Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUN r <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Gemco Ripon Truck Plaza Inc. 1022 E FRONTAGE RD, RIPON June 29, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 309 CCR 2666(b)(2), 2636(f)(1) Failure to have continuous monitoring that activates audible-visual alarm or stops flow at <br /> dispenser. <br /> OBSERVATION: The 87 and 91 underground storage tanks systems(UST)at this facility are not in use.According <br /> to the technician, Jason Shaw,the monitoring panel was disconnected and removed approximately a month ago. <br /> The system is not currently being monitored for leaks. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: CORRECTIVE ACTION: Correct immediately by having a properly licensed, trained, and <br /> certified contractor restore all monitoring to this system, or remove the fuel from the USTs within 48 hour and <br /> immediately comply with closure requirements. <br /> This is a Class II violation. <br /> 311 HSC 25291(b)Monitoring system incapable of detecting leak into secondary containment(pre-Jul 2003). <br /> OBSERVATION: The 87 and 91 underground storage tanks systems(UST)at this facility are not in use.According <br /> to the technician, Jason Shaw,the monitoring panel was disconnected and removed approximately a month ago. <br /> The system is not currently being monitored for leaks. <br /> REGULATION GUIDANCE: The underground storage tank system shall be designed and constructed with a <br /> monitoring system capable of detecting leaks from primary containment into secondary containment. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor restore <br /> all monitoring to this system, or remove the fuel from the LISTS within 48 hour and immediately comply with closure <br /> requirements. <br /> This is a Class II violation. <br /> 314 CCR 2631(g), 2632(c)(2)Failure to continuously monitor interstitial space with audible-visual alarm system (pre-Jul <br /> 2004). <br /> OBSERVATION: The 87 and 91 underground storage tanks systems(UST)at this facility are not in use.According <br /> to the technician, Jason Shaw,the monitoring panel was disconnected and removed approximately a month ago. <br /> The system is not currently being monitored for leaks. <br /> REGULATION GUIDANCE: The interstitial space shall be monitored with a monitoring system connected to an <br /> audible and visual alarm system. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor restore <br /> all monitoring to this system, or remove all fuel from the USTs within 48 hours and immediately comply with closure <br /> requirements. <br /> This is a Class II violation. <br /> FA0000650 PR0231604 SCO21 06/29/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />