My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2021
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
V
>
VICTOR
>
880
>
2300 - Underground Storage Tank Program
>
PR0231746
>
COMPLIANCE INFO_2021
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/9/2021 8:50:52 AM
Creation date
3/25/2021 8:52:28 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2021
RECORD_ID
PR0231746
PE
2361
FACILITY_ID
FA0003862
FACILITY_NAME
Marks Fuel & Food, Inc.
STREET_NUMBER
880
Direction
E
STREET_NAME
VICTOR
STREET_TYPE
RD
City
LODI
Zip
95240
APN
049-050-32
CURRENT_STATUS
01
SITE_LOCATION
880 E VICTOR RD
P_LOCATION
02
P_DISTRICT
004
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
53
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Marks Fuel& Food, Inc. T880 E VICTOR RD, LODI September 28, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 306 HSC 25291(e) Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the diesel turbine pump sump. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: This violation was corrected on site. The operator removed approximately 45 gallons of <br /> liquid from the diesel turbine pump sump and placed the liquid into a 55 gallon drum labeled as hazardous waste. <br /> Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This is a repeat violation, Class II. <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The diesel turbine pump sump sensor failed to activate an audible and visual alarm while fully <br /> submerged in liquid. Per technician, David Winkler,the diesel turbine pump sump was filled with approximately 50 <br /> gallons of liquid upon removing the sump lid. David stated that the sensor was fully submerged but the panel was <br /> not in alarm. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION:After removing all liquid from the diesel turbine pump sump,the sensor was tested and <br /> passed. Per service technician David Winkler, he tapped the sensor multiple times before testing the sensor to <br /> trigger an audible and visual alarm. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by October 28, 2021 . <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($152). To schedule an appointment, please call (209)468-3420. <br /> Documents provided during inspection: inspection report, return to compliance certification, corrective action <br /> statement, and list of free CUPA classes. <br /> FA0003862 PR0231746 SCO01 09/28/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 6 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.