ELECTRICAL SPECIFICATIONS
<br />GENERAL
<br />1.
<br />NOTES:
<br />ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA
<br />CODE
<br />OF
<br />REGULATIONS,
<br />INCLUDING THE FOLLOWING:
<br />TITLE
<br />24,
<br />CCR,
<br />PART 2,
<br />2016 CBC
<br />TITLE
<br />24,
<br />CCR,
<br />PART 3,
<br />2016 CEC
<br />TITLE
<br />24,
<br />CCR,
<br />PART 4,
<br />2016 CMC
<br />TITLE
<br />24,
<br />CCR,
<br />PART 9,
<br />2016 CFC
<br />ALL APPLICABLE
<br />LOCAL
<br />CODES.
<br />2. ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, ETC.
<br />REQUIRED TO CARRY ON AND COMPLETE THE WORK. PERMIT BY OWNER.
<br />3. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND
<br />PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER
<br />EXECUTION AND COMPLETION OF ALL "ELECTRICAL WORK" WHETHER SPECIFICALLY
<br />MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED HEREIN, AND/OR IMPLIED THEREBY TO
<br />CARRY OUT THE APPARENT INTENT THEREOF.
<br />4. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS'
<br />LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL
<br />WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY
<br />FURNISHED BY THAT AGENCY.
<br />5. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE
<br />AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE,
<br />CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS AND VERIFY
<br />THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT
<br />AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES.
<br />6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWN UNLESS OTHERWISE
<br />NOTED OR REQUIRED BY CODE.
<br />7. ALL LUMINAIRES AND BALLASTS SHALL BE CERTIFIED BY THE MANUFACTURER TO
<br />THE CALIFORNIA ENERGY COMMISSION.
<br />B. FLASH AND COUNTER FLASH ALL ITEMS PASSING THROUGH THE ROOF. ANY ROOF
<br />PENETRATIONS WILL BE APPROVED BY THE OWNER. ROOFING MFG. HAS SPECS. AS TO
<br />NOT VOID 20 YEAR WARRANTY.
<br />9. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE
<br />INSTALLED AT LEAST 24" BELOW GRADE. BACKFILL IN 6" THICK, PROPERLY MOISTENED
<br />LAYERS, SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT LESS THAN THAT OF
<br />ADJACENT, UNDISTURBED EARTH. RESTORE SURFACES, ROADWAYS, WALKS, CURBS,
<br />WALLS, EXISTING UNDERGROUND INSTALLATIONS TO ORIGINAL CONDITION IN AN
<br />ACCEPTABLE MANNER.
<br />10. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND
<br />SWITCHES BEFORE THEY ARE ROUGHED IN AT NO EXTRA COST.
<br />11. ALL EXIT SIGNS TO BE UNSWITCHED.
<br />NAMEPLATES & IDENTIFICATION:
<br />INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC.
<br />NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS
<br />ROUND HEAD CADMIUM PLATED SELF—TAPPING SCREWS, BRASS BOLT, OR WITH A PLASTIC
<br />RESIN ADHESIVE GLUE, GOODYEAR "PLIEBOND" OR EQUAL.
<br />ELECTRICAL SPECIFICATIONS
<br />GENERAL NOTES (CONT.):
<br />HVAC UNIT DISCONNECTS:
<br />1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR
<br />EXACT LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. VERIFY AND
<br />CONFIRM THE ACTUAL MOUNTING LOCATION ON THE HVAC UNIT FOR THE DISCONNECT.
<br />2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST
<br />FUSE SIZE ON THE UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE
<br />FUSES OF THIS RATING.
<br />3. FURNISH AND INSTALL ALL LINE VOLTAGE AND LOW VOLTAGE CONDUITS AND LINE
<br />VOLTAGE WIRING (LOW VOLTAGE WIRING BY OTHERS) TO HVAC EQUIPMENT AND
<br />ASSOCIATED CONTROLS AND DEVICES AS SHOWN ON THE ELECTRICAL AND MECHANICAL
<br />PLANS, UNLESS OTHERWISE NOTED.
<br />WIRING METHODS:
<br />1. ALL WIRING SHALL BE INSTALLED IN STEEL CONDUITS, CONCEALED IN WALL AND
<br />CEILING U.O.N.
<br />2. MINIMUM CONDUIT SIZE SHALL BE 1/2". MINIMUM ACCEPTABLE CONDUITS ARE
<br />A. GALVANIZED RIGID STEEL.
<br />B. GALVANIZED STEEL EMT.
<br />C. LIQUID TIGHT STEEL FLEX — FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT
<br />D. FLEXIBLE STEEL CONDUIT — FOR INDOOR FINAL CONNECTIONS TO
<br />MECHANICAL EQUIPMENT (NOT TO EXCEED 36").
<br />E. PVC CONDUIT SCHEDULE 40, UNDERGROUND.
<br />3. NMC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING.
<br />4. MC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING.
<br />WIRING DEVICES:
<br />UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS
<br />(BROWN, WHITE, GREY, BEIGE OR IVORY) AS SELECTED BY THE ARCHITECT:
<br />A. WIRING DEVICES LEVITON # HUBBELL # P & S #
<br />SINGLE POLE SWITCH 1221 1221 2OAC1
<br />THREE WAY SWITCH 1223 1223 20AC3
<br />DUPLEX CONV. OUT. 15A 5262 5262 5262
<br />DUPLEX GFI CONV. OUT. GF5262
<br />DEVICE PLATES:
<br />1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE SMOOTH NYLON OR APPROVED
<br />EQUAL UNLESS OTHERWISE NOTED. ALL DEVICE PLATES FOR OUTDOOR USE SHALL
<br />BE RAISED METAL.
