Underground Storage Tank <br /> Secondary Containment Testing Report Farm <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum R3 Hydrostatic <br /> Test Equipment Used: lake test <br /> SumplUDC ID reg stp plus stp sup stp udc 1/2 <br /> Sump Manufacturer unknown unknown unknown environ <br /> Sump Depth (inches) 67 63 62 30 <br /> Sump Bottom to Top of 23 23 22 10 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:36 9:48 9:48 11:21 <br /> Initial Reading 27in 27in 26in 14in <br /> Test End Time 12:36 10:48 10:48 12:21 <br /> Final Reading 27in 27in 26in 14in <br /> Change in Reading 0 0 0 0 <br /> PasslFail Criteria .125in .125in .125in .125in <br /> Tightness Test Results 0 pass ❑ Fail 0 Pass ❑ Fail 14 Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC IID udc 3/4 udc 5/6 udc 7/8 udc 9/10 <br /> Sump Manufacturer environ environ environ environ <br /> Sump Depth (inches) 30 30 30 30 <br /> Sump Bottom to Top of 10 10 10 10 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1121 9:48 11:21 11:21 <br /> Initial Reading 14in 14in 14in 14in <br /> Test End Time 1221 10:48 1221 1221 <br /> Final Reading 14in 14in 14in 14in <br /> Change in Reading 0 0 0 0 <br /> PassfFall Criteria .125in .125in .125in .125in <br /> Tightness Test Results R] Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fall"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />