Laserfiche WebLink
1.4.2. Break-Away Reconnection: <br /> Reconnect the breakaway assembly per the procedure in the Re-connectable <br /> Breakaway Coupling section of the CARB Approved Installation, Operation <br /> and Maintenance Manual. <br /> 1 .4.3. Liquid Leak and Meter Creep Test: <br /> Authorize the fueling position, purge any air from the fueling position by dispensing at <br /> least two gallons of product into an approved container, and then inspect the hanging <br /> hardware for liquid leaks and/or meter creep. <br /> Note: With the fueling position still authorized and no product dispensing, the <br /> fueling position gallon display should not count up for at least two minutes <br /> while extending and twisting the hanging hardware to inspect for liquid leaks <br /> and/or meter creep. <br /> If no liquid leaks or meter creep are observed, proceed to section 1.4.4 of this <br /> procedure. If liquid leaks or meter creep are observed the operator may replace the <br /> curb hose, and/or nozzle, and/or breakaway, and/or whip hose, using the installation <br /> procedures and functional tests specified in the applicable CARB Approved <br /> Installation, Operation and Maintenance Manual (IOM), and re-conduct the liquid leak <br /> and meter creep test. If liquid leaks or meter creep are observed after replacement of <br /> the equipment, leave the dispenser out of service and contact a Certified Technician <br /> for repairs. <br /> 1 .4.4. Nozzle Bag Test: <br /> Conduct the Nozzle Bag Test using the procedure from Exhibit 7 of Executive Order <br /> VR-201 or VR-202. If the bag around the nozzle does not collapse, proceed to <br /> section 1.4.5 of this procedure. If the nozzle bag test fails, the operator may replace <br /> the nozzle using the installation procedures and functional tests specified in the IOM. <br /> 1 .4.5. Insertion Interlock and Automatic Shutoff Tests: <br /> • Test the insertion interlock feature of the nozzle using the procedures outlined in <br /> Sections 1.1.7 and 1.1 .8 in the Healy Model 900 Nozzle section of the IOM. If the <br /> nozzle fails either of these tests, the operator may replace the nozzle using the <br /> installation procedures and functional tests specified in the IOM. <br /> • Test the automatic shutoff feature of the nozzle using the procedures outlined in <br /> Sections 1.2.8, 1.2.9 and 1.2.10 in the Healy Model 900 Nozzle section of the <br /> IOM. If the nozzle fails any of the tests, the operator may replace the nozzle using <br /> the installation procedures and functional tests specified in the IOM. <br /> 1-4 <br /> CARB Approved IOM 1 —Systems Scheduled Maintenance—EO's VR-201 and VR-202 <br />