Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-91-PS 2-Red DsIPS 3-Trans PS-1 4-Trans PS-2 <br /> Sump Manufacturer Unknown FGC Unknown FGC Unknown FGC Unknown FGC <br /> Sump Depth (inches) 35" 30" 47" 28" <br /> Sump Bottom to Top of 10" 10" 41" 15" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1:52 1:57 1:02 1:39 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 2:22 2:27 1:32 2:09 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 1-91 UDC 2-91 UDC 3-RD <br /> Sump Manufacturer Bravo S-FGCS Bravo S-FGCS Bravo S-FGCS <br /> Sump Depth (inches) 13" 13" 13" <br /> Sump Bottom to Top of 7" 7" 7" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1:07 1:12 1:47 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 1:37 1:42 2:17 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />