Item No. 12 <br /> P/C 10-6-77 <br /> 5-78-1 <br /> Page 4 <br /> 2. Gate valves shall be so located that no single case of accident, <br /> breakage or repair to the pipe system, exclusive of arteries will <br /> necessitate the shut down of an artery or a length of pipe greater <br /> than 800". <br /> Hydrant Distribution <br /> 1. One hydrant shall be provided for each 120,000 square feet served <br /> by the system. Approximately 500' separation between hydrants. <br /> 2. Hydrants shall meet specifications of the Woodbridge Fire Department. <br /> 3. Street connections *hall be not less than 6" in diameter. <br /> 4. A gate valve shall be provided on all connections between hydrants <br /> and street mains. <br /> Reliability of Supply <br /> 1. Pumps shall, if possible, receive electrical power from separate <br /> sources to insure reliability. <br /> 2. Automatic motor driven power sources or adequate storage sources <br /> may be considered in lieu of the two separate sources of public utility <br /> power. <br /> - Pacific Gas & Electric Company <br /> - Pacific Telephone & Telegraph Company <br /> - Surveyor <br /> - Flood Control <br /> - Air Pollution Control District <br /> - Delta College District <br /> - Woodbridge Fire District - The tentative subdivision map of Fairway Estates <br /> has been received and reviewed by this department. The following comments <br /> and recommendations should be reviewed by your committee. <br /> 1. Water Supply: The required fire flow shall be 1000 gallons per minute <br /> for a duration of two hours. Minimum residual water pressure of 20 PSI <br /> is required during flow. <br /> 2. Water Mains: Minimum size of mains shall be 8 inch. The system shall <br /> be installed so that a single break in any feature of the supply works <br /> will not prevent delivery of maximum daily consumption plus standard fire <br /> flaws. Sufficient valves shall be provided so that no single accident break- <br /> age or repair will necessitate shutting down a length of pipe greater than <br /> 800 feet. <br /> 3. Fire Hydrants: Hydrants installed shall conform to the standard American <br /> Water Works Association. They shall have two 2�" inch outlets, a 4;j" inch <br /> Pumper outlet and a 6" inch street main connection, properly valved. A gate <br /> valve shall be provided between Hydrant and street mains. Hydrants shall be <br />