Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMPIUDC TEST <br /> Test Method Developed by Manufacturer v/ industry Standard Lj Professional Engineer <br /> Test Type Lj Pressure EjVacuum ZHydrostatic <br /> Test Equipment Used:ancon TS-STS <br /> Sump/UDC ID 87 T2 STP 87 Tl STP 87 T3 STP 91 T4 STP <br /> Sump Manufacturer Xerxes Xerxes Xerxes Xerxes <br /> Sump Depth (inches) 62" 61" 60" 62" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 46- 44* 43" 44* <br /> (inches) <br /> Test Start Time 10:58am 10:58am 10:15am 10:15am <br /> Initial Reading 2.4237" 6.5361" 5.0512" 2.1057* <br /> Test End Time 11:13am 11:13am 10:30am 10:30am <br /> Final Reading 2.4234" 6.5359" 5.0509" 2.1056" <br /> Change in Reading 0.0003" 0.0002" 0.0003" 0.0001" <br /> Pass/Fail Criteria 0.002" 0.002" 0.002" 0.002" <br /> Tightness Test Results Pas Fail 2]PassLjFaiI Z Pas Fail E]PassLjFaii <br /> rs <br /> ump/UDC ID 87 T2 Fill 87 TZ Fill 87 T3 Fill 91 T4 Fill <br /> ump Manufacturer Xerxes Xerxes Xerxes Xerxes <br /> ump Depth (inches) 61" 51* 1610 55" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 42- 31" 42" 35" <br /> (inches) <br /> Test Start Time 12:36pm 12:38pm 12:38pm 12:3Spin <br /> Initial Reading 1.1976* 3.25630 3.6725" 1.5695" <br /> Test End Time 12:53pm 12:53pm 12:53pm 12:53pm <br /> Final Reading 1.1975" 3.2563" 3.6726" 1.5704" <br /> Change in Reading 0.0001" o- 0.0001" 0.0009- <br /> Pass/Fail Criteria 0.002" 0.002" 0.002- 0.002* <br /> Tightness Test Results IZPassLjFail L,/ Pass Fail ZPass Fail v( Pass Fail <br /> Additional copies of this page may be attached. <br /> All tests marked"Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />