSTEMS TO MINIMIZE e�
<br /> \ DISRUPTIONS TO FIRE SPRINKLER PROTECTION OF BUILDING. FIR
<br /> I SPRINKLER SYSTEMS MAY ONLY BE TAKEN OUT OF SERVICE WHILE FIRE
<br /> FIRE PUMP&FIRE SPRINKLER RISERS
<br /> I o � O O � \ SPRINKLER INSTALLER IS ON SITE ACTIVELY WORKING ON FIR
<br /> SPRINKLER SYSTEM UPGRADES AND PROVIDING A FIRE WATCH. FIRE
<br /> Q1 ® ® ® C c c �� SPRINKLER SYSTEMS MUST BE RETURNED TO SERVICE UPON
<br /> `.. ♦``� \ COMPLETION OF EACH WORK SHIFT.
<br /> 1 I W I N C O FOODS STORE INSTALL TAMPER SWITCHES ON OS&Y��VALVES .. ♦♦♦ \
<br /> j FI EPT. CONNECTION ® ® C C C l/�'''
<br /> FF= 20. 50
<br /> � I i �. �\ I I
<br /> 3
<br /> ♦♦
<br /> ------------------------------------------------------------------------------ �.�• ♦♦ - <V 3i� DOWN TO FIRE
<br /> I I I �• ti
<br /> C C C •�,�' ' SPRINKLE CROSS
<br /> MAIN BEL W
<br /> 000 - - - - •-•- * ROOF DEC
<br /> I 23� 1-1/2"
<br /> 1 I
<br /> c c C C EC D EC OR ASV D MBLY
<br /> ----�� ---•-
<br /> I I
<br /> I r -----
<br /> � 232 I I
<br /> 1 o I C c
<br /> I
<br /> 233
<br /> AC C C N N N
<br /> 1 I I INSTALL BURIED CONDUIT AND ~
<br /> I I
<br /> e ° e e e e e e e e ° ° ° ° e I CONNECT VALVE SWITCHES TO FA 1-1/2" 1-1/2'
<br /> SYSTEM IN BUILDING
<br /> I
<br /> 1 E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E
<br /> I
<br /> --------- ---------------------------------------------------------- -
<br /> ---� 234
<br /> I
<br /> SHEET TITLE
<br /> ' I I FIRE
<br /> _x.....................................................X_. _.._._._.._.._._._.._.._._._.._.. ............................................__._.. _._.._.._._.._.._._._.._.._._._.._.._._._._ ._.._.._.._.._.._.._.._.._.._.._.._.._.._._.._..__ .............................................. x._. ._ _x_ _x_ _,�.
<br /> SPRINKLER
<br /> 1 5 SCHEDULES &
<br /> I
<br /> DETAILS
<br /> GRAPHIC SCALE FIRE SPRINKLER PLAN
<br /> FIRE PROTECTION BACKFLOW PREVENTER SITE SCHEMATIC 40 20 40 80 CANOPY TOWER NORTH
<br /> 3 SHEET
<br /> 1" 100'-0" 1 INCH -40 FEET %2" 1'-0"