TANK AND PIPING INSTALLATION SCOPE OF WORK: <br />(1 1) METAL PIPE AND FITTINGS: <br />E -STOP <br />DISCONNECTS <br />THE HOT AND NEUTRAL WIRES TO THE DISPENSERS <br />ENSURE THAT THE <br />E -STOP <br />STANDARD: STEEL PIPE SHOWN ON <br />THESE DRAWINGS <br />TO BE <br />MINIMUM <br />SCHEDULE 40. METAL PRODUCT LINE <br />FITTINGS TO BE MALLEABLE IRON CLASS <br />150, GALVANIZED. ALL MALLEABLE <br />IRON FITTINGS SHALL <br />BE SUPPLIED <br />BY "ANVIL" (FORMERLY "GRINNELL") <br />OR EQUAL SPECIFICATIONS AS FOLLOWS: <br />TURBINE <br />DIMENSIONS <br />MATERIAL <br />GALVANIZING THREAD <br />PRESSURE RATING <br />M.I. FITTINGS <br />HAS ITS OWN <br />DEDICATED CIRCUIT <br />ENSURE THAT THE <br />DISPENSING <br />EQUIPMENT <br />IS GROUNDED PER NEC <br />(TEES, ELBOWS) <br />0 <br />0 <br />CLASS 150/PN 20 <br />ASME 816.3 <br />ASTM <br />A-197 <br />ASTM <br />A-153 ASME B.1 20.1 <br />ASME B16.3 <br />M.I. UNIONS <br />SEAL: <br />FESS /0 <br />Gf-�gp�l <br />NO. 36475 <br />* XP. 6-30-22 <br />CLASS 150/PN 20 <br />ASME 816.39 <br />ASTM <br />A-197 <br />ASTM <br />A-153 ASME B.1 20.1 <br />ASME B16.3 <br />STEEL PIPE NIPPLES <br /><z 00 o <br />Z <br />z LU <br />00 <br />cnrnco <br />CLASS 150/PN 20 <br />ASTM A733 <br />ASTM <br />A-53 <br />ASTM <br />A-153 ASME B.1 20.1 <br />ASME B16.3 <br />(F OR <br />E) <br />LLJ< <br />z Q -- <br />STEEL PIPE <br />z 3 t <br />� <br />Q <br />w 00 w <br />o <br />0 <br />z = <br />CLASS 150/PN 20 <br />N/A <br />ASTM <br />A-53 <br />ASTM <br />A-153 ASME B.1 20.1 <br />ASME B16.3 <br />SCHEDULE 40 <br />ADDRESS <br />(F OR <br />E) <br />DESIGNED BY: <br />GASOLINE/ALCOHOL COMPATIBLE THREAD SEALANT LIKE LOCTITE <br />567 <br />SHALL BE <br />USED ON ALL THREADED PIPE CONNECTIONS. <br />ANY METAL PIPE OR FITTING USED <br />FOR PRODUCT, VENT, OR <br />VAPOR <br />RECOVERY <br />WHICH CONTACTS SOIL OR <br />BACK FILL MUST BE 100% COVERED WITH <br />A 3M SCOTCHRAP PRIMER AND 3M <br />TEMFLEX 10 MIL. <br />OR 10 <br />MIL. SELF -PRIME <br />PROSELECT PIPE TAPE. <br />STANDARD: CONTRACTOR TO INSTALL SUMP PENETRATION FITTINGS. ALL PENETRATIONS OF THE SUMPS TO BE ON A LINE TOWARD THE CENTER OF <br />THE SUMP, NOT TO EXCEED MANUFACTURERS RECOMMENDED ANGLE IN ANY DIRECTION, TO ENSURE THE PROPER INSTALLATION OF ALL BULKHEAD <br />AND COMPRESSION FITTINGS AND RESULTANT WATER TIGHTNESS. ALL PIPING, CONDUIT AND GROUNDS THAT PENETRATE THE SUMP SIDE WALLS MUST <br />BE SEALED WITH DOUBLE SIDED BULKHEAD FITTINGS IN SUMPS. SUMPS SHALL BE HYDROSTATICALLY TESTED WITH STANDING WATER FOR A PERIOD <br />OF 24 HOURS OR CERTIFIED USING SUMP MANUFACTURERS APPROVED TESTING PROCEDURE TO INSURE THAT SUMPS ARE WATERTIGHT. THE OWNER'S <br />ENGINEER, THE BP PROJECT MANAGER MUST SIGN OFF ON THIS TESTING ON THE TANK INSTALLATION CHECK LIST. <br />MANUFACTURER ENTRY BOOT TYPE VARIANT: THE MAKE AND MODEL NUMBERS OF THE PIPING PENETRATION FITTINGS SHOWN IN THE DETAILS ARE <br />NOT SUBJECT TO CHANGE. N.O.V. FRP BONDED ENTRY FITTINGS ARE REQUIRED FOR ALL PIPING PENETRATIONS. CONDUIT PENETRATIONS INTO SUMPS <br />SHALL BE AS SPECIFIED ON THE PLANS. <br />CALIFORNIA VARIANT: CONTRACTOR TO INSTALL SUMP PENETRATION FITTINGS THAT MEET THE ADDITIONAL CRITERIA REQUIREMENT FOR CONTINUOUS <br />HYDROSTATIC AND VACUUM MONITORING. <br />(13) DISPENSER INSTALLATION: <br />STANDARD: CONTRACTOR TO INSTALL "WAYNE OVATION" STYLE DISPENSERS WITH INTEGRATED CARD READERS AND INTERCOM SYSTEM AS SHOWN ON <br />SITE SPECIFIC DESIGN DETAIL SHEETS. DISPENSERS TO BE INSTALLED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. INSTALLATION TO INCLUDE <br />DISPENSER ISLANDS, SINGLE WALL DISPENSER CONTAINMENT SUMPS, AND THE INSTALLATION OF ALL SHEAR VALVES, RISERS, PIPING CONNECTIONS <br />AND ALL PENETRATIONS INTO THE SUMPS. SEE TANK ELECTRICAL DRAWINGS FOR CONDUIT AND WIRING REQUIREMENTS. <br />DISPENSER START UP: - START UP BY MANUFACTURERS REPRESENTATIVE. CONTRACTOR TO PURGE LINES WITH 200 GALLONS PER HOSE MINIMUM. <br />ANY AIR POCKETS OR START UP PROBLEMS DUE TO IMPROPER INSTALLATION OR INCORRECT WIRING THAT DESTROYS ELECTRONICS WILL BE BILLED <br />BACK TO THE CONTRACTOR <br />NYC VARIANT: DISPENSER SUMPS SHALL BE BACK FILLED WITH PEA GRAVEL PER NYC CODE. DISPENSER ISLAND SHALL BE EQUIPPED WITH A FIRE <br />SUPPRESSION SYSTEM. SEE FIRE SUPPRESSION DETAILS FOR INSTALLATION REQUIREMENTS. <br />ARCO BRANDED VARIANT: DISPENSERS INSTALLED WITHOUT CARD READERS IN DISPENSERS. CONTRACTOR TO INSTALL TWO (2) DOUBLE SIDED <br />PAYMENT ISLAND CASHIERS (PIC UNITS) AS SHOWN ON SITE SPECIFIC PLANS. START UP BY MANUFACTURERS REPRESENTATIVE. START UP PROBLEMS <br />DUE TO IMPROPER INSTALLATION OR INCORRECT WIRING THAT DESTROYS ELECTRONICS WILL BE BILLED BACK TO THE CONTRACTOR. REFER TO <br />ARCHITECTURAL CANOPY DRAWINGS FOR ADDITIONAL SITE PREP AND CONDUIT REQUIREMENTS. <br />CALIFORNIA VARIANT: DISPENSER SUMPS TO BE DOUBLE WALL AND INSTALLED WITH CONTINUOUS HYDROSTATIC MONITORING DEVICE PER AB -2481 <br />REQUIREMENTS <br />INSTALLATION OF HANGING HARDWARE: <br />STANDARD: - CONTRACTOR TO INSTALL VAPOR ASSIST HOSES, NOZZLES, SWIVELS AND BREAK AWAY VALVES PER '96' CARB EXECUTIVE ORDER <br />G -70 -153 -AD. SITES WHERE ORVR COMPATIBLE SYSTEMS ARE NOT REQUIRED <br />ARCO BRAND VARIANT - CONTRACTOR TO INSTALL ORVR COMPATIBLE BALANCE HOSES, NOZZLES, SWIVELS AND BREAK AWAY VALVES PER CARB <br />EXECUTIVE ORDER G -70 -52 -AM PER LOCAL STATUES. <br />CALIFORNIA VARIANT - CONTRACTOR TO INSTALL ORVR/PHASE II EVR COMPATIBLE HOSES, NOZZLES, SWIVELS AND BREAK AWAY VALVES PER <br />APPLICABLE CARB EXECUTIVE ORDER WITH IN SYSTEM DIAGNOSTICS (ISD) PER LOCAL JURISDICTIONAL REQUIREMENTS. <br />NEW JERSEY VARIANT - CONTRACTOR TO INSTALL LOW PERMEATION HOSE AND COMPATIBLE HARDWARE. SEE SHEET G.0.6.15 <br />14) SUMP SENSOR INSTALLATION: <br />CONTRACTOR TO INSTALL ALL FILL SUMP TURBINE SUMP AND DISPENSER SUMP SENSORS PER VEEDER ROOT INSTALLATION INSTRUCTIONS. SUMP <br />SENSORS TO BE INSTALLED IN SUMP HOLDERS MOUNTED TO SIDE OF SUMP WALLS SEE TANK DETAIL SHEETS FOR LIQUID SENSOR DETAILS. <br />TURBINE SIDE SUMP SENSORS TO BE MOUNTED AT SIDE OF TANK WHERE PRODUCT PENETRATION INTO SUMP IS MADE AND BELOW LOWEST <br />PENETRATION FITTING WITHIN SUMP AREA AT BOTTOM OF SUMP. SEE TANK ELECTRICAL DRAWINGS FOR MONITORING CONDUIT DETAILS AND SENSOR <br />AND PROBE WIRING DETAILS. <br />(15) OVERFILL ALARM AND ACKNOWLEDGE SWITCH INSTALLATION: <br />CONTRACTOR TO INSTALL OVERFILL ALARM & ACKNOWLEDGMENT AS SHOWN. ALARM AND SWITCH TO BE LOCATED TO PROVIDE AN <br />UNOBSTRUCTED VIEW TO TRUCK DRIVER. PROVIDE BOLLARD PROTECTION OF FREE STANDING POLE. SEE SITE SPECIFIC WIRING DIAGRAM <br />AND DETAILS FOR MOUNTING REQUIREMENTS. <br />(16) VEEDER ROOT CONSOLE INSTALLATION: <br />CONTRACTOR TO INSTALL "VEEDER ROOT TLS -350 PLUS" TANK AND LINE ALARM CONTROL PANEL IN BUILDING. INSTALL PER <br />MANUFACTURER'S INSTALLATION INSTRUCTIONS. SEE ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR EXACT LOCATION IN BUILDING <br />CALIFORNIA VARIANT: TLS -350 PLUS CONSOLE TO BE EQUIPPED WITH ADDITIONAL SENSOR MODULES TO ADDRESS AB -2481 AND CARB ISD <br />REQUIREMENTS. <br />NYC VARIANT: CONSOLE TO BE PROGRAMMED FOR MASTER/MASTER ALTERNATE START <br />(17) CONCRETE SLAB INSTALLATION: <br />REFER TO PROJECT GENERAL SPECIFICATIONS FOR ADDITIONAL CONCRETE REQUIREMENTS NOT INDICATED ON THESE DRAWINGS. <br />STANDARD: <br />1. CONCRETE SLAB OVER TANKS WITH A MINIMUM 8" THICK FIBER REINFORCEMENT TO BE USED. REINFORCE CONCRETE SLAB <br />AROUND MANHOLES WITH (4) #4 REBAR, 60" IN LENGTH FOR THE LARGE MANHOLES AND 30" FOR SMALL MANHOLES <br />PLACE REBAR 6" FROM SIDES OF BOX. SEE RECIPE BELOW. <br />2. CONCRETE DRIVE SLAB AT CANOPY FUELING AREA WITH A MINIMUM 6" THICK FIBER REINFORCED CONCRETE TO BE USED. <br />SEE RECIPE BELOW. <br />3. CONCRETE FORMLESS ISLAND WITH A 6" HEIGHT ABOVE FINISHED GRADE FIBER REINFORCED CONCRETE TO BE USED. <br />SEE RECIPE BELOW. <br />NYC VARIANT: <br />1. CONCRETE SLAB OVER TANKS WITH A MINIMUM 10" THICKNESS AND BELOW TANKS WITH A MINIMUM 12" THICKNESS, <br />REINFORCED WITH TWO LAYERS OF 6X6-W5.5XW5.5 ON 2" STEEL CHAIRS TOP & BOTTOM. REINFORCE CONCRETE SLAB <br />AROUND MANHOLES WITH (4) #4 REBAR, 60" IN LENGTH FOR THE LARGE MANHOLES AND 30" FOR SMALL MANHOLES <br />PLACE REBAR 6" FROM SIDES OF BOX. SEE RECIPE BELOW. <br />2. LOAD BEARING 12"X16" CONCRETE BLOCK PIERS FILLED WITH TYPE "M" MORTAR SPACED NO MORE THAN 3'-2" APART. <br />FOR ALTERNATE SONOTUBE PIER CONFIGURATION A MINIMUM 16" DIAMETER CONCRETE PIER WITH #3 REBAR HORIZONTAL <br />TIES SPACED EVERY 2' VERTICALLY AND (5) #5 VERTICAL REBARS SPACE EQUALLY <br />3. CONCRETE DRIVE SLAB AT CANOPY FUELING AREA WITH A MINIMUM 6" THICK, REINFORCED WITH TWO LAYERS OF <br />6X6-W5.5XW5.5 ON 2" STEEL CHAIRS TOP & BOTTOM. <br />4. CONCRETE FORMLESS ISLAND WITH A 6" HEIGHT ABOVE FINISHED GRADE FIBER REINFORCED CONCRETE TO BE USED. SEE <br />RECIPE BELOW. <br />5. CONCRETE WALKWAY WITH A MINIMUM 4" THICK FIBER REINFORCED CONCRETE TO BE USED. SEE RECIPE BELOW. <br />6. CONCRETE DRIVEWAY WITH A MINIMUM 7" THICK FIBER REINFORCED CONCRETE TO BE USED. SEE RECIPE BELOW. <br />CALIFORNIA VARIANT: <br />1. CONCRETE SLAB OVER TANKS WITH A MINIMUM 8" THICK FIBER REINFORCEMENT TO BE USED. REINFORCE CONCRETE SLAB <br />AROUND MANHOLES WITH (4) #4 REBAR, 60" IN LENGTH FOR THE LARGE MANHOLES AND 30" FOR SMALL MANHOLES <br />PLACE REBAR 6" FROM SIDES OF BOX. SEE RECIPE BELOW. <br />2. THICKEN CONCRETE SLAB AT DISPENSER SUMPS AND TANK FILL AND TURBINE SUMPS SUCH THAT THE BOTTOM OF <br />CONCRETE IS BELOW THE TOP OF THE TERMINATION OF THE SECONDARY CONTAINMENT OF THE SUMPS PER AB -2481 <br />REQUIREMENTS. <br />3. CONCRETE DRIVE SLAB AT CANOPY FUELING AREA WITH A MINIMUM 6" THICK FIBER REINFORCED CONCRETE TO BE USED. <br />SEE RECIPE BELOW. <br />4. CONCRETE FORMLESS ISLAND WITH A 6" HEIGHT ABOVE FINISHED GRADE FIBER REINFORCED CONCRETE TO BE USED. <br />SEE RECIPE BELOW. <br />CONCRETE MIX RECIPE. PREMIX UNIFORMLY THROUGHOUT CONCRETE. REINFORCEMENT BARS TO BE NO LESS THAN 2" AND NO <br />MORE THAN 4" FROM SURFACE. <br />UNLESS OTHERWISE NOTED ON THESE DRAWINGS: <br />a. CONCRETE - REGULAR WEIGHT HARD ROCK CONCRETE (150 LBS/CU FT) <br />b. CEMENT - TYPE 1/II, SULFATE RESISTANT <br />c. AGGREGATES - ASTM C33, (MAXIMUM SIZE 3/4 INCHES) <br />d. 28 DAY CONCRETE STRENGTH (f'c): <br />4,000 PSI - SLAB (DESIGN BASED ON 2,000 PSI NO SPECIAL INSPECTION REQUIRED) <br />e. SLUMP - 311+ 1 " - 4" MAXIMUM AT POINT OF PLACEMENT <br />f. SHRINKAGE - 0.05% MAXIMUM <br />9. ENTRAINED AIR RANGE - 2% TO 4% <br />CONCRETE SHALL BE NORMAL WEIGHT WITH A MIX OF 1 : 2 1/2 : 3 1/2, WITH A MAXIMUM 7 1/2 GALLONS OF WATER PER <br />SACK. ADD 3.0 LB MARCO (STRUCTURAL) FIBER PER CU. YD. REINFORCING CONCRETE. <br />REINFORCING STEEL FOR TANK SUMP CAGES SHALL BE #4 REBAR. <br />MAINTAIN CONCRETE IN A MOIST CONDITION FOR AT LEAST 7 DAYS AFTER PLACEMENT. <br />PLACE CONCRETE DIRECTLY FROM TRUCK INTO FORMS. DO NOT PUMP CONCRETE UNLESS SPECIAL INSPECTION, IN ACCORDANCE WITH <br />CHAPTER 3 OF THE IBC, IS PROVIDED. <br />SUBMIT MIX DESIGNS, WITH STRENGTH AND SHRINKAGE TEST RESULTS, TO OWNER'S ENGINEER AT LEAST 7 DAYS BEFORE PLACING CONCRETE. <br />CONSOLIDATE CONCRETE IN PLACE USING A MECHANICAL VIBRATOR. <br />BEFORE PLACING CONCRETE, SECURE REINFORCING STEEL, ANCHOR BOLTS, DOWELS, AND OTHER INSERTS IN POSITION TO PREVENT <br />MOVEMENT. <br />MATERIALS AND WORKMANSHIP SHALL CONFORM TO A.C.I. - 318 (SPECIFICATIONS OF THE DESIGN AND PLACEMENT OF CONCRETE). <br />MANHOLE CROWNS: <br />ALL MANHOLE OPENINGS ON THE TANK SLAB SHALL BE INSTALLED WITH A 1-1/2" CROWN (1" RISE OVER 12" RUN) OF <br />CONCRETE TO PREVENT WATER INTRUSION INTO THE MANHOLE. THE OWNER'S ENGINEER, THE BP PROJECT MANAGER WILL BE <br />REQUIRED TO SIGN OFF ON THIS ITEM ON THE TANK INSTALLATION CHECKLIST. <br />PRODUCT IDENTIFICATION MARKINGS: <br />CONTRACTOR TO INSTALL PRODUCT IDENTIFICATION TAGS AT ALL MANHOLE OPENING PER SITE SPECIFIC DETAIL DRAWINGS. <br />(18) TESTING: <br />CONTRACTOR SHALL COMPLETE ALL TESTING ACCORDING TO MANUFACTURER'S INSTRUCTIONS FOR TANKS AND PIPING AND PER INDUSTRY <br />RECOMMENDED PRACTICES (API & PEI). CONTRACTOR SHALL COMPLETE ALL WARRANTY VALIDATION TESTING AND PROVIDE DOCUMENTATION TO <br />OWNER'S REPRESENTATIVE OR HIS AGENT, THE BP PROJECT MANAGER. <br />PIPE TESTING: <br />ISOLATE THE PRODUCT TANKS AND DISPENSERS DURING PRESSURE TESTING OF LINES IN ORDER TO PREVENT DAMAGE. <br />THE DESIGN, ASSEMBLY, AND TESTING OF THE PIPING SYSTEM SHALL BE IN CONFORMANCE WITH THE APPLICABLE SECTION <br />OF ANSI -1331, AMERICAN NATIONAL STANDARD CODE FOR PRESSURE PIPING, NFPA 30, FLAMMABLE AND COMBUSTIBLE <br />LIQUIDS CODE, AND AMERICAN PETROLEUM INSTITUTES RECOMMENDED PRACTICE 1615. <br />DURING CONSTRUCTION, BEFORE BACK FILLING, PIPING SHOULD BE ISOLATED FROM THE TANKS AND SUBJECTED TO A PIPE TIGHTNESS TEST. <br />OTHER TESTING METHODS MAY ALSO BE ACCEPTABLE IF APPROVED BY THE AUTHORITY HAVING JURISDICTION. A CONSTRUCTION PIPE TEST IS <br />CONDUCTED AS FOLLOWS: <br />A. THE PRODUCT PIPING TO BE TESTED IS ISOLATED AND PRESSURIZED WITH COMPRESSED AIR TO 150 PERCENT OF THE MAXIMUM SYSTEM <br />OPERATING PRESSURE (OR A MINIMUM OF 50 POUNDS PER SQUARE INCH GAUGE; MAXIMUM AS RECOMMENDED BY COMPONENT MANUFACTURER) <br />FOR AT LEAST 30 MINUTES AND NOT MORE THAN 1 HOUR. <br />B. ALL PIPING SURFACES INCLUDING VALVES, FITTINGS, JOINTS, AND SO FORTH ARE WETTED WITH A SOAP SOLUTION AND INSPECTED FOR <br />BUBBLES. <br />C. LEAKS, AS INDICATED BY BUBBLES, ARE REPAIRED OR REPLACED, AND THE PIPING RE -TESTED AS NECESSARY. <br />D. THE INNER PIPE WALLS SHALL BE TESTED FOR TIGHTNESS BEFORE CLOSING THE OUTER PIPE. THE OUTER PIPE MUST BE TESTED AT A 5 <br />POUNDS PER SQUARE INCH GAUGE MAXIMUM BEFORE BACKFILLING. CARE SHOULD BE TAKEN TO PREVENT OVER PRESSURIZATION OF THE <br />INTERSTICE. IT IS IMPORTANT THAT THE MANUFACTURER'S INSTRUCTIONS BE FOLLOWED. REPEAT BOTH TESTS AFTER BACKFILLING. <br />WHEN THE PIPING IS INSTALLED AND OPERATIONAL, A HYDROSTATIC TEST OF THE PIPING, AS SPECIFIED IN NFPA 329, MAY BE REQUIRED BY <br />CODES. <br />CAUTION: EXTREME CARE SHOULD BE EXERCISED IN CONDUCTING PIPE TIGHTNESS TEST. PRESSURIZED PIPING IS POTENTIALLY DANGEROUS <br />BECAUSE OF THE POSSIBILITY OF VIOLENT RUPTURE. THIS TEST SHOULD BE CONDUCTED WITH MINIMUM EXPOSURE OF PERSONNEL AND WITHOUT <br />MOVING OR DISTURBING THE PIPING BEING TESTED. WHEN THE TEST IS COMPLETED, THE PIPING PRESSURE CAN BE REDUCED OR RELEASED <br />COMPLETELY FOR THE REMAINDER OF CONSTRUCTION. REFER TO THE PIPING MANUFACTURER'S RECOMMENDATIONS. <br />N.O.V. PIPING SHALL BE TESTED ACCORDING TO MANUFACTURER'S SPECIFICATIONS. <br />VAPOR RECOVER PIPING MUST PASS ALL CARB BLOCKAGE TESTING RELATIVE TO TIGHTNESS, PRESSURE DECAY, & BLOCKAGE RATES. A/L TESTING <br />IS REQUIRED FOR "ASSISTED" STAGE II SYSTEMS (IF INSTALLED). NOTIFY THE BP PROJECT MANAGER TO COORDINATE. <br />CONTAINMENT SUMP TESTING: <br />ALL TANK SUMPS AND UNDER DISPENSER CONTAINMENT SUMPS SHALL BE HYDROSTATICALLY TESTED (LAKE TEST) WITH STANDING WATER <br />ABOVE THE LEVEL OF THE HIGHEST PIPE OR CONDUIT PENETRATION FOR A PERIOD OF 24 HOURS AFTER ALL WORK IS COMPLETED TO <br />INSURE THAT THE SUMPS ARE WATERTIGHT OR CERTIFIED USING SUMP MANUFACTURER'S APPROVED TEST PROCEDURE TO INSURE THAT <br />SUMPS ARE WATERTIGHT PER UST REGULATIONS. THE OWNER'S ENGINEER MUST SIGN OFF ON THIS TESTING ON THE TANK INSTALLATION <br />CHECKLIST. <br />CALIFORNIA VARIANT: ALL DOUBLE WALL SUMPS SHALL BE BRINE FILLED AND INSPECTED FOR TIGHTNESS THROUGHOUT THE INSTALLATION <br />PROCESS ONCE SUMPS HAVE BEEN FILLED WITH BRINE SOLUTION. <br />FINAL SYSTEM TESTING: <br />AFTER COMPLETE INSTALLATION OF THE ENTIRE FUEL SYSTEM AND ALL PAVING, THE OWNER'S REPRESENTATIVE OR HIS AGENT, THE BP PROJECT <br />MANAGER, SHALL ARRANGE FOR A PRECISION TANK AND LINE TEST TO BE PERFORMED ON THE COMPLETE SYSTEM. SUCCESSFUL COMPLETION OF <br />THIS TEST WILL BE REQUIRED FOR FINAL APPROVAL. THIS TEST SHALL ENSURE THAT ALL NEW TANK & PIPING SHALL MEET ALL FEDERAL, STATE, <br />& LOCAL REQUIREMENTS FOR TIGHTNESS INTEGRITY, PRIOR TO START-UP OF SYSTEM. OPERATIONALLY TEST ALL OTHER EQUIPMENT, INCLUDING <br />IMPACT (SHEAR) VALVES, LINK LEAK DETECTORS, LEAK DETECTOR ALARMS, AND EMERGENCY SHUTDOWN SWITCHES IN ACCORDANCE WITH THE <br />MANUFACTURER'S INSTRUCTIONS. CONTRACTOR SHALL PROVIDE (3) COPIES OF ALL CERTIFICATIONS & TEST RESULTS TO OWNER'S REPRESENTATIVE <br />OR HIS AGENT, THE BP PROJECT MANAGER. <br />TANK SYSTEM TEST METHOD CALIFORNIA ONLY AB -2481: <br />BEFORE THE UNDERGROUND STORAGE TANK IS PLACED INTO USE, THE UNDERGROUND STORAGE TANK SHALL BE TESTED AFTER <br />INSTALLATION USING ONE OF THE FOLLOWING METHODS TO DEMONSTRATE THAT THE TANK IS PRODUCT TIGHT: <br />1) ENHANCED LEAK DETECTION (ELD) BY TRACER CORPORATION. <br />2) AN INERT GAS PRESSURE TEST THAT HAS BEEN CERTIFIED BY A THIRD PARTY AND APPROVED BY THE BOARD. <br />3) A TEST METHOD DEEMED EQUIVALENT TO ENHANCED LEAK DETECTION OR AN INERT GAS PRESSURE TEST BY THE BOARD IN <br />REGULATIONS ADOPTED PURSUANT TO THE APPLICABLE CHAPTER IN THE CODE. AN UNDERGROUND STORAGE TANK INSTALLED AND TESTED <br />IN ACCORDANCE WITH THIS SECTION IS EXEMPT FROM THE REQUIREMENTS OF SECTION 25292.5. <br />(19) CHECKING FOR PRODUCT QUALITY: INITIAL SITE COMMISSIONING RECOMMENDED PRACTICES <br />BEFORE OPENING YOUR STORE, IT IS APPROPRIATE AND PROPER PROCEDURE TO CHECK YOUR FUELING EQUIPMENT TO MINIMIZE POSSIBLE <br />PRODUCT QUALITY ISSUES. THIS GUIDANCE MUST BE FOLLOWED TO ENSURE THAT PRODUCT QUALITY HAS BEEN MAINTAINED, AND IS <br />ACCEPTABLE FOR OUR CUSTOMERS. <br />THE UNDERLYING ASSUMPTION IS THAT THE GENERAL CONTRACTOR, WHO WAS RESPONSIBLE FOR BUILDING YOUR STATION, HAS PROPERLY <br />PERFORMED THEIR JOB AND CHECKED THAT TANKS AND PIPING HAVE BEEN PROPERLY INSTALLED, TESTED, CLEANED, AND LABELED AT A <br />MINIMUM. ANY BP AREA MAINTENANCE MANAGER, OR BP PROJECT MANAGER, HAS A CHECKLIST SHOWING KEY POINTS TO LOOK FOR <br />BEFORE ACCEPTING A SITE AS "COMPLETE" FROM THE CONTRACTOR. SOME KEY AREAS ARE AS FOLLOWS: <br />K�l�lyl:��f�7/�tl��:iil�:�/����:ii]:DI��Ltely7/\�/�:3��►■1►��11���:1_���.1��1��:����:�� <br />2. PERFORM A FINAL INSPECTION FOR THE PRESENCE OF WATER IN THE PIPING TO THE DISPENSERS BY OPENING THE TURBINE <br />DISCHARGE CONNECTION AT EACH TURBINE SUMP, AND OPENING/REMOVING THE BLEEDER/TEST PLUG ON IMPACT VALVE. ANY TRAPPED <br />LIQUIDS SHOULD DRAIN BACK TO THE TURBINE SUMP FOR REMOVAL. <br />3. CONFIRM THAT BOTH GASOLINE AND DIESEL DISPENSERS ARE INSTALLED WITH A MINIMUM (MEANING A MESH SIZE NOT GREATER <br />THAN) 10 MICRON FILTER. ANY FACTORY INSTALLED FILTER AFTER STARTUP MUST BE DISCARDED IN ACCORDANCE WITH USED FUEL <br />FILTER WASTE MANAGEMENT ENVIRONMENTAL GUIDELINES. <br />4. CONFIRM THAT PROPER DECALS, TAX NUMBERS, AND OTHER SIGNAGE REQUIRED PER PLANS, REGULATORY REQUIREMENTS, AND <br />CONTRACTUAL AGREEMENTS ARE INSTALLED. <br />5. PERFORM A FINAL INSPECTION FOR THE PRESENCE OF WATER WITHIN THE UNDERGROUND STORAGE TANKS, OR IN THE PIPING <br />GOING TO THE DISPENSERS. INSPECTION FOR WATER IN THE TANK SHALL BE PERFORMED USING SARGEL'S WATER FINDING PASTE (OR <br />EQUAL), AND CONDUCTED AT BOTH ENDS OF THE TANK. IF LEVELS OF WATER GREATER THAN 1/4" ARE DETECTED, PROCEED WITH <br />WATER ELIMINATION PROCEDURES, AND REQUEST THAT THE CONTRACTOR DO THIS AS PART OF THEIR SCOPE OF WORK. <br />6. THE BP REPRESENTATIVE (REGIONAL ACCOUNT EXECUTIVE OR FRANCHISE CONSULTANT) SHALL BE INFORMED OF ALL MAJOR <br />MILESTONES LEADING UP TO SITE START-UP. BP RESERVES THE RIGHT TO REQUEST COPIES OF INSPECTION REPORTS BEFORE INITIAL <br />SITE START-UP. <br />7. AFTER DELIVERY OF THE FIRST LOAD OF PRODUCTS, EACH PRODUCT MUST BE TESTED AND THE RESULTS PROVIDED TO THE BP <br />AREA MAINTENANCE MANAGER AND TO THE BP PROJECT MANAGER, PRIOR TO ANY SALE. <br />COSTS OF THE SAMPLING AND ANALYSIS ARE TO BE INCLUDED IN THE CONTRACTOR'S SCOPE OF WORK. A LABORATORY CERTIFIED TO <br />CONDUCT FUELS SAMPLING AND TESTING MUST BE USED. <br />(20) TANK ELECTRICAL SPECIFICATIONS: <br />GENERAL: <br />ALL MATERIALS AND WORKMANSHIP WILL CONFORM TO THE MOST RECENT EDITIONS OF THE NATIONAL ELECTRICAL CODE, N.E.T.A., B.I.C.S.I., <br />U.B.C. & NFPA AS REQUIRED BY THE ENGINEER, LOCAL AND STATE CODES AND ORDINANCES, AMERICANS WITH DISABILITIES ACT, E.P.A., <br />AND UTILITY COMPANY REQUIREMENTS. <br />THE CONTRACTOR WILL VISIT THE JOB SITE AND FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS WHICH MAY AFFECT HIS BID OR <br />WORK. NO ALLOWANCES WILL BE MADE AFTER THE BID FOR EXISTING CONDITIONS OR THE CONTRACTORS FAILURE TO VERIFY EXISTING <br />CONDITIONS. <br />FURNISH AND INSTALL A COMPLETE ELECTRICAL SYSTEM AS DEPICTED FROM THE PLANS AND SPECIFICATIONS HEREIN - AS NOTED OR <br />IMPLIED - NOT LIMITED TO WHAT IS SHOWN. <br />ALL DRAWINGS ARE SCHEMATIC IN NATURE AND ALL APPURTENANCES NOT INDICATED TO MAKE A WORKING SYSTEM MUST BE INCLUDED <br />IN CONTRACTOR'S BID. <br />IF THERE APPEARS TO BE ANY ITEMS IN CONFLICT WITH THE DRAWINGS INCONSISTENCIES WITH DESIGN OR INTENT OR NEED FOR <br />CLARIFICATION, IT IS THE CONTRACTOR'S RESPONSIBILITY TO CLARIFY THESE ITEMS PRIOR TO BID IN WRITING WITH THE ENGINEER. IF <br />THE CONTRACTOR FAILS TO CLARIFY ANY QUESTIONS OR INCONSISTENCY, THEY ACCEPT RESPONSIBILITY TO CORRECT AT THEIR COST ANY <br />SUCH ITEM SO AS TO MEET INTENT AS DEFINED BY ENGINEER. <br />UTI LITI ES: <br />CONTRACTOR WILL SUPPLY INFORMATION AS REQUIRED TO ALL SERVING UTILITIES IN A TIMELY MANNER TO PROVIDE SERVICE REQUIRED. <br />RSG FITTINGS & CONDUIT: <br />RGS FITTINGS MUST BE STEEL COMPRESSION TYPE; EACH WITH CODE SIZED COPPER BOND WIRE. MINIMUM CONDUIT 1" C. EXCEPT AS <br />NOTED. ALL WORK WILL BE IN CONDUIT; COMPLETED SYSTEM REAMED, AND SWABBED PRIOR TO CONDUCTOR INSTALL. <br />ALL CONDUITS TO BE CONCEALED EXCEPT TO SURFACE MOUNTED PANELS TIE WIRE, PERFORATED STRAPS, OR OTHER PIPING OR <br />CONDUIT ARE NOT ACCEPTABLE SUPPORTS. NO TIE WIRE WILL BE ALLOWED ON PROJECT. <br />CALIFORNIA VARIANT - THE LAST 2 FEET (MINIMUM) OF ALL CONDUITS THAT ARE ROUTED TO AND PENETRATE TANK SUMPS, DISPENSER <br />SUMPS AND VENT TRANSITION SUMPS SHALL BE PVC COATED RIGID STEEL GALVANIZED WHERE PENETRATIONS TO THE BRINE FILLED <br />SUMPS ARE MADE. ROBROY CONDUIT MUST BE USED WITH THE BRAVO PENETRATION FITTING - NO SUBSTITUTE PERMITTED. <br />CONDUCTORS: <br />CONDUCTORS TO BE 60OV., COPPER (98% CONDUCTIVITY). BRANCH CIRCUITS TO HAVE THHN/THWN GAS & OIL RESISTANT INSULATION. <br />CONDUCTORS WILL BE STRANDED, HYDRAULIC CRIMP ALL CONNECTIONS. CONDUCTOR INSULATION WILL BE CONTINUOUSLY COLOR COATED. <br />ALL GROUNDING/BUILDING CONDUCTORS WILL BE MULTI -CONDUCTOR TYPE (U.L. LABELED - ROPE STRAND BUILDING WIRE CLASS 'M') <br />BARE OR INSULATED AS NOTED OR REQUIRED. <br />MINIMUM LINE VOLTAGE WIRE SIZE IS #12 AWG (STRANDED) FOR LINE VOLTAGE WIRING DEVICES TO BE SPECIFICATION GRADE, <br />MINIMUM 20 AMPS FOR RECEPTACLES. HUBBELL OR ENGINEER APPROVED. ALL SPECIAL RECEPTACLES AND GROUND FAULT <br />PROTECTED DEVICES MUST BE PERMANENTLY MARKED WITH ENGRAVED COVER PLATES. <br />FILL RISER GROUNDING: <br />ALL RISERS IN THE FILL SUMP SHALL BE GROUNDED AND BONDED. <br />INSTALL 1/2" x 10'-0" LONG CONTINUOUS COPPER CLAD GROUND ROD IN NATIVE SOIL FOR TANK SYSTEM GROUNDING. PROVIDE <br />MANHOLE ACCESS TO GROUND ROD AND COPPER GROUND WIRE, SEE DETAILS ON SHEET G.0.7 <br />EMERGENCY SHUTDOWN: <br />ENSURE THAT THE <br />E -STOP <br />DISCONNECTS <br />THE HOT AND NEUTRAL WIRES TO THE DISPENSERS <br />ENSURE THAT THE <br />E -STOP <br />DISCONNECTS <br />THE HOT AND NEUTRAL WIRES TO THE TURBINES <br />ENSURE THAT THE <br />TURBINE <br />PUMPS ARE <br />ISOLATED TO AVOID FEEDBACK VOLTAGE <br />ENSURE THAT THE <br />E -STOP <br />DISCONNECTS <br />THE LOW VOLTAGE WIRES TO THE DISPENSER (I.E. DATA, INTERCOM, MEDIA) <br />ENSURE THAT THE <br />TURBINE <br />AND DISPENSER BREAKERS ARE CLEARLY IDENTIFIED / LABELED <br />ENSURE THAT EACH DISPENSER <br />HAS ITS <br />OWN DEDICATED CIRCUIT <br />ENSURE THAT EACH PUMP <br />HAS ITS OWN <br />DEDICATED CIRCUIT <br />ENSURE THAT THE <br />DISPENSING <br />EQUIPMENT <br />IS GROUNDED PER NEC <br />ENSURE THAT ALL OF THE DISPENSING EQUIPMENT MEETS NEC LOCK OUT/TAG OUT CODES. <br />CONTRACTOR PERFORMANCE: <br />THE CONTRACTOR WILL GUARANTEE ALL MATERIALS AND WORKMANSHIP FURNISHED BY HIM UNDER THIS CONTRACTOR FOR A PERIOD OF TWO <br />YEARS FROM THE DATE OF FINAL ACCEPTANCE OF THE WORK OF THIS CONTRACT BY THE OWNER AND THE ENGINEER AND PROVIDE A BOND TO <br />VALIDATE THIS GUARANTEE. ANY DEFECTS DEVELOPING WITHIN THE PERIOD TRACEABLE TO MATERIALS OR WORKMANSHIP PERFORMED HERE UNDER, <br />WILL BE MADE GOOD AT THE EXPENSE OF THE CONTRACTOR NOT THE OWNER OR ENGINEER. THE CONTRACTOR WILL ACCEPT AND FULLY <br />UNDERSTAND THIS PROVISION PRIOR TO CONTRACT BEING AWARDED, AS NO CLAIM FOR EXTRA COMPENSATION WILL BE ALLOWED FOR CORRECTION <br />OF FAULTY WORK OR DEFECTIVE MATERIALS. ANYTIME DURING THE CONSTRUCTION PERIOD, THE OWNERS REPRESENTATIVES AND THE ENGINEER <br />RETAIN THE RIGHT TO REQUIRE THE CONTRACTOR TO REMOVE AND REINSTALL ANY EQUIPMENT OR MATERIALS NOT FOLLOWING THE STANDARDS AS <br />PRESENTED HEREIN OR ON THE DRAWINGS WITHOUT COST TO THE OWNER OR ENGINEER. <br />CONTRACTOR WILL PROVIDE PROOF OF PERFORMANCE BOND WITH SHOP DRAWINGS <br />PROVIDE 3 SETS OF SHOP DRAWINGS & SAMPLES FOR ALL EQUIPMENT, PRIOR TO ORDERING AND IN A TIMELY MANNER (AS DETERMINED BY THE <br />ENGINEER) SO NOT TO DELAY WORK, TO THE ENGINEER FOR APPROVAL. (CONDUIT, SWITCHES, CONDUCTORS, ECT.) WHERE SUBSTITUTIONS ARE <br />MADE. CONTRACTOR WILL INCLUDE COMPARISON DATA & SAMPLES FOR BOTH THE SUBSTITUTE AND SPECIFIED ITEMS FOR REFERENCE PURPOSES. <br />CONTRACTOR WILL PROVIDE LETTER TO ENGINEER CONFIRMING ALL EQUIPMENT AND TERMINATIONS ARE PROPERLY TORQUED - SIGNED BY <br />LICENSED CONTRACTOR. <br />CONTRACTOR WILL PROVIDE ACCURATE AND COMPLETE "AS BUILT" DRAWINGS TO OWNER AND ENGINEER AT TIME OF OWNER ACCEPTANCE. ALL <br />"AS BUILT" DRAWINGS TO BE 4 SETS OF "BLUELINES" OR PHOTO COPY PRINTS 24" X 36" AND TWO SETS (OWNER/ENGINEER) ON MAGNETIC <br />MEDIA & AUTOCAD 2010 (BY AUTODESK) COMPATIBLE. FAILURE TO DO SO WILL CONSTITUTE FORFEITURE OF ALL PAYMENTS DUE AND HOURLY <br />RATES OR $99.00/HOUR/MAN MINIMUM TO ENGINEER PAID BY CONTRACTOR FOR "AS BUILT" DEVELOPMENT. <br />CLIENT: <br />4: bp <br />'Ad & <br />lir <br />ARCO <br />BP WEST COAST PRODUCTS, LLC <br />NO. <br />DATE <br />DESCRIPTION <br />0 <br />0 <br />A <br />0 <br />0 <br />0 <br />0 <br />0 <br />0 <br />io <br />0 <br />SEAL: <br />FESS /0 <br />Gf-�gp�l <br />NO. 36475 <br />* XP. 6-30-22 <br />ATF <br />OF- <br />z <br />Lu <br />2 <br />• <br />Lu co <br />co <br />Qco <br /><z 00 o <br />Z <br />z LU <br />00 <br />cnrnco <br />00 <br />UOQ <br />�QU <br />Lo <br />�m>}< <br />I I w w <br />v7LL <br />0 O z o <br />z U U o <br />Z <br /><w <br />LLJ< <br />z Q -- <br />06 <br />z 3 t <br />� <br />Q <br />w 00 w <br />o <br />0 <br />z = <br />2 0- <br />z <br />g <br />DEVELOPMENT INFORMATION: <br />SITE ADDRESS: <br />ADDRESS <br />2510 S. STATE HWY 99 W. FRONTAGE ROAD <br />SAN JOAQUIN COUNTY, CA 95205 <br />DESIGNED BY: <br />CHECKED BY: <br />DRAWN BY: <br />ER <br />DATE: <br />PROJECT NO: <br />10/23/2019 <br />DRAWING TITLE: <br />TANK AND PIPING <br />SCOPE OF WORK <br />AND GENERAL NOTES <br />(FRP 2 OF 3) <br />SHEET NO: <br />