Laserfiche WebLink
Hazardous Waste Tank bib,-� <br /> System Integrity Report <br /> ==M= = <br /> For <br /> HMT Inspection <br /> The Kraft Heinz Company <br /> Stockton CA February 1 <br /> � o 34 Page 14 of 34 <br /> 3.1 CONTAINMENT ASSESSMENT AND EVALUATION <br /> We have evaluated the tank containment and find the following to be true: <br /> The tank containment (secondary polyethylene tank detail) has now and will <br /> continue to contain in the future liquids that can be classified as non-RCRA <br /> hazardous materials. <br /> The following assessment details are known or have been evaluated for the tank: <br /> 1. Pursuant to 22 CCR §66265.193(b)(1); The secondary <br /> containment (secondary tank) / concrete containment area is <br /> designed and constructed such that it will contain any minor leak of <br /> stored liquid until it can be properly cleaned; <br /> 2. Pursuant to 22 CCR §66265.193(b)(2); The secondary tank / <br /> concrete containment has been designed to accepted industry <br /> practice for total storage volume and is free of defects and may <br /> temporarily retain these non-RCRA hazardous materials until such <br /> leaks or spills are detected and cleaned up; <br /> 3. Pursuant to 22 CCR §66265.193(c)(1); The secondary tank is <br /> adequately constructed with materials that are compatible with the <br /> waste to be placed in the tank system and has sufficient strength <br /> and thickness to prevent failure due to pressure gradients, physical <br /> contact with the stored waste, climatic conditions, the stress of <br /> installation, and the stress of daily operations as required; <br /> 3. Pursuant to 22 CCR §66265.193(c)(2); The concrete slab under <br /> the tank is adequately constructed according to accepted industry <br /> practice and supports the Hazardous Waste Tank as required; <br /> 4. Pursuant to 22 CCR §66265.193(c)(3) and (4); The hazardous <br /> materials action plan currently in place at the facility provides that <br /> any leakage or spills from the tanks in this area will cleaned as soon <br /> as detected (visual inspection of this area is performed by the <br /> operators responsible for this operations area); <br /> 5. Pursuant to 22 CCR §66265.193(d); Secondary containment <br /> consists of a secondary tank; <br /> NDTRPTNE.DOT REV 2 23264941 Hazardous Wast Tank r3(Rev 1).doc 3/16/2021 1:52 PM <br />