Laserfiche WebLink
they are Xerxes tank charts and the plans state that Containment Solutions tanks will be <br />installed. <br />5) The section on vacuum zones on M.5.3.09 lists vapor recovery under 87 Zone 1 only. Please <br />include documentation for 91 vapor recovery piping. 91 on this page only shows vacuum zones <br />for product (zone S), vent (zone 6) and crossover (zone 7). <br />6) Provide line length information for verifying line leak detector compatibility. I don't see the line <br />length information on G.0.2.0. <br />7) Provide a drawing indicating the locations of all water wells, septic systems, and storm drains. 1 <br />see that existing storm drains were noted on page G.0.2.0 but any water wells and septic <br />systems were not noted. <br />8) Provide completed UPCF Underground Storage Tanks — Facility form (A) and UPCF Underground <br />Storage Tanks (B) — Tank (one form per tank). <br />All the Best, <br />Carol Presto <br />Environmental Health Specialist Trainee <br />San Joaquin County Environmental Health Department <br />Email: cpresto@sigov.org <br />Phone: (209) 616-3061 <br />https://www.slgov.org/department/envhealth/ <br />In order to comply with the Regional Stay at Home order effective December 6, 2020, the Environmental Health Department's <br />public lobby will be limited to no more than two customers at a time. To decrease possible waiting time, please call (209) 468- <br />3420 to schedule an appointment. You may still use the Environmental Health website to contact this Department, pay fees or <br />download documents. <br />Tips to prevent the spread of COVID-19: <br />• Avoid close contact with people who are sick. <br />• Avoid touching your eyes, nose, and mouth with unwashed hands. <br />• Wash your hands often with soap and water for at least 20 seconds. Use an alcohol -based hand sanitizer that contains at least <br />60% alcohol if soap and water are not available. <br />Visit SJReady.org for current information regarding COVID-19 in San Joaquin County. <br />From: Presto, Carol [EHD] <br />Sent: Monday, February 22, 20215:06 PM <br />To: roberty@asengineer.com <br />Subject: FW: SR0081541- 2510 S. Hwy 99, Stockton - UST Install <br />Good Afternoon Robert, <br />I hope all is well. This new installation has been reassigned to me. I was reviewing the list below that <br />Stacy requested from you. I was unable to find a copy of the application in the emails she forwarded me <br />for this site. If you could please forward over the application and ELD testing work plan you've sent to <br />Stacy, it would be greatly appreciated. I've also attached a blank copy to this email for reference. I have <br />some added some comments below to her list based on a previous response from you from 6/12/2020. <br />1) Page 3 of the Application for the Underground Storage Tank Installation Permit: <br />Owner/operator information is outdated. <br />2) Complete manufacturer certifications were not submitted. Provide current contractor's training <br />certifications for installation and testing of all proposed UST equipment/components, including <br />tanks & sumps, flex connectors, piping, spill buckets, sump shields & lids, leak detectors, and <br />24 <br />