Seresco Dehumidifier Submittal <br />2.17 AIR-COOLED AIR CONDITIONING <br />E. Unit shall be equipped with air conditioning mode where excess compressor heat is rejected to <br />an outdoor air-cooled condenser. The outdoor air-cooled condenser shall be capable of <br />rejecting 100% of the compressor beat rejection with an air on temperature at summer design <br />conditions. <br />F. Unit shall be provided with' a dry contact rated for 24VAC15A to operate the remote outdoor <br />condenser control. <br />G. Refrigeration circuit shall include solenoid refrigerant valves, receiver with pressure relief valve <br />set at 400 psig, pressure control valve and pressure differential valve, and two manual shutoff <br />valves to isolate the outdoor condenser. <br />PART 3 - EXECUTION <br />3.1 UNIT SELECTION <br />A. Unit shall be a Seresco NE Series. Model NE -004 -NV <br />3.2 PRODUCT DELIVERY, STORAGE AND HANDLING <br />A. Handle unit carefully to prevent damage, breaking, denting and scoring. Damaged units or <br />damaged components shall not be installed. Replace all damaged parts with new parts from the <br />manufacturer. <br />B. If unit is to be stored prior to installation store in a clean, dry place. Protect from weather, dirt, <br />fumes, water, construction, 4ud physical damage. <br />C. Comply with manufacturers rigging and installation instructions for unloading the unit and <br />moving it to the final location. <br />3.3 START UP <br />A. The agency responsible for start up should work in accordance with the specifications and in <br />accordance with the Seresco's instructions and only by workmen experienced in this type of <br />work. <br />INSTALLATION <br />B. Execute the work in accordance with the specifications and in accordance with the Seresco's <br />instructions and only by workmen experienced in this type of work <br />END OF SECTION <br />5 <br />