Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 6. TANK SECONDARY CONTAINMENT TEST <br /> Test Method Developed by ❑ Manufacturer © Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure © Vacuum ❑ Hydrostatic <br /> Test Equipment Used: Vacuum Pump/Vacuum Gauges in Hg. <br /> Tank ID 1-Regular 87 2-Super 91 3-Diesel-W 4-Diesel-E <br /> Tank Manufacturer Trusco GST Trusco GST Trusco GST Trusco GST <br /> Tank Capacity 12K 8K 20K 20K <br /> Test Start Time 8:30 8:30 8:40 8:50 <br /> Initial Reading -10 Hg. -10 Hg. -10 Hg. -10 Hg. <br /> Test End Time 10:30 10:30 10:40 10:50 <br /> Final Reading -10 Hg. -10 Hg. -10 Hg. -10 Hg. <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria No Loss No Loss No Loss No Loss <br /> Tightness Test Results ® Pass ❑ Fail I ® Pass ❑ Fail I ® Pass ❑ Fail I ® Pass ❑ Fail <br /> 7. PIPE SECONDARY CONTAINMENT TEST <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ® Pressure ❑ Vacuum ❑ Hydrostatic <br /> Test Equipment Used: Pressure Gauges in Psi/Nitrogen <br /> Pipe Run ID 1-87 2-91 3-Dsl-Auto 4-Dsl-Siphon <br /> Pipe Manufacturer Ameron FRP Ameron FRP Ameron FRP Ameron FRP <br /> Test Start Time 8:35 8:45 8:55 9:05 <br /> Initial Reading 5 Psi 5 Psi 5 Psi 5 Psi <br /> Test End Time 9:35 9:45 9:55 10:05 <br /> Final Reading 5 Psi 5 Psi 5 Psi 5 Psi <br /> Change in Reading 0 Psi 0 Psi 0 Psi 0 Psi <br /> Pass/Fail Criteria No Loss No Loss No Loss No Loss <br /> Tightness Test Results © Pass ❑ Fail © Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Pipe Run ID 5-Dsl-M-E-HF <br /> Pipe Manufacturer Ameron FRP <br /> Test Start Time 9:15 <br /> Initial Reading 5 Psi <br /> Test End Time 10:15 <br /> Final Reading 5 Psi <br /> Change in Reading 0 <br /> Pass/Fail Criteria No Loss <br /> Tightness Test Results © Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 2of5 <br />