<br />2. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL
<br />PLATES. WEATHERPROOF COVERS TO BE SNAP TYPE COVERS.
<br />3. DEVICE PLATES FOR TELEPHONE AND COMPUTER OUTLETS TO BE PROVIDED BY
<br />OWNER'S VENDOR. ALL TELEPHONE AND COMPUTER SYSTEM WIRING BY OWNER'S
<br />VENDOR.
<br />I ELECTRICAL SPECIFICATIONS I
<br />GENERAL NOTES (CONT.):
<br />SUPPORTS:
<br />1. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL
<br />ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT.
<br />2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS,
<br />TO METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION
<br />ANCHORS AND MACHINE SCREWS OR BOLTS.
<br />GROUNDING:
<br />1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND
<br />SPECIFICALLY INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, ETC.
<br />PANELBOARDS:
<br />UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL
<br />SCHEDULE, WITH THE NUMBER AND SIZE OF BREAKERS INDICATED ON THE PANEL
<br />SCHEDULE. SINGLE POLE, TWO POLE AND THREE POLE BREAKERS SHALL BE BOLT—
<br />ON TYPE. THE PANEL DOORS SHALL HAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE
<br />KEYED ALIKE AND HAVE TYPEWRITTEN DIRECTORIES INDICATING FIXTURES,
<br />EQUIPMENT, OR OUTLETS SERVICED BY EACH BREAKER. ALL BUSSING SHALL BE
<br />COPPER.
<br />WORKING CLEARANCES FOR PANELS & SWITCHBOARDS
<br />1. COORDINATE WITH OTHER TRADES TO ENSURE CODE REQUIRED WORKING
<br />CLEARANCES, ACCESS, ETC. FOR PANELS AND SWITCHBOARDS PER C.E.C.
<br />SECTIONS 110-16 AND 384-4.
<br />TESTING:
<br />1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS
<br />AND IMPROPER GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY
<br />AND GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND
<br />WHETHER SUCH TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY
<br />SHALL BE LOCATED, REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE.
<br />2. DEMONSTRATE TO THE OWNER AND THE ARCHITECT, THAT THE ENTIRE
<br />INSTALLATION IS COMPLETE, IN PROPER OPERATING CONDITION AND THAT THE
<br />CONTRACT HAS BEEN PROPERLY AND FULLY EXECUTED. PROVIDE ALL
<br />INSTRUMENTS TO MAKE SUCH TESTS.
<br />NORTH
<br />ELECTRICAL SITE PLAN
<br />SCALE: 1/16"=1'-0" (I
<br />En ineerin
<br />`'
<br />50 years
<br />4512 Feather River Or "F. Stockton. CA 95219
<br />209-478-8270 1 www.hcs-eng.com
<br />® Richard C. Smith, PE richard@hcs-eng.Can
<br />❑ Bhupendra Patel, PE bhupendra@hcs-mg.con
<br />❑ Elizabeth Aguilar elizabeth@hcs-eng.com
<br />PROJECT " 2019247
<br />spl COPYRIGHT 2019
<br />THIS DOCUMENT, AND THE IDEAS AND
<br />DESIGNS INCORPORATED HEREIN, AS AN
<br />INSTRUMENT OF PROFESSIONAL SERVICE,
<br />IS THE PROPERTY OF `apl" AND IS
<br />NOT TO BE USED, IN WHOLE OR IN
<br />PART, FOR ANY OTHER PROJECT
<br />PLANNING■■■
<br />RCHITECTUREN■ ■
<br />m 0
<br />P I
<br />ARCHITECTURE PLUS INC.
<br />4335—B NORTH STAR
<br />WAY
<br />MODESTO, CA 95356
<br />ph. 209.577.4661
<br />fx. 209.577.0213
<br />www.apiarc.com
<br />FRANK C. BOOTS
<br />JOSEPH L. SMITH
<br />RODNEY C. ALONZO
<br />A R C Hl T E C T S
<br />Q
<br />U
<br />p
<br />Q
<br />z ry
<br />W
<br />Q12 0
<br />W D__
<br />> ry
<br />O z
<br />ry I--
<br />Q a- 0
<br />N � z
<br />— d
<br />Q Z Q
<br />ry Q
<br />o-
<br />z
<br />0
<br />CI
<br />CK
<br />a
<br />J
<br />a
<br />rn
<br />J
<br />a
<br />U_
<br />v
<br />w
<br />J
<br />W
<br />O
<br />Z
<br />Q
<br />to
<br />0
<br />O
<br />Z
<br />J
<br />6
<br />IZ'
<br />W
<br />Z
<br />W
<br />C7
<br />QRpF ESSIpy
<br />t,�0 Rp C. S "�
<br />No. E14303
<br />w Exp. 6-30-21
<br />"C TR
<br />Or CALIF p�
<br />DATE : AUGUST 2019
<br />JOB NO. : 18-114
<br />DRAWN: BA
<br />CHECKED: RCS
<br />SHEET:
<br />E I I