Laserfiche WebLink
Hi Case, <br /> Thank you for the email. I will give it to the area inspector. <br /> Thank you, <br /> Ge*%.eyi y Marl-i,vvea I Sr. Office Assistant <br /> San Joaquin County Environmental Health Department <br /> 1868 E. Hazelton Ave. Stockton, CA 95205 <br /> (209)468-02171A (209) 468-34331 El gmartinez@sigov.org <br /> EHD Website: https://www.sigov.org/department/envhealth/ <br /> From: Case Gilson<case@armer-norman.com> <br /> Sent:Tuesday, September 13, 2022 7:28 AM <br /> To: EH-UST<ust@sigov.org> <br /> Cc: Keith Powers<Keith.Powers@aIbertsons.com>;Tyler Olea <Tyler.0lea@albertsons.com>;Aldo Basurto <br /> <aldo.basurto@safeway.com> <br /> Subject: Safeway 2707, 6425 Pacific Ave, Stockton-Secondary Containment 2022 <br /> Good day SJCEHD HazMat/UST <br /> I am writing to align on secondary containment status at the subject facility. Recent 36-mo periodic testing <br /> documented "fail" for all secondary piping pressure integrity and UDC hydrostatic integrity but the testing was <br /> attempted with all secondary piping termination boots removed. With the new drip-floor UDC adapter frames <br /> at the site, the UDC necks are now significantly closed and thus the piping termination boots are not accessible <br /> from grade for secondary testing. <br /> To make the UDCs and the secondary piping testable, valved secondary jumpers will be installed for all <br /> termination boots. This configuration allows each UDC to act as "point of earliest detection" containment <br /> 2 <br />