Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8. IN-TANK GAUGING TESTING <br /> ® Check this box if tank gauging is used only for inventory control. <br /> ❑ Check this box if NO tank gauging equipment is installed. Yes No NA <br /> Do not complete this section if either box is checked. <br /> All wiring has been: 1) visually inspected for kinks, breaks and proper entry and 0 0 0 <br /> termination; and 2 tested for ground faults? <br /> Were all in-tank gauging probes visually inspected for damage and residue buildup ❑ ❑ <br /> to ensure that floats move freely, functionally tested, and confirmed operational? <br /> Was accuracy of system's product level readings tested? ❑ ❑ ❑ <br /> Was accuracy of system's water level readings tested? ❑ ❑ ❑ <br /> Were all probes reinstalled properly? ❑ ❑ ❑ <br /> Were all items on the equipment manufacturer's maintenance checklist completed? ❑ ❑ ❑ <br /> Probe ID Probe Model Tanks Monitored Pass Fail <br /> ❑ 0 <br /> 0 0 <br /> ❑ 0 <br /> ❑ IM <br /> 9. COMMENTS <br /> Describe all answers marked "No"or "Fail"and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> DIESEL STP SUMP HAD A SMALL AMOUNT OF LIQUID IN THE SUMP,THE LIQUID WAS <br /> REMOVED FROM THE DIESEL STP SUMP. THE DIESEL STP SUMP SENSOR WAS FOUND TO <br /> BE SETTING ON THE TANK ANNULAR HUMP AND NOT AT THE LOWEST SPOT IN THE SUMP <br /> AFTER TESTING THE DIESEL STP SUMP SENSOR WAS SET TO THE LOWEST SPOT IN THE <br /> SUMP. <br /> THE TANK ANNULAR SENSORS WERE LABELED INCORRECTLY SENSOR LABELING WAS <br /> CHANGED IN LIQUID SENSOR SET UP TO REFLECT THE CORRECT TANK ANNULAR. <br /> Page 5 of 6 <br />