Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-PS-87 2-PS-91 3-PS-Dsl Sip 4-PSDsI HF-E <br /> Sump Manufacturer Unknown FGC Unknown FGC Unknown FGC Unknown FGC <br /> Sump Depth (inches) 65" 63" 72" 72" <br /> Sump Bottom to Top of 16" 19" 23" 23" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:42 8:47 9:21 9:26 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:12 9:17 9:51 9:56 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID 5-Dsl Auto 6-Dsl HF-W 7-13sl AST-Tr UDC 1&2 <br /> Sump Manufacturer Unknown FGC Unknown FGC Bravo Sysfgc Bravo Syscsc <br /> Sump Depth (inches) 69" 69" 31" 10" <br /> Sump Bottom to Top of 34" 32" 15" BP <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:02 10:07 10:47 8:52 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 10:32 10:37 11:17 9:22 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />