A. GENERAL NOTES 3. HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE OR MASONRY. HANGING FROM METAL
<br /> 1. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY DECK IS NOT PERMITTED. HANGERS MUST BE ATTACHED TO UPPER CHORDS OF BAR JOISTS. WHERE
<br /> CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS, APPLY TO ALL SECTIONS OF DIVISION 15000. INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT (DUCTWORK OR PIPING)THE CONTRACTOR SHALL
<br /> 2. THE CONTRACTOR FOR THIS DIVISION OF WORK IS REQUIRED TO READ THE SPECIFICATIONS AND INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT
<br /> REVIEW THE DRAWINGS FOR ALL DIVISIONS OF WORK PRIOR TO BEGINNING WORK AND IS RESPONSIBLE INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, AND OTHER EQUIPMENT.
<br /> FOR THE COORDINATION OF HIS/HER WORK AND THE WORK OF HIS/HER SUBCONTRACTORS WITH ALL 4. HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE OUTER DIAMETER OF
<br /> DIVISIONS OF WORK TO AVOID INTERFERENCE AND CONFLICTS. IT IS THIS CONTRACTOR'S INSULATION. INSTALL 6" LONG SPLIT CIRCLE GALVANIZED SADDLE BETWEEN THE HANGER AND THE
<br /> RESPONSIBILITY TO PROVIDE HIS/HER SUBCONTRACTORS WITH COMPLETE SETS OF BID DOCUMENTS. PIPE INSULATION. PROVIDE HIGH DENSITY INSULATION INSERT BETWEEN THE SADDLE AND THE PIPE.
<br /> 3. THIS CONTRACTOR IS RESPONSIBLE FOR SCHEDULING THE COMPLETION AND INSPECTION OF HIS/HER 5. HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI-ELECTRICALLY SEPARATED.
<br /> WORK AND THE WORK OF HIS/HER SUBCONTRACTORS TO COMPLY WITH THE SCHEDULE. ivy
<br /> 4. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTAL OF BID TO DETERMINE CONDITIONS
<br /> U) AFFECTING THE WORK. ANY ITEMS WHICH ARE NOT COVERED IN THE BID DOCUMENTS OR ANY I. DIRT AND DUST CONTROL
<br /> PROPOSED SUBSTITUTIONS SHALL BE LISTED SEPARATELY AND QUALIFIED IN THE CONTRACTORS BID. 1. SCREEN OFF ALL AREAS WHERE CONSTRUCTION IS TO TAKE PLACE FROM THE AREAS TO REMAIN
<br /> Ln SUBMITTAL OF A BID SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY INHABITED. INHABITED AREAS SHALL REMAIN DUST AND DEBRIS FREE DURING CONSTRUCTION.
<br /> MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS 2. CLEAN ANY AREAS OUTSIDE DESIGNATED CONSTRUCTION AREA WHICH MAY HAVE BECOME SOILED DUE
<br /> U_ SHALL BE INCLUDED. FAILURE TO VISIT THE SITE DOES NOT RELIEVE THE CONTRACTOR OF HIS/HER TO CONSTRUCTION.
<br /> o RESPONSIBILITY IN PERFORMANCE OF WORK
<br /> J. EQUIPMENT, PIPING AND INSTALLATION
<br /> B. GENERAL REQUIREMENTS: 1. REFER TO PLANS FOR SCHEDULES OF EQUIPMENT AND FIXTURES. AMERICAN STANDARD, KOHLER AND
<br /> 1. THIS CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SERVICES, TOOLS, CRANE ARE CONSIDERED ACCEPTABLE AS EQUALS.
<br /> o TRANSPORTATION, AND FACILITIES NECESSARY TO PROVIDE A COMPLETE HVAC, PLUMBING, FIRE 2. MAINTAIN A MINIMUM CLEARANCE OF 6" BETWEEN PLUMBING PIPING AND EQUIPMENT AND ALL
<br /> co PROTECTION SYSTEM AS SHOWN ON THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS AND AS FIRE/SMOKE RATED WALLS.
<br /> REQUIRED BY JOB CONDITIONS. ALL WORK NECESSARY AND NOT SPECIFICALLY NOTED TO BE 3. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. INSTALL UNITS
<br /> a) PROVIDED BY OTHERS SHALL BE PROVIDED BY THIS CONTRACTOR. LEVEL AND PLUMB, FIRMLY ANCHORED IN LOCATIONS INDICATED.
<br /> _
<br /> 0 2. ALL WORK SHALL BE PERFORMED IN A NEAT, PROFESSIONAL MANNER USING GOOD CONSTRUCTION 4. POTABLE WATER PIPING SHALL BE AS FOLLOWS:
<br /> PRACTICES. a. BELOW GRADE: TYPE 'K', ANNEALED TYPE TEMPERED COPPER TUBE FOR PIPE SIZES 2 INCHES AND
<br /> 3. UNLESS SPECIFICALLY NOTED OTHERWISE, MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING ALL SMALLER. BRAZE ALL JOINTS.
<br /> COMPONENTS THEREOF, SHALL BE NEW, TESTED, LISTED AND SIZED IN CONFORMITY WITH b. ALL OTHER: TYPE 'L' DRAWN COPPER TUBE WITH WROUGHT COPPER FITTINGS AND 95-5
<br /> REQUIREMENTS OF STATE AND LOCAL CODES, WHICHEVER IS MORE STRINGENT. TIN-ANTIMONY SOLDER.
<br /> 4. ALL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICING, 5. PIPING OF DISSIMILAR METALS SHALL BE DI-ELECTRICALLY SEPARATED.
<br /> °' GNICH
<br /> MAINTAINING AND REPAIRING. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT 6. FIELD VERIFY EXACT CONNECTION POINTS PRIOR TO SUBMITTING BID AND NOTIFY ENGINEER IF
<br /> SERVICE ACCESS TO ALL EQUIPMENT. CONDITIONS ARE NOT AS SHOWN ON THE PLANS ORAS STATED IN THE SPECIFICATIONS. CONTRACTOR
<br /> ARCHITECTURE
<br /> 5. FIELD MEASURE AND VERIFY REQUIREMENTS FOR EXACT DIMENSION'S. OFFSETS AND ADDITIONAL SHALL VERIFY THE OPERABILITY OF ENTIRE SYSTEM PRIOR TO TIE-IN AS FOLLOWS: I I D I 0
<br /> 0 ELBOWS REQUIRED TO SUIT SITE CONDITIONS ARE CONSIDERED PART OF THE SCOPE. c. SNAKE SANITARY FOR A DISTANCE OF 100 FEET AND REPORT ANY BLOCKAGE. v
<br /> d. TEST WATER PRESSURE TO INSURE MINIMUM PSI MATCHES MOST DEMANDING EQUIPMENT AN OREGON LIMITED LIABILITY COMPANY
<br /> C. CODES SUPPLIED.
<br /> Q 1. ALL WORK SHALL COMPLY WITH 2019 CALIFORNIA PLUMBING CODE ORDINANCES AND OTHER STATE, 7. INSULATE ALL HOT AND COLD WATER PIPING WITH 1" THICK (K=0.23 @ 75°F) FIBERGLASS PIPE
<br /> COUNTY, CITY AND LOCAL CODES AND ORDINANCES, SAFETY AND HEALTH CODES, NFPA CODES, INSULATION WITH AN ALL SERVICE JACKET TO MEET LOCAL CODES AND UL FLAME SPREAD AND SMOKE
<br /> ENERGY CODES AND ALL OTHER APPLICABLE CODES AND REQUIREMENTS. THIS CONTRACTOR SHALL DEVELOPED RATING. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
<br /> INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS. THIS 8. INSULATE THE TRAP, SANITARY AND SUPPLY PIPES UNDER LAVATORIES WITH TRUEBRO MODEL 102W
<br /> a CONTRACTOR SHALL INCLUDE IN THE BID ANY CHANGES REQUIRED BY CODES AND IF THESE CHANGES "HANDI LAV GUARD" INSULATION KIT OR EQUAL. 1001 SE SANDY BLVD, SUITE 100
<br /> ARE NOT INCLUDED IN THE BID, THEY MUST BE QUALIFIED AS A SEPARATE LINE ITEM IN THE BID. AFTER 9. INSTALL ALL NECESSARY PIPE HANGERS, SADDLES, AND CARRIERS TO PROPERLY SUPPORT ALL PIPING PORTLAND, OR 97214
<br /> Q CONTRACT IS ISSUED, NO ADDITIONAL COST DUE TO CODE ISSUES SHALL BE REIMBURSED TO THE AND FIXTURES. HANGERS SHALL SUIT TYPE OF PIPING PROVIDED AND BE SPACED AT A MAXIMUM SPAN V. 503.552.9079
<br /> 12 CONTRACTOR. OF 5 FEET. F. 503.241.7055
<br /> In 10.FLUSH STERILIZE WATER SYSTEM IN ACCORDANCE WITH LOCAL CODES. WWW.GNICHARCH.COM
<br /> D. LICENSES, PERMITS AND INSPECTION FEES 11.TEST ENTIRE PLUMBING SYSTEM IN ACCORDANCE WITH 2019 CALIFORNIA PLUMBING CODE.
<br /> 1. THIS CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, INSPECTIONS AND FEES 12.PROVIDE WATER METER AND REMOTE READER PER LOCAL UTILITIES REQUIREMENT, IF APPLICABLE. 01.13.21
<br /> REQUIRED OR RELATED TO DIVISION 15000 WORK. 13.CONDENSATE DRAIN: PROVIDE POLYVINYL CHLORINE (PVC) SCHEDULE 40 PLASTIC PIPE (TYPE (DWV) IN
<br /> 2. FURNISH TO THE (OWNER)ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL AT CONFORMANCE WITH STANDARD ASTM D2665.
<br /> Q COMPLETION OF PROJECT. 14.VALVES: PROVIDE BALL VALVE NIBCO SERIES 585-70 FOR SHUT-OFF
<br /> a 15.PROVIDE ACCESS PANELS WHERE REQUIRED FOR OPERATION, MAINTENANCE AND BALANCING OR �R��E55lply,
<br /> o E. GUARANTEE PLUMBING EQUIPMENT. �p ���Ray cfiy
<br /> 1. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORK PROVIDED UNDER HIS/HER 16.PROVIDE WATER HAMMER ARRESTORS AT EACH BRANCH LINE. w '�
<br /> a, CONTRACT AND SHALL MAKE GOOD, REPAIR OR REPLACE AT HIS/HER OWN EXPENSE, ANY DEFECTIVE ��
<br /> o WORK, MATERIAL OR EQUIPMENT DISCOVERED WITHIN A PERIOD OF 12 MONTHS FROM THE DATE OF H. GAS PIPING 2�
<br /> ACCEPTANCE (IN WRITING) OF THE INSTALLATION. EXTENDED WARRANTIES ARE AS SPECIFIED WITH 1. FURNISH AND INSTALL A COMPLETE GAS PIPING SYSTEM. FSPR'
<br /> o INDIVIDUAL EQUIPMENT. 2. GAS LINES SHALL BE BLACK STEEL, SCHEDULE 40, ASTM A-53, WITH MALLEABLE THREADED FITTINGS CHCli A�1G '`
<br /> 2. THE HOT WATER HEATERS SHALL BE FURNISHED WITH A 5 YEAR HEAT EXCHANGER WARRANTY. FOR 2"AND SMALLER, AND WITH WELDED JOINTS FOR 2-1/2"AND LARGER. �9T�rOF CA4140
<br /> 3. FURNISH AND INSTALL A GAS COCK, DIRT LEG, AND UNION CONNECTION AT EACH PIECE OF EQUIPMENT.
<br /> .E F. PHASING REQUIREMENTS (IF APPLICABLE) 4. PITCH PIPING AT A UNIFORM GRADE OF 1/4" IN 15 FEET UPWARD IN DIRECTION OF FLOW. SUPPORT
<br /> 1. THIS CONTRACTOR SHALL INCLUDE IN THE BID ALL NECESSARY SERVICE REQUIRED TO KEEP THE PIPING EVERY 5 FEET, AS DETAILED ON DRAWINGS, OR BY STANDARD INDUSTRY PRACTICE, WHICHEVER
<br /> OPERATING PORTION OF THE BUILDING'S (HVAC, PLUMBING AND SPRINKLER) SERVICES IN OPERATION. IS MORE STRINGENT.
