Laserfiche WebLink
Environmental Health Department <br />AMENDED <br />6/11/2021 <br />Underground Storage Tank Program Inspection Report <br />Date: <br />April 27, 2021 <br />Facility Address: <br />121 S CENTER ST, STOCKTON <br />Facility Name: <br />7-ELEVEN #38153 <br />UST System Observations <br />336 □ V □ R □ COS <br />Failure to affix a tag/sticker on each monitoring equipment certified, repaired, or replacedCCR 2638(f), 2641(i) <br />Single-Walled Non-Pressurized Piping <br />401 □ V □ R □ COS <br />Safe suction piping not properly sloped or check valve incorrectly locatedCCR 2636(a)(3), <br />2641(b) <br />402 □ V □ R □ COS <br />Failure to conduct monitoring and maintain records for single-walled conventional suction (pre-1984)CCR 2643(d) <br />403 □ V □ R □ COS <br />Failure to conduct 0.1 gph integrity test for single-walled conventional suction systems (pre-1984)CCR 2643(d), 2661(f) <br />404 □ V □ R □ COS <br />Failure to conduct 0.1 gph test on single-walled gravity piping biennially or post repair (pre-1984)CCR 2643(e), 2661(f) <br />Other Violations <br />2010 □ V □ R □ COS <br />Unlisted General violation See below <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br />102 CCR 2711 Failure to submit a complete and accurate application for a permit to operate a UST. <br />OBSERVATION: UST Tank Information forms are not current in the California Environmental Reporting System <br />(CERS). Facility indicated the use of fiberglass riser piping for (87, 91, and Diesel) tanks. Steel risers were observed <br />for the (87, 91, and Diesel) tanks, and confirmed by the service technician. <br />REGULATION GUIDANCE: Any change of information must be updated in CERS within 30 days of the changes. <br />CORRECTIVE ACTION: Immediately log into CERS, update the required information, and submit for review by the <br />EHD. <br />This is a minor violation. <br />115 CCR 2638(c), 2638(d) Failure to submit "Monitoring System Certification Form" within 30 days of completion of the <br />test. <br />OBSERVATION: Annual monitoring system certification, leak detector testing, and spill container testing was <br />performed on 4/23/2020 and a test report was submitted on 6/30/2020, 1 months late. <br />REGULATION GUIDANCE: A copy of the test report must be submitted within 30 days of the tests. <br />CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are performed <br />in a timely manner. <br />This is a repeat violation, Class II. <br />FA0024656 PR0543446 SC001 04/27/2021 <br />EHD 23-01 Rev. 9/16/2020 Underground Storage Tank Program OIRPage 4 of 7 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD