Laserfiche WebLink
Environmental Health DepartmentUnderground Storage Tank Program Inspection ReportDate:December 16, 2020Facility Address:8660 LOWER SACRAMENTO RD, STOCKTONFacility Name:fast and easy mart #103Single-Walled Non-Pressurized Piping404□ V □ R □ COSFailure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair (pre-1984)CCR 2643(e), 2661(f)Other Violations2010□ V □ R □ COSUnlisted General violation See belowSUMMARY OF VIOLATIONS(CLASS I, CLASS II, or MINOR - Notice to Comply)RemarksItem #106CCR 2632(d), 2641(h) Failure to submit and maintain a current facility plot plan / site map. OBSERVATION: An accurate UST Monitoring Site Plan was not submitted. UST Monitoring Site Plan is lacking some essential elements, for example, location of each sensor, line leak detector etc. REGULATION GUIDANCE: A site plan must be submitted identifying the locations where monitoring will be performed. The site plan must show the general layout of tanks and piping and clearly identify locations of the following equipment, if installed: 1) monitoring system control panels; 2) in-tank liquid level probes (if used for leak detection); 3) devices monitoring tank annular spaces or vault; 4) devices monitoring product piping; 5) devices monitoring fill piping; 6) devices monitoring vent piping; 7) devices monitoring vapor recovery piping; 8) devices monitoring vent/transition sumps; 9) devices monitoring under-dispenser containment; 10) line leak detectors; and 11) devices monitoring any other secondary containment areas. CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov/ and upload a copy of the UST Monitoring Site Plan.This is a repeat violation, Class II.107HSC 25292.2; CCR 2711(a)(11) Failure to submit and maintain complete and current financial responsibility documents. 1) OBSERVATION: Financial responsibility documents have not been submitted to the EHD. The most recent financial responsibility documents in CERS are dated 12/03/2018. REGULATION GUIDANCE: Current financial responsibility documents are required to be submitted annually. CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov/, and upload the required documents.2) OBSERVATION: Current finanacial responsibility documents were not available on site for inspection. REGULATION GUIDANCE: A copy of these documents shall be accessible on site at all times. CORRECTIVE ACTION: Immediately locate and retain a copy on site.This is a repeat violation, Class II.FA0003726 PR0231161 SC001 12/16/2020EHD 23-01 Rev. 9/16/2020Underground Storage Tank Program OIRPage 4 of 91868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD