Laserfiche WebLink
<br /> <br /> <br /> made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 2 of 5 <br />Test Method Developed by Manufacturer Industry Standard Professional Engineer <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used: Vacuum Pump/Vacuum Gauges in Hg. <br />Tank ID Regular 87 Super 91 <br />Tank Manufacturer Trusco Trusco <br />Tank Capacity 20K 10K <br />Test Start Time 11:30 11:50 <br />Initial Reading -10" Hg. -10" Hg. <br />Test End Time 1:30 12:50 <br />Final Reading -10" Hg. -10" Hg. <br />Change in Reading 0 0 <br />Pass/Fail Criteria No Loss No Loss <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Test Method Developed by Manufacturer Industry Standard Professional Engineer <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used: Pressure Gauges in Psi/Nitrogen <br />Pipe Run ID 1-87 2-91 <br />Pipe Manufacturer Smith Smith <br />Test Start Time 11:50 11:55 <br />Initial Reading 5 Psi 5 Psi <br />Test End Time 12:50 12:55 <br />Final Reading 5 Psi 5 Psi <br />Change in Reading 0 0 <br />Pass/Fail Criteria No Loss No Loss <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Pipe Run ID <br />Pipe Manufacturer <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Additional copies of this page may be attached. <br />6. TANK SECONDARY CONTAINMENT TEST <br />7. PIPE SECONDARY CONTAINMENT TEST