Laserfiche WebLink
ISD Vapor Flow Meter Installation Product Marking Information <br /> UL/cUL Control Drawing <br /> Equipment Document No. <br /> Associated Apparatus <br /> TLS-450/8600 331940-008 <br /> TLS-350,TLS-350R 331940-011 <br /> Intrinsically Safe Apparatus for Wireless Applications <br /> Tank Gauge Accessories 331940-012 <br /> The control drawings contain information related to the correct installation of the overall intrinsically Safe System. <br /> This includes information such as maximum number of apparatus,specific apparatus allowed in the system, <br /> maximum cable lengths, references to codes, proper grounding and so on. Control drawings can be found on the <br /> accompanying Compact Disk (TECH DOCS CD) or on the internet at veeder.com under SUPPORT;VR <br /> TECHNICAL DOCUMENTS; DRAWINGS. <br /> CLASS I Division 1,Group D I Non-Hazardous Location <br /> CLASS 1,Zone 0 Associated Apparatus <br /> Hazardous Location 8482rTLS-350R ATG Console <br /> Intrinsically Safe Apparatus <br /> Vapor White o <br /> (+) I <br /> 0 <br /> Flow Black - p <br /> Meter <br /> I.S.Sensor (+) <br /> Connections (-) <br /> Weatherproof I S <br /> Junction Box <br /> Intrinsically Safe <br /> Wiring I.S. <br /> R <br /> Rigid Conduit� I <br /> \Seal-Off I.S. <br /> Non-Hazardous Location •8 <br /> Associated Apparatus • <br /> El <br /> 8600fTLS-450 ATG Console e 0 I.S.Sensor <br /> Connections <br /> GENERAL PRODUCT WIRING DIAGRAM <br /> Product Label Contents <br /> Ir�VEEDER-ROOT I.S.CIRCUIT FOR HAZLOC SENSOR <br /> TM <br /> F/N 332374-XXX <br /> CL I, DIV. 1, GRD <br /> CL I, ZONE 0 S/N XXXXXX <br /> AEx is IIA 40°C<Ta < +60°C 24G6 <br /> Ex ia TC=T4A MANUAL NO.577013-916 C UL US <br /> SECURITE INTRINSEQUE LISTED <br /> 2 <br />