VR-201-Z/VR-202-Z -4- Exhibit 15 <br /> 7.2.3 Continue recording HC Analyzer readings and time in 5-minute increments <br /> for 20 minutes (5 recordings total). Record these readings and times on <br /> Form 1. If the Permeator shuts off before 5 readings, repeat sections 7.2.2 <br /> and 7.2.3 until completed. <br /> 7.2.4 Calculate the average HC concentration from the 5 readings and record this <br /> on Form 1. <br /> 7.2.5 If the HC concentration average is less than or equal to 3.0%, record the <br /> compliance test as a "Pass". If the concentration average is greater than <br /> 3.0% HC, record the compliance test as a "Fail". If a failure is recorded, the <br /> ARID Permeator AT-150 is not in compliance with Exhibit 2. <br /> 8. ALTERNATIVE TEST PROCEDURES <br /> This procedure shall be conducted as specified. Modifications to this test procedure shall <br /> not be used to determine compliance unless prior written approval has been obtained from <br /> the CARB Executive Officer or delegate, pursuant to Section 14 of Certification Procedure <br /> CP-201. <br />