Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUN r <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Gemco Ripon Truck Plaza Inc. 1022 E FRONTAGE RD, RIPON June 29, 2021 <br /> Single-Walled Non-Pressurized Piping <br /> 404 CCR 2643(e),2661(f) Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair(pre-1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ■V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 214 CCR 2712 Failure to comply with UST operating permit conditions. <br /> OBSERVATION: The facility is not in compliance with the written conditions of the operating permit. <br /> REGULATION GUIDANCE: The owner and operator of underground storage tank(UST)systems shall comply with <br /> all requirements of the permit issued for the operation of the UST system. <br /> CORRECTIVE ACTION: Immediately take all necessary actions to bring these UST systems into compliance. <br /> Immediately restore all monitoring to this system,or remove all fuel from the USTs within 48 hours and immediately <br /> comply with closure requirements. <br /> This is a Class II violation. <br /> 301 HSC 25292.1(a)Failure to operate UST system to prevent unauthorized releases including leaks, spills and overfills. <br /> OBSERVATION: The 87 and 91 underground storage tanks systems(UST)at this facility are not in use.According <br /> to the technician, Jason Shaw,the monitoring panel was disconnected and removed approximately a month ago. <br /> The system is not currently being monitored for leaks. <br /> REGULATION GUIDANCE: The underground storage tank system shall be operated to prevent unauthorized <br /> releases, including spills and overfills. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor restore <br /> all monitoring to this system, or remove the fuel from the USTs within 48 hour and immediately comply with closure <br /> requirements. <br /> This is a repeat violation, Class II. <br /> 308 CCR 2632(c), 2634(d),2636(f)Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The 87 and 91 underground storage tanks systems(UST)at this facility are not in use.According <br /> to the technician, Jason Shaw,the monitoring panel was disconnected and removed approximately a month ago. <br /> The system is not currently being monitored for leaks. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor restore <br /> all monitoring to this system, or remove the fuel from the USTs within 48 hour and immediately comply with closure <br /> requirements. <br /> This is a Class II violation. <br /> FA0000650 PR0231604 SCO21 06/29/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 4 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />