PLASTEEL° UNDERGROUND TANK <br /> APPENDIX B <br /> INTERSTITIAL VACUUM TEST (IVT) <br /> 1.0 Introduction: This test method has been developed by down on the ELUTRONO jacketed tank may require <br /> PLASTEEL INC.to meet the E.P.A.Alternate(Non-Volumetric)Tank Tightness reiteration due to the slow nature of air movement in the <br /> test procedures. The IVT has been verified by a third party to be capable of interstitial space. <br /> detecting a 0.1 gal/hr leak rate with a probability of detection of 100%when all 5.4 To ensure a vacuum has been established,the gauge must <br /> of the testing criteria are met. The false alarm rate for a tight tank is less than read 10"hg.for three(3)hours without any decrease on <br /> 5%.It is impossible to maintain a steady vacuum if a leak is present.This test is the gauge before proceeding with 5.6. Contact the <br /> not necessary to attain the PLASTEEL®tank warranty.This test is offered as a factory if the vacuum cannot be established per this <br /> stand alone leak tightness test method. <br /> paragraph. <br /> 2.0 Application: The IVT is applicable to the PLASTEEL® 5.5 Complete sections II and III of the Certificate of <br /> ELUTRON® (jacketed) Double-wall tank and the PLASTEEL® Composit Tightness Test. <br /> Double-wall tank. For compartmented tanks, consult the factory for the test 5.6 Refer to the Test Time Table (Figure 6.0) to determine <br /> time. <br /> the correct minimum time period for a valid test. <br /> 3.0 Authority: The Jurisdiction Having Authority(JHA)will determine Begin timing the test after completing 5.4. Record the <br /> whether the double-wall UST must be subject to a leak tightness test before nominal tank capacity, primary tank product and <br /> placing the UST in service. required test hours in Part IV of the Certificate. <br /> 4.0 Pre-Delivery Procedure: 5.7 After the required test time has passed, observe the <br /> gauge reading and record the reading, date and time of <br /> 4.1 Read and understand the PLASTEEL® Tank Installation day in Part IV of the Certificate. <br /> instructions and Appendix B before attempting the interstitial 5.8 Test Conclusions:The tank has passed the leak tightness <br /> vacuum test. Contact the PLASTEEL®tank manufacturer if you p g <br /> have any questions. test when the final gauge reading has not decreased from <br /> the initial gauge reading of 10"Hg.If other observations <br /> 4.2 Consult the PLASTEEL® tank manufacturer before the tank is are made,consult the tank manufacturer. <br /> shipped to ensure that the tank is delivered with the test gauge <br /> assembly. This assembly is an optional piece of equipment Test Time Tables: The table in Figure 6.0 lists the <br /> supplied by the tank manufacturer. minimum test period(in hours) to perform a valid IVT with a <br /> 4.3 Prior to shipment from the factory, you may request that the dr (air only) primary tank. The IVT test may be performed <br /> manufacturer deliver the tank with the vacuum established. with gasoline,diesel or water in the primary tank. Consult the <br /> PLASTEEL® tank manufacturer for the specific test time for <br /> 4.4 Upon delivery, the delivery document will indicate the correct these situations. <br /> vacuum gauge reading. Call the factory if the gauge reading does <br /> meet the gauge reading specified on the delivery document. <br /> TEST TIME TABLE:DRY PRIMARY TANK <br /> 4.5 To maintain the vacuum during the unloading and installation <br /> phases, extreme care must be taken to ensure the IVT gauge CAPACITY JACKETED COMPOSIT <br /> assembly is not jarred, struck or moved in any manner. Call the (GALS.) (HOURS) (HOURS) <br /> factory for instructions if the vacuum has decreased. 500 4.0 4.5 <br /> 5.0 Test Procedures: 1,000 4.0 5.5 <br /> QUICK 5.1 If the vacuum was established at 2,000 4.0 8.0 <br /> DISCONNECT BUTTERFLY deliveryand has not decreased <br /> (Optional) VALVE 3,000 4.0 9.0 <br /> 1 during the unloading and <br /> installation phases, you may 4,000 4.0 9.5 <br /> by-pass 5.2 and 5.3 5,000 4.0 10.5 <br /> 5.2 Install the vacuum gauge test 6,000 4.0 11.0 <br /> .� assembly (see Fig. 5.0) in the 8,000 4.0 13.0 <br /> monitor access NPT coupling on <br /> r the tank top centerline. Ensure 10,000 4.0 14.5 <br /> .o <br /> INTERSTITIAL that any additional monitor 12,000 4.0 15.5 <br /> MONITOR access couplings are properly <br /> 15,000 4.0 17.5 <br /> _ FITTING sealed with threaded plugs. <br /> 20,000 4.0 20.5 <br /> 5.3 Connect the vacuum pump to <br /> the test gauge assembly and 30,000 4.0 37.5 <br /> FIGURE 5.0: VACUUM GAUGE draw down to 10" hg. Record 40,000 4.0 45.5 <br /> TEST ASSEMBLY(TYPICAL). initial gauge reading, date, and <br /> ACCURACY:ASME(ANSI)GRADE B, 50000 4.0 53.0 <br /> 2%, 0-30"Hg,with 1"Hg GRADUATIONS. time of day in Part IV of the , <br /> Certificate. The initial pump FIGURE 6.0 <br /> YOUR Licensed PLASTEEL®tank manufacturer is: <br /> APP.B,1106 <br />