Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard 0 Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID UDC 3&4 UDC 5&6 UDC 7&8 UDC 9-A <br /> Sump Manufacturer Bravo Syscsc Bravo Syscsc Bravo Syscsc Bravo Syscsc <br /> Sump Depth (inches) 10" 10" 10" 10" <br /> Sump Bottom to Top of BP BP BP BP <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:57 9:02 9:07 10:52 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:27 9:32 9:37 11:22 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results © Pass ❑ Fail © Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 9&10A UDC 10&11A UDC 11&12A UDC 12&13A <br /> Sump Manufacturer Bravo Syscsc Bravo Syscsc Bravo Syscsc Bravo Syscsc <br /> Sump Depth (inches) 10" 10" 10" 10" <br /> Sump Bottom to Top of BP BP BP BP <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:57 11:02 11:07 11:12 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 11:27 11:32 11:37 11:42 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ❑x Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4of5 <br />