Laserfiche WebLink
SAN JOAQUIN <br />CCUNT <br />Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />ESCALON MINI MART <br />1097 YOSEMITE AVE, ESCALON <br />December 21, 2021 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />310 <br />CCR 2636(f)(4) Failure to meet monitoring requirements in lieu of being tightness tested every 12 months. <br />OBSERVATION: The monitoring equipment does not provide positive shut down and does not meet the <br />requirements for annual line tightness testing exemption. The monitoring system does not shut down the turbine <br />pump in the event of a power outage, or when the monitoring system fails or is disconnected. <br />REGULATION GUIDANCE: All pressurized piping with secondary containment shall be pressure tested at least <br />once every 12 months at a minimum release detection of 0.1 gallons per hour at 150 percent of the normal <br />operating pressure. Continuous monitoring systems that are fail safe and shut down the pump when a leak is <br />detected, or optionally stop the flow of product at the dispenser if the leak is in the under dispenser containment <br />(UDC), shall satisfy the requirement for annual line tightness testing. <br />CORRECTIVE ACTION: Immediately schedule an annual line tightness test and provide 48 hours notification to the <br />EHD. <br />This is a Class II violation. <br />319 <br />CCR 2635, 2637.2, 2665, 2712 Failure to comply with overfill prevention equipment requirements. <br />OBSERVATION: The fill tube shut off valve used as the overfill prevention system is not currently functional on the <br />87 UST. Per the 11/15/2021 Overfill prevention test result; the 87 overfill prevention equipment failed. <br />REGULATION GUIDANCE: All UST systems must be equipped with an approved, functional overfill prevention <br />device at all times during delivery operations. <br />CORRECTIVE ACTION: Immediately discontinue deposition of petroleum into this tank until the component is <br />repaired or replaced by a properly licensed, trained, and certified contractor under permit and inspection of the EHD. <br />If the failed component can't be replaced immediately, there is a possibility that the 87 UST system may be red <br />tagged to prevent fuel inputs. <br />This is a repeat violation, Class ll. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by 01/21/2022 . <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in -office CERS help will be provided at EHD hourly rate <br />($152). To schedule an appointment, please call (209) 468-3420. <br />Documents provided during inspection: Free CUPA Class Flyer, Return to Compliance Certification, Official <br />Inspection Report <br />------------ <br />FA0000279 PR0231497 SCO01 12/21/2021 <br />EHD 23-01 Rev. 12/06/2021 Page 5 of 6 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />