Laserfiche WebLink
Tesoro/USA#6815013975 E. Hwy 88 Lockeford, CA 95237 SR0064416 <br /> Section 3 Why are there three vents?Yet the plan states the vents are manifolded. If <br /> manifolded then the vent riser detail diagram should show it. <br /> Section B Add water tight and vapor tight lid w/gasket. <br /> Section C 58"hydrostatic sensor" is pointing to the interstitial sensor. Remove#58 and <br /> the interstitial sensor with reservoir that it is pointing to. There is already#98 on the right <br /> side of the detail diagram. <br /> 8. WD1.0 Tank Sump Components#6 should be 857080-111 diesel 12 inch and 857080- <br /> 101 gas 12 inch. <br /> Chart needs to list vacuum sensors, interstitial sumps and under dispenser containment <br /> sumps sensors, and smart liquid sensors. <br /> Verify that the monitoring panel model to be installed is the Veeder Root TLS-350 plus. <br /> SEE REV• PI A0 <br /> If you have any further questions, please contact me at(209) 468-3453. <br /> Tha�k you, <br /> d _ <br /> Aris Cacapit, REHS <br /> Registered Environmental Health Specialist <br /> 2 <br />