Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />8. SUMP/UDC TEST <br />Test Method Developed by ® Manufacturer 0 Industry Standard ® Professional Engineer <br />Test Type ® Pressure R7 Vacuum 0 Hydrostatic <br />Test Equipment Used: Incon STS <br />Sump/UDC ID Reel UDC <br />Sump Manufacturer cont Solutions <br />Sump Depth (inches) 36" <br />Sump Bottom to Top of <br />17„ <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time 10:03 <br />Initial Reading 5.9300 <br />Test End Time 10:37 <br />Final Reading 5.9299 <br />Change in Reading .0001 <br />Pass/Fail Criteria .002 <br />Tightness Test Results Pass ® Fail ® Pass rj Fail ® Pass ® Fail ® Pass ® Fail 11 <br />Sump/UDC ID <br />Sump Manufacturer <br />Sump Depth (inches) <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />Tightness Test Results ® Pass ® Fail ® Pass ® Fail ® Pass ® Fail ® Pass rl Fail <br />Additional copies of this page may be attached. <br />All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 5 <br />