Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMPIUDC TEST <br /> Test Method Developed by ❑ Manufacturer N Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: INCON STS <br /> Sump/UDC ID 87 STP 91 STP 87 Fill 91 Fill <br /> Sump Manufacturer <br /> Sump Depth (inches) 78 78 79 83 <br /> Sump Bottom to Top of 12 12 10 10 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:49 9:49 9:49 9:49 <br /> Initial Reading 2.7449 3.6684 4.8920 7.5210 <br /> Test End Time 10:04 10:04 10:04 10:04 <br /> Final Reading 2.7450 3.5685 4.8921 7.5209 <br /> Change in Reading 0.0001 0.0001 0.0001 0.0001 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results M Pass ❑ Fail N Pass ❑ Fail N Pass ❑ Fail N Pass ❑ Fail <br /> Sump1UDC ID UDC 112 UDC 314 UDC 516 UDC 718 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 32 32 32 32 <br /> Sump Bottom to Top of 10 10 10 10 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:22 11:22 11:22 11:22 <br /> Initial Reading 4.2153 4.0149 5.9780 4.8839 <br /> Test End Time 11:37 11:37 11:37 11:37 <br /> Final Reading 4.2157 4.0150 5.9791 4.8845 <br /> Change in Reading 0.0004 0.0001 0.0011 0.0006 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> [Tightness Test Results N Pass ❑ Fail N Pass ❑ Fail N Pass ❑ Fail N Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked"Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />