Laserfiche WebLink
F 100A MAIN LUG ONLY <br /> SERVES: TENANT SPACE NEYV PANELBOARD 1PH 3WIRE 208/120V CONDUIT SCHEDULE <br /> SERIES RATED NAME DESCRIPTION <br /> LOCATION: STOCKROOM GROUND BAR CONDUIT SIZE QTY WIRE SIZE(MFR# WIRE QTY <br /> MOUNTING: SURFACE 101 DISPENSER POWER-NON DIESEL 314" - #12 THWN-2 1#12 HOT, 1#12 NEUT, 1#12 GR <br /> CK LOAD SERVED WIRE BRKR PL PHASE G PHASE A PL BRKR WERE LOAD SERVED GK <br /> 1 DISPENSER f <br /> 102 DISPENSER SUMP SENSOR/FLOW METER 314, 1 BELDEN #88760 2 <br /> 12 20 1 1.08 1.08 1 20 12 DISPENSER 2 2 <br /> EXISTING PANEL 3#12, 3/4"C 3 SWITCHED NEUTRAL -- -- - 0.00 0.00 - -- - SWITCHED NEUTRAL 4 102A DISPENSER 1 SUMP SENSORIFLOW METER/ <br /> PRESSURE SENSOR 314" 1 BELDEN #88760 3 <br /> /, 5 SPARE -- 2O 1 0.00 0.00 1 20 -- SPARE B 2-WIRE TWISTED PAIR 2 PAIR .� � <br /> FEEDER TO REMAIN 7 SPARE -- 20 1 0.00 0.00 1 20 -- SPARE g 103 DISPENSER DATA* 314" 2 <br /> CAT6 (FOR FUTURE EMV) 1 O <br /> ONE-LINE DIAGRAM IS FOR REFERENCE SPARE -- 20 1 0.00 0.00 1 20 - SPARE 10 <br /> XISTIN NEW ONLY. FUEL CONTRACTOR TO VERIFY 11 SPARE -- 2O 1 0.00 0.00 1 20 -- SPARE 12 104 2HP STP POWER 314° - #12 THWN-2 2#12 HOTS, 1#12 GR p U <br /> FEEDER PANEL LOADS TO BE PLACED ON PANELS. 13 SPARE -- 20 1 0.00 0,00 1 20 -- SPARE 14 RUL TANK ATG/SUMP SENSORS/INTERSTITIAL <br /> PANEL F 15 SPARE -- 20 1 0.00 0.00 1 20 -- SPARE 16 105 VACUUM SENSOR 314" 1 BELDEN #88760 7#88760 <br /> 17 RUL STP 12 20 2 1.21 1.21 2 20 12 PUL STP 18 106 PULIDSL TANK ATG/SUMP SENSORSANTERSTITIAL <br /> 19 ----- -- -- - 1.21 1.21 - 20 VACUUM SENSOR 1 1 BELDEN#88760 13#88760 cs, <br /> 21 D-BOX CONTROLLER 12 20 1 0.11 1.09 2 20 12 DSLSTP22 o0 <br /> 107 VENT/FILL SUMP SENSOR 314" 3 BELDEN #88760 1 <br /> POLE, 100 AMP 23 SPACE -�- -- 0.00 1.09 24 <br /> CONTACTOR EXISTING EMERGENCY GASOLENE 25 SPACE - 0.00 0.00 __ __ _____SPACE 26 o <br /> 108 STP SUMP SENSOR/ATG PROBE/VACUUM SENSOR 3/4" 3 BELDEN #88760 <br /> 5 <br /> SHUT-OFF SWITCH. TO BE 27 LOW VOLTAGE DISC 20 1 0.36 0.00 SPACE 28 � <br /> RECONFIGURED TO SHUT DOWN 29 SPACE 0.00 0.3fi 1±2 0 12 OVERFILL ALARM 30 N <br /> CONTACT AS SHOWN. 100 INTERCOM 1 <br /> NOTE: TOTAL 6.14 3.87 KVA - BELDEN 8762 2 PAIR PER CALL BOX <br /> (1) GENERAL CONTRACTOR TO INSTALL PANELS CIRCUIT BREAKERS AND CONDUIT. 51.17 32.25 AMPS <br /> (2) FUEL CONTRACTOR SHALL INSTALL WIRING (FROM CIRCUIT BREAKERS TO TOTAL LOAD 10.01 KVA 48.13 AMPS 110 DISPENSER POWER- DIESEL 3/4" 2 #12 THWN-2 1#12 HOT, 1#12 NEUT, 1#12 GR Prato 08-21-17 <br /> EQUIPMENT), RELAYS, ETC. MAKE ALL CONNECTIONS AND COMPLETE SEAL OFF. PER NEC ARTICLE 220 FEEDER LOAD 10,01 KVA 48.13 AMPS 111 1.5HP STP POWER 314" 3 #12 THWN-2 2#12 HOTS, 1#12 GR <br /> STP POWER CONDUITS MUST BE RUN IN SEPARATE RACE=WAY. COORDINATE POWER INTEGRITY PANEL AND FUELING 112 AIR VAC MACHINE 3/41" - #12 THWN-2 1#12 HOT, 1#12 NEUT, 1#12 GR <br /> PARTIAL ELECTRICAL ONE LINE DIAGRAM ENTIRE WIRING RUN MUST BE IN RIGID PVC COATED AREA CIRCUIT LOAD INFORMATION WITH FUEL GC. <br /> _ <br /> GALVANIZED STEEL CONDUIT, USE ONLY ROB ROY CONDUIT FUEL CONTRACTOR TO SUPPLY AND INSTALL NEW 113 CANOPY LIGHTING POWER 314"� _ SEE BLDG ELECTRICAL SEE BLDG ELECTRICAL <br /> TYPES "PERMA-COAT", "PLASTI-BOND"OR"KORKAP" PANELS AND VERIFY ELECTRIC � W W <br /> ELECTRICAL CONDUITS. NO PVC OR RNC CONDUIT ALLOWED. PANEL CAN MEET LOAD REQUIREMENTS. 114 CANOPY SIGN POWER 314°' - SEE BLDG ELECTRICAL SEE BLDG ELECTRICAL ti Z_ J <br /> USE ONLY ROB ROY CONDUIT TYPES "PERMA-COAT", 115 WJ <br /> VENT SUMP SENSOR 3/4-` 1 BELDEN #88760 1 x � W W <br /> "PLASTI-BOND"OR "KORKAP" ELECTRICAL CONDUITS AT � � � Z = <br /> FIBERGLASS TANK SUMPS OR WHERE BRAVO F-17-RR OR 116 PRICE SIGN POWER 3/4" 1 PULL STRING PULL STRING � � W o � U <br /> F-10-RR ENTRY FITTINGS ARE CALLED OUT FOR FIRST 10' OF � " <br /> RUN. TRANSITION TO RIGID NONMETALLIC CONDUIT(RNC) z Z w <br /> 117 OVERFILL ALARM/ACKNOWLEDMENT SWITCH 314"' 1 #12 THWN-2 1#12 HOT1#12 NEUT1#12 GR 0.) U), , N Q Z J <br /> WHERE ALLOWED BY JURISDICTION, > _ J W <br /> 118 OVERFILL ALARM/ACKNOWLEDMENT SWITCH 3/4"' 1 BELDEN #88760 1 z - <br /> RUN PVC COATED GALVANIZED STEEL FOR WIRING RUNS � J <br /> EXPOSED TO THE WEATHER; FOR ENCLOSING MAIN * REFERENCE GILBARCO FIELD WIRING DIAGRAM FE-363R FOR COMPLETE SPECIFICATIONS W Q <br /> Z <br /> ? Z 'Q <br /> GROUNDING CONDUCTOR: WHERE REQUIRED FOR * CONTRACTOR TO UPSIZE CONDUCTORS FOR VOTLAGE DROP AS REQUIRED Lu � W U EL <br /> ❑ <br /> MECHANICAL PROTECTION OR WHERE SPECIFICALLY W }. > Q - Z <br /> INDICATED. J W ti U Fr <br /> W W Jd" Q <br /> WITH THE EXCEPTION OF THE FIRST AND THE LAST 10' OF THE � W W <br /> m U <br /> UNDERGROUND RUN AND ONLY WHERE AHJ ALLOWS, 00 <br /> RIGID <br /> NONMETALLIC CONDUIT(RNC) IS ALLOWED FOR J <br /> Y W <br /> U <br /> UNDERGROUND RUNS IF CONDUIT IS BURIED AT A MINIMUM _ � Q <br /> OF 2'. <br /> W - <br /> o ❑ <br /> O <br /> ii <br /> 0 <br /> ANNULAR SPACE RESERVOIR <br /> REF 4-G3.0 <br /> 42"CONTAINMENT MANWAY ma <br /> ° WITH PRODUCT FILL AND <br /> 7VAPOR CONNECTION <br /> 7 �? k ,l REF 1-G4.1 <br /> OS 7 42" CONTAINMENT MANWAY <br /> 77 <br /> ANNULAR SPACE RESERVOIR WITH SUBMERGED PUMP <br /> AND TANK PROBE <br /> REF 4-G3.0 777 REF 1-G4.0 <br /> 42"CONTAINMENT MANWAY 11� 0 <br /> WITH SUBMERGED PUMP =k <br /> AND TANK PROBE REF 2-G4.0 /T <br /> 42" CONTAINMENT MANWAY ��v 42"'CONTAINMENT MANWAY <br /> WITH PRODUCT FILL AND �7 �c®' WITH SUBMERGED PUMP <br /> DIESEL VENT CONNECTION Z � <br /> REF 2-G4.1 �� 717 ,lb AREFAND�,l-G4,2 ROBE <br /> v <br /> 708 p� 42" CONTAINMENT MANWAY m <br /> WITH PRODUCT FILL AND cn o <br /> 708 VAP C NECTION ; v S <br /> 7�� o. Z� 2 REF'2-G4. n`too 'T v <br /> rn <br /> NOTE: ROUTE ALL CONDUITS UNDERGROUND TO C-STORE ELEC J' EXTENTS OF N.E.C. CLASSIFIED O b < <br /> ROOM. DATACOM CABLE EXCESS TO BE COILED IN ELEC RM Q AREA TYPICAL ALL DISPENSERS a r <br /> FOR ROUTING ABOVE CEILING IN C-STORE TO FINAL r LL <br /> TERMINATION POINT. <br /> 0 <br /> STORE SIDE act ❑ � � T�� <br /> a D © W �' Q C <br /> F-1 110 ` _ _ <br /> € NOTE: PVC CONDUIT (WHERE ALLOWED BY AHJ), MAY BE USED. ATA 103 178 NEW PRICE SIGN ON c:) <br /> Q CD CQ <br /> SEE SPECIFICATION SHEET G16.0, SECTION 2.3.1 FOR EXISTING MONUMENT SIGN Z <br /> a LOCATIONS WHERE PVC CONDUIT MAY BE USED. EXISTING CLEAN AIRco <br /> cisSIDE 1 �iy FIELD VERIFY LOCATION <br /> SEPARATOR 102A _ � � r7? ( ) 0 � <br /> SENSOR DISP 1 778 N Q <br /> FOR STP POWER CONDUITS, USE ONLY ROB ROY a Ela w m <br /> STREET SIDE v <br /> CONDUIT TYPES "PERMA-COAT" "PLASTI-BOND" � <br /> OR"KORKAP"WHERE BRAVO FITTINGS ARE USED 3: 0 <br /> �IS PERMITTED. � U (t1 <br /> AND CONDUITSOINp EIPERATE RACEWAYOUTE Q ��'Oy <br /> NO PVCp� <br /> W ❑ ❑ U <br /> CD a o DN � S� nN0ctici� S� �3 <br /> REMOTE VENT F-2 110 _ _ -6 L ; 0 0 o E <br /> FUELING CONTRACTOR; �� � �o �� � ���U o <br /> EXTEND CONDUITS AS REQUIRED TO NEW DATA 103 o c 2 <br /> a Q om. o� oc ( cL <br /> 0 <br /> DISPENSERS AND FUEL TANKS . TIE TO EXISTING SIDE 1 w r, - • 0_ m o <br /> Ln WHERE IT IS POSSIBLE. NEW CONDUITS AS 102 E X c o �. E 0 <br /> REQUIRED. SEE SPECIFICATION SHEET G16.0, SENSOR DISP 2 c f° � �- � c <br /> z SECTION VII, 2.3.1 FOR CONDUIT TYPES. ® O a o <br /> as Qp �'.q m 3� ca u�i= crs <br /> 0 115 p ?p, �[ � . ? CDmOL � °• <br /> � NOTE: PULL ALL NEW WIRES AND PULL STRINGS � E � � �-ow <br /> � ��L� �U � <br /> z <br /> m o W.;-o 5 <br /> AS REQUIRED. ti OR <br /> 0 o us0C0 <br /> c� c}a �,� � o m �2 � a s�? <br /> W <br /> NOTE: TIE NEW DISPENSER AND SUMP CONDUIT <br /> D E � oc4x0 Vis_ <br /> INTO EXISTING ELECTRICAL ROOM AS REQUIRED. <br /> FIELD VERIFY EXISTING CONDITIONS. opV.C)FE ,fo <br /> c7 <br /> air 8497 rn <br /> zr) TE OF C4fl <br /> 0 <br /> c.t <br /> di <br /> ME <br /> a NOT USED- <br /> � _ <br /> SHEET: <br /> NONE UDERGROUND � U MATIC <br /> , G9 . 0 <br /> FUELING - USA <br />