Laserfiche WebLink
Tesoro/USA##150 13975 E Hwy 88 Lockeford, CA 95237 SR0064416 <br /> product, only deck iron steel, Resubmit the site plan sheet TK2.1 specifying black iron <br /> steel pipe. SEE REVISED SHEET TK2-1 <br /> 14. The site plan sheet TK2-3 in 029 of the general notes refers to a tank monitoring system <br /> certified to most the requirements of a tank integrity test may be substituted for the <br /> Enhanced Leak Detection (ELD)test. A certified tank monitoring system cannot be <br /> substituted for an ELD lest. Resubmit the site plan sheet TK2 3 without#29. <br /> REMOVED NOTE 929. SHEET TK2-3. <br /> 15 The Me plan sheets TK3-2 and TK3.3 detail of the fill and turbine sumps does not <br /> demonstrate vapor tightness and the detail of the fill sump lid does not demonstrate a <br /> gasket for water tightness Resubmit the site plan suet TK3-2 with updated details <br /> demonstrating vapor tightness for the fill and turbine sumps and a gasket for water <br /> tightness of the fill sump lid <br /> 16, The site pian sheet TK3.3 specifies#54 galvanized iron pipe for the diesel tank. <br /> Galvanized iron pipe Is not allowed for diesel product, only black iron steel. Resubmit the <br /> site plan sheet TK3-3 spocifying black iron steel pipe. SEE REVISED SHEET TK3-3 <br /> 17. The site plan sheets TK4-1 and TK4-2 indicate that an oft set dispenser frame is being <br /> used. A portion of the piping in the dispenser is not being contained by fine under <br /> dispenser containment (UDC). A conversion frame may be required for the UDC There <br /> are two that are approved <br /> 18. The site plan sheets TK3-2 and TK5-1 indicate 87 vacuum lines for the product and the <br /> vapor recovery lines. The site plan sheet TK5-3 indicates 87 vacuum lines for the <br /> product, vapor recovery, and the vent lines. Resubmit the site plan sheets and specify If <br /> the vent and or vapor recovery lines are mantfolded. Installation must be consistently <br /> specified on the site plan sheets. <br /> 19. The site plan sheet TK5.3 detail of the vent sump lid does not demonstrate vapor and <br /> water tightness. Resubmit the site plan sheet TK3-2 with updated details demonstrating <br /> vapor tightness for the fill and turbine sumps and a gasket for water tightness of the fill <br /> sump lid. <br /> 20 Tank buoyancv calculations and lank 6e down information must be submitted. <br /> SEE REVISED SHEET TK3-1 <br /> 21 Submit the contractor technician's training certification of for Xerxes. <br /> 22 Three copies of each updated site plan sheet must be sent to the EHD <br /> If you have any further questions, please contact me at(209) 468-3453. <br /> t hank you. <br /> r <br /> Ans Cacaprt, REHS <br /> Registered Environmental Health Specialist <br /> 3 <br />