<br /> CONTRACTOR MUST SCHEDULE IN WRITING ONE WEEK PRIOR TO ANY SHUT DOWN OF (THE HVAC, 5. GAS PIPING EXPOSED ON ROOF SHALL BE PAINTED WITH RUST-INHIBITING PAINT.
<br /> PLUMBING OR FIRE PROTECTION) SYSTEMS 6. GAS PIPING INSTALLED IN RETURN AIR PLENUMS SHALL BE SLEEVED AND VENTED OR WELDED IN
<br /> 2. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE DEMOLITION OF EXISTING ACCORDANCE WITH THE LOCAL GAS COMPANY, LOCAL CODE AND APPLICABLE NFPA 54 CODES.
<br /> WORK AND THE RENOVATION WORK. COORDINATE WITH THE OTHER CONTRACTORS ANY EXISTING 7. TESTING AND PURGING OF GAS PIPING SHALL BE DONE PER THE REQUIREMENTS OF THE LOCAL GAS
<br /> EQUIPMENT REQUIRED TO BE LEFT INTACT. THIS CONTRACTOR SHALL INCLUDE AND WILL BE HELD COMPANY, LOCAL CODES AND APPLICABLE NFPA CODES.
<br /> RESPONSIBLE FOR, THE REMOVAL OF ALL EXISTING (FIRE PROTECTION SYSTEMS, PLUMBING FIXTURES, 8. CONTACT AND COORDINATE GAS SERVICE, METER AND REGULATOR REQUIREMENTS WITH THE LOCAL
<br /> PIPING SYSTEMS, HVAC UNITS, REFRIGERANT RECAPTURE, EXHAUST FANS). AND ASSOCIATED ROOF GAS COMPANY PRIOR TO BID. INCLUDE INSTALLATION COST OF GAS METER AND REGULATOR IN BID. Q
<br /> CURBS OR RAILS NOT TO BE REUSED ON THIS PROJECT, UNLESS SPECIFICALLY NOTED OTHERWISE.
<br /> L CONTRACTOR SHALL VERIFY ALL PRESUMED ABANDONED (EQUIPMENT, PIPES, DUCTWORK AND I. LABELS/PIPE MARKERS 0
<br /> EQUIPMENT) PRIOR TO REMOVAL. ROOF CURBS SHALL BE REMOVED AND THE ROOF PATCHED. ALL 1. FURNISH AND INSTALL PIPE IDENTIFICATION MARKERS EVERY 5 FEET ON ALL PIPES INSTALLED UNDER C)
<br /> EXTRANEOUS ITEMS IN THE SPACE, ASSOCIATED WITH THE SPACE, OR ON THE ROOF NOT APPLICABLE THIS CONTRACT. MARKERS SHALL BE A MINIMUM OF 1-1/2" X 8" AND IDENTIFIED IN ACCORDANCE WITH N
<br /> FD
<br /> .? TO THE NEW WORK MUST BE REMOVED AND ROOF/WALL/FLOOR PATCHED/REPAIRED TO MATCH THE BACKGROUND AND LETTER COLORS ISSUED BY THE AMERICAN NATIONAL STANDARDS INSTITUTE 0 Q
<br /> EXISTING SURROUNDINGS. EXISTING ABANDONED (PIPES, DUCTS OR EQUIPMENT) IN THE FLOOR, (ANSI). MARKERS SHALL BE MANUFACTURED BY CHAMPION AMERICA INC., BRADY, SETON, OR EQUAL. C-0
<br /> o EMBEDDED IN CONCRETE, OR OTHERWISE INACCESSIBLE ARE TO BE CUT OFF AND SEALED BELOW OR 2. PIPING SHALL BE IDENTIFIED AS FOLLOWS: CONDENSATE, REFRIGERANT LIQUID, REFRIGERANT
<br /> WITHIN THE FLOOR OR WALL WHEN THEY ARE NOT TO BE REUSED IN THIS PROJECT. IF REQUIRED BY SUCTION, AND DIRECTIONAL ARROWS. ALL IDENTIFICATIONS MUST BE VISIBLE AT EQUIPMENT.
<br /> CODES, ABANDONED (PIPING AND/OR DUCTWORK) MUST BE REMOVED TO POINT OF ORIGIN. CONFIRM 3. VALVES SHALL BE TAGGED IN ACCORDANCE TO VALVE OPERATION SCHEMATIC.
<br /> THE EXTENT OF DEMOLITION PRIOR TO BID AND INCLUDE IN BID PROPOSAL. 4. LABEL ALL FILTERED SUPPLY STOPS. O
<br /> Q
<br /> G. SLEEVE J. STEEL FRAMING FOR SUPPORT (00 -+--
<br /> 1
<br /> 15 1. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE 1. PROVIDE ALL NECESSARY STEEL FRAMING REQUIRED TO INSTALL ALL HVAC EQUIPMENT AS DESCRIBED O v>
<br /> INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH ITS RESPECTIVE FLOOR, WALL OR PARTITION OR IMPLIED ON THE DRAWINGS. ALL PENETRATIONS OF EXISTING STRUCTURE SHALL BE DONE AT THIS 0
<br /> AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH CONTRACTOR'S EXPENSE Q)
<br /> SHALL EXTEND 2"ABOVE THE FLOOR. Ll_
<br /> 2. CONTRACTOR SHALL COORDINATE ANY CORE DRILLING OR CUTTING OF OPENINGS IN MASONRY K. SYSTEM START-UP
<br /> o FLOORS OR WALLS. 1. THIS CONTRACTOR SHALL INCLUDE AS A BASE, 2-HOURS OF START-UP TIME PLUS AN ADDITIONAL r , 0
<br /> m 3. ALL SLEEVES AND OPENINGS THROUGH FIRE-RATED WALLS AND/OR FLOORS SHALL BE FIRE SEALED 2-HOURS OF START-UP TIME PER HVAC UNIT SHOWN ON DRAWINGS.
<br /> o WITH CALCIUM SILICATE, SILICONE "RTV" FOAM, "31M" FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN
<br /> THEIR FIRE RATING.SLEEVES IN BEARING AND MASONRY WALLS, FLOORS, AND PARTITIONS SHALL BE
<br /> O
<br /> US STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY L. FINAL INSPECTIONS 0 0 Qj N
<br /> -° PARTITIONS, THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL PIPING, SLEEVES SHALL 1. ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE, THE ENGINEER SHALL BE NOTIFIED (IN 0
<br /> BE NO. 22 U.S.G. GALVANIZED STEEL MINIMUM. WRITING) TO INSPECT THE FINISHED INSTALLATION UPON COMPLETION FOR COMPLIANCE WITH THE z O U
<br /> o PLANS, SPECIFICATIONS AND CODES. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE TO BRING �- rO U O
<br /> H. HANGERS ALL ITEMS REPORTED BY THE ENGINEER INTO COMPLIANCE U
<br /> 1. PROVIDE HANGERS AND SUPPORTS FOR ALL PIPING, DUCTWORK, AND EQUIPMENT IN ACCORDANCE ( LO "-
<br /> WITH SMACNA, MSS, ASME, AND ASHRAE STANDARDS. t.J 0 O` m
<br /> 2. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C-CLAMPS WITH m O Q O
<br /> RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK. . � p U "'t CL
<br /> 0
<br /> O - O 00 "' C:
<br /> CN Q
<br /> cu
<br /> .O
<br /> a ISSUED FOR PERMIT:
<br /> � a
<br /> 01 . 13.2021
<br /> E �
<br /> a �
<br /> � (D
<br /> O O-
<br /> cu
<br /> E � EV: DATE: DESCRIPTION:
<br /> CU
<br /> _
<br /> � U
<br /> _ d
<br /> C �
<br /> N �
<br /> C
<br /> O �
<br /> C O
<br /> C
<br /> Cm O
<br /> N �
<br /> N
<br /> SHEET NAME:
<br /> 0
<br /> PLUMBING
<br /> 0
<br /> SPECIFICATIONS
<br /> co
<br /> m SHEET NUMBER:
<br /> CAtSE
<br /> Engineerin Inc.g P6 . 0
<br /> kj
<br /> 796 Merus Court I T 636.349.1600
<br /> St.Louis,MO 63026 F 636.349.1730
<br /> 02020 DB Franchising USA,LLC
<br />